LK11series
IntelligentLightbarController
Instructionmanual
ⅠApplication
LKseriesisakindofintelligentandprecisionaldigitalindicator&controller.Itcanworkwithmutualinductor,sensorandtransmittertomakeupvariouscontrolsystemofdifferentrangeandspecificationfortemperature,pressure,liquid,torque,ampere,voltetc..Itcanmeasurevolt,ampere,tacho,frequency,etc.,andconnecttoPLCaswell.Pleaseindicatewhenordering.
ⅡFunction
Hand/Autoconvertwithoutinterference
Positive/Negativefunctionofheatingorcoolingselectedbysoftware
Ampliturelimitonoutputsignal
CombinationoffuzzyandtraditionalPIDcontrol,Highpreciseauto-tuningtoensurehigh
Speedresponse,lowovershootandhighaccuracy.what’smore,ithasgoodcontrolover
longtime-delaysystemwhichisdifficulttocontrolbyregularPID.
ⅢTechnicalparameters
Error:
0.2%FS±1digit,14digitA/Dconvertor(18digitA/Dconvertoratmost,indicatewhen
ordering)
InputSignal:
·TC:
B、S、K、E、J、T、WRetc.
·RTD:
Pt100、Cu50、Cu53、Cu100、BA1、BA2
·Ampere:
0~10mA,4~20mA;etc.(Inputimpedance≤250Ω)AC0-5A
·Voltage:
0~5V,1~5V;etc.(Inputimpedance≥1MΩ)
·Remotetransmitpressureresistor:
(0~400)Ω
Samplingspeed:
0.2s(10~200/sec,setbyuser)
Display:
Dualline4digitLEDdisplaywithlightbar,Lightbardisplaysthepercentage.
Alarmoutput:
Upto16alarms,eachcircuithashigh&lowalarmoutput.Relayoutputcapacity:
AC220V/3AorAC220V/1A。
Analogoutput:
4~20mA、0~10/20mA(Loadresistance≤250Ω,othersshouldbe
indicatewhenordering)
1~5V、0~5V/10V,(Loadresistance≥200KΩ)
12bitdigitalD/AIC,isolatedoutput
Communication:
RS485/RS422/RS232/Modem
Baudrate——300~9600bps
Auxiliarypower:
DC24V/30mA,DC12V/30mA
PowerSupply:
Switchpower85~265VACor24VDCor12VDC
PowerConsumption:
4W
AmbientEnvironment:
(-20~70)℃(inabout30minutesafterpoweron,thebearableultimatetemperature)
(0~50)℃<85%RH
Panelsize:
160mm×80mm、96mm×96mm、96mm×48mm
ⅣCodeIllustration
ⅤDiagram
⑴LK11Standard:
80×160×125size
Note:
1.WhenRTD,remotetransmitpressureresistorinput,itshouldadopts3-wireconnection
2.Otherspecialrequestedmeter,pleaserefertothediagramshowingonthemeter.
ⅥOperation
(⒈)Keyfunction
●—Handprintkeyorotherspecialfunction
■—Insettingestate,presstoquitthemenu.
En—parametersettingkey.Insettingestate,presstosavethevalueandentertonextparameter.
▲—UPkey.Insettingestate,presstoincreasethevalue
▼—DOWNkey.Insettingestate,presstodecreasethevalue
(⒉)Self-check
⑴Wellconnecttheterminalsforpower,input,outputandalarmsaccordingtothediagram.
⑵Re-checkthewiringsbeforeturningonthepower.
⑶Turnonthepower.Youcanentertheparametersettingbyman-machineinteractivemode.
(3)Parameterssetting:
Insettingestate,upLEDdisplayssignsofparameters,downLEDdisplayssettingvalue.
Indisplayingestate,upLEDdisplaysmeasuringvalue,downLEDdisplayssettedvalue.
PressEnkey>1stoenterthesettingestate.Press▲/▼tomodifythepassword,andpressEntoconfirmandenterthesettingestate.Thenyoucansettheparametersonebyone.
(1)J1HA:
J1alarmvaluesetting(whenJ1-H=OFF,inactive)
(2J1HF:
J1alarmresetvaluesetting.(whenJ1-H=OFF,inactive)
(3)J2HA:
J2alarmvaluesetting(whenJ1-H=OFF,inactive)
(4)J2HF:
J2alarmresetvaluesetting.(whenJ1-H=OFF,inactive)
J3,J4areofthesameoperation.
Afterthealarmsetting,youshouldinputpasswordtoenterthe2ndparametersettingmenu.
(5)cd-Password,Press▲/▼tomodifythepasswordfrom800to808,andpressEntoconfirmandenterthesettingestate.Thenyoucansettheparametersonebyone.
(6)Sn—Inputsignalselection。
Note:
signalchart(normallytheitemdetectsthesignalautomatically,noneedtoadjust.mAsignalconnectsnoresist)
(7)dot—Decimalpointsetting,range:
0~3,eg.Ifdot=2,thevaluedisplaysinXX.XXformat.ForTC/RTDinput,dot=0/1only.Itmeanstheresolutionis0.1℃,Theresolutionchangeto1℃whenthetempisover1000℃.
Parameter
Inputsignal
Parameter
Inputsignal
tc―K
K
rtd
Resistor0-400Ω
tc―S
S
bA1
BA1
tc―E
E
bA2
BA2
tc―b
B
0―50
0―50mV
tc―t
T
0―5V
0―5V
tc―n
N
1―5V
1―5V
tc―J
J
0―20
0―20mA
P100
Pt100
0―10A
0―10mA
C100
Cu100
4―20
4―20mA
Cu50
Cu50
Othersshouldindicate
(8)inPL—Lowlimitdisplayvalueforlinearityinput,range:
-1999~9999。
(9)inPH—Highlimitdisplayvalueforlinearityinput,range:
-1999~9999
(10)J1-H—J1relayalarmmode.
J1-H=-HH-,meanshighalarm
J1-H=-LL-,meanslowalarm
J1-H=-OFF-,meansalarminactive
J2,J3,J4alarmmodeissubjecttothis
(11)bS—analogoutputmode,1~5V、0~5V、4~20mA、0~10mA、0~20mAavailable,
(12)bS-L—lowanalogoutputdisplayvalue
(13)bS-H—Highanalogoutputdisplayvalue
(14)oSEt—Zeropointcalibrationrate,displayvaluePV=PVF+oSEt,factorysetting:
oSEt=0.0
(15)FSEt—Fullpointcalibrationrate,range:
0.500~2.000,displayvaluePV=FSEt×(PVF+oSEt),factorysetting:
FSEt=1.000.
(16)Lb—Digitalfilteringparameter,Range:
0~10,0meansnofiltering.1meansforaveragevalue.2-10meansforcombinationofaveragevalueand2ndintegralvalue.ThelargertheLbvalue,themoresteableofmeasuringvalue,theslowertheaction.YoucanenlargetheLbwhenthereexistbiginterference.YoucansetLbto0/1tospeedtheactionwhenyoucalibratethemeter.
(17)Addr—Communicationaddress,range:
1~99.
(18)bAUd—Communicationbaudrate,range:
1200~9600.
(19)LdiS—whattodisplayinthe2ndLEDwindow,itcanbe.J1HA、J2HA、J3HA、J4HA、Addr、
OFF
LdiS=OFF,thenthe2ndwindowhasnodisplay
LdiS=Addr,thenthe2ndwindowdisplaythecommunicationaddress,
-EndintheUPLEDmeanstheendofsetting
ⅦAlarm
Thisitemcanhaveseveralrelay,alarmmode:
Hi,Low,NOalarm.Thehysteresisvaluesettingcanavoidfrequenton-offofrelay.Whentherelayisonalarmingestate,therelaywillactive,andindicatelampon.
Forexample:
J1:
J1-H=-HH-,theitementeralarmingestatewhenPVF>J1HA;
WhenPVFfallsbacktoJ1HA,theitemwon’tstopalarming.OnlywhenPVF.J1HF.
J1-H=-LL-,theitementeralarmingestatewhenPVFWhenPVFgrowuptoJ1HA,theitemwon’tstopalarming.OnlywhenPVF.>J1HFthealarmingstops.Under-LL-mode,J1HAⅧAnalogoutput
Theoutputmodeissettedbyparameter“bS”.
Theanalogoutputrangeissettedbyparameters“bS-L”&“bS-H”.
Eg.InputsignalPT100,requiretemp0℃outputs4.0mA,when150℃outputs20.0mA,thenbS=4-20,bS-L=0.0,bS-H=150.0.Whenthetempis75.0℃,theoutputis12.0mA.
ⅨCommunication
RS232、RS485interfaceisavailableforconnectionwithPCdirectly.
ForRS485interface,thedistancecanbeasfaras1.5Km&connetabletoseveralmeters.
ForRS232interface,thedistanceiswithin15m&connetabletoonemeteronly.
Modbusprotocolcanconnecttoalmostconfigurablesoftware.
Datastructure:
Startbit=1,Databit=8,,calibration,Stopbit=1
ⅩModbusprotocol
TheinstrumentadoptsstandardModbusprotocol.Whenconfigurationsoftwareisapplicated,pleaseselectMODICONPLC,Modbus-RTUaddress.Thereare16digitsintotal.Itstartsfrom4001,whenusingkingviewregister;Otherconfigurationsoftwaremaystartfrom3001.
CodeParameterMeans
4x0001PVMeasuringvalue
4x0002J1J1alarmestate
4x0003J2J2alarmestate
4x0004J3J3alarmestate
4x0005J4J4alarmestate
Eg.Readmeasuringvaluefrominstrumentaddressed01,(PV1=1000)
Sendorder:
01030000000184OA,
Returndata:
01030203E8B8FA(03E8—1000)
01istheaddressofinstrument(settedbyparameterAddr),03isCOM(FUNCTIONno),0000isthebeginningaddressforregister,0001isthefirstvaluetocount,84,OAisCRCcalibrationcode.Ifyouwanttoread(B8,FAinthisexample)
ToreadPV,J1HA,sendorder:
010300000002C40B.