AnExperimentonEnergyReductionofanExhaustAirHeatRecoveryTypeOutdoorAirConditioningSystemforSemiconductorManufacturingCleanRooms
Kyung-HoonYoo1,Gen-SooSong1,Hyung-TaeKim1,Seung-WooSon2andDug-JunPark3
1NanoscaleContaminationControlLaboratory,KoreaInstituteofIndustrialTechnology
(KITECH),1271-18,Sa-1-dong,Ansan-si,426-171,Gyeonggi-do,SouthKorea
2SunglimPSCo.,1301,NamseongPlaza,345-30,Gasan-dong,Geumcheon-gu,Seoul,153-802
3ShinsungENGCo.,404-1,Baekhyeon-dong,Bundang-gu,Seongnam-si,463-420
ABSTRACT
Inrecentsemiconductormanufacturingcleanrooms,theenergyconsumptionofanoutdoorairconditioningsystemrepresentsabout45%ofthetotalairconditioningloadrequiredtomaintainacleanroomenvironment.Meanwhile,thereisalargeamountofexhaustairfromacleanroom.Fromanenergyconservationpointofview,heatrecoveryfromtheexhaustairisthereforeusefulforreducingtheoutdoorairconditioningloadforacleanroom.Inthepresentwork,anenergy-efficientoutdoorairconditioningsystemwasproposedtoreducetheoutdoorairconditioningloadbyutilizinganairwashertorecoverheatfromtheexhaustair.Theproposedoutdoorairconditioningsystemconsistedmainlyofapre-heater,anairwasher,twostagecoolingcoils,areheatingcoil,ahumidifierandtwoheatrecoverycoolingcoilsinsertedintotheairwasherandconnectedtoawetscrubber.Itwasshownfromthelab-scaleexperimentwithoutdoorairflowof1,000m3/hthattheproposedsystemwasmoreenergy-efficientforthesummerandwinteroperationsthananoutdoorairconditioningsystemwithasimpleairwasher.
KEYWORDS:
SemiconductorManufacturingCleanRoom,OutdoorAirConditioningSystem,AirWasher,HeatRecovery,EnergyReduction.
Introduction
Forrecentsemiconductormanufacturingcleanrooms,theenergyconsumptionofanoutdoorairconditioning(hereafterOAC)systemrepresentsabout45%ofthetotalairconditioningloadrequiredtomaintainacleanroomenvironment[1,2].Inaddition,thereisalargequantityofexhaustairfromacleanroom,leadingtotheconsequentlargeamountofwasteheat.Fromanenergysavingpointofview,heatrecoveryfromtheexhaustairisthereforehelpfulforreducingtheoutdoorairconditioningloadforacleanroom.Recently,airwashershavebeensometimesusedinOACsystemsforsemiconductormanufacturingcleanroomstocontrolhumidityandsimultaneouslyremovesuspendeddustsandgaseouscontaminantssuchasNH3,SOx,NOxandorganicgasesinincomingoutdoorair,asshowninFigure1.Meanwhile,sincetheexhaustaircarrieschemicallytoxicgaseousmatter,awetscrubberhastobeusedtohandleitbeforeitisdischargedtotheatmosphere.Inthewetscrubbertheheattransferbetweentheexhaustairandthescrubbingwateralwaystakesplace.Thetransferredheatdeservesutilizingtoheatorcooltheincomingoutdoorair,whichneedstobecontactedindirectlywiththescrubbingwaterbecauseofprotectionfromcontamination.
Figure1.Schematicdiagramoftheproposedenergyefficientoutdoorairconditioningsystemwithanairwasherofheatrecoveryfunction.
SofaronlyafewstudiesregardingtheairwasherwiththeheatrecoveryfunctionforsemiconductorcleanroomshavebeenconductedbyFujisawaetal.[3,4],Shiromaetal.[5]andYamamotoetal.[6].NoneoftheabovementionedpublicationsseemstohavebeendescribedsufficientlyindetailtoallowtheunderstandingoftheoverallenergyconsumptionandsavingperformanceoftheOACsystem.Theyfocusedonlyonheatrecoveryequipment,notontheOACsystemitself.Thereforetheeffectofairconditioningprocessconstraintssuchassupplyairconditionandthecombinationwithheating/coolingcoilsontheenergysavingperformanceofanenergy-efficientOACsystemdesignneedstobetakenintoaccount.Inthepresentwork,anenergy-efficientOACsystemwasproposedtoreducetheoutdoorairconditioningloadbyutilizingtheairwasherwithheatrecoveryfunctionbasedonthepreviousworkbyFujisawaetal.[3,4]andYamamotoetal.[6].TheproposedOACsystemconsistedmainlyofairfilters,apre-heater,anairwasher,twostagecoolingcoils,areheatingcoil,ahumidifier,andtwoheatrecoverycoolingcoilsinsertedintotheairwasherandconnectedtoawetscrubber,asshowninFigure2.Anexperimentwascarriedoutonthelab-scalewithanairflowof1000m3/hregardingenergyconsumptionandsavingoftheproposedenergy-efficientOACsystemcomparedwiththeOACsystemwithasimpleairwasher.
ExperimentalMethods
Figure2.Schematicdiagramofthepresentexperimentalapparatusfortheenergy-efficientoutdoorairconditioningsystemwithheatrecoveryfunction.
Figure2showstheschematicdiagramoftheoverallexper