UC-KB-2008可燃气体报警控制器及UC-KT-2010型可燃气体探测器培训手册.doc
《UC-KB-2008可燃气体报警控制器及UC-KT-2010型可燃气体探测器培训手册.doc》由会员分享,可在线阅读,更多相关《UC-KB-2008可燃气体报警控制器及UC-KT-2010型可燃气体探测器培训手册.doc(21页珍藏版)》请在冰豆网上搜索。
UC-KB-2008D型气体报警控制器
目录
1.引言·····························································2
1.1简述·······················································2
技术指标···················································2
主要功能···················································3
2.安装····························································5
2.1安装尺寸···················································5
2.2安装方式···················································5
2.3接线·······················································5
3.操作说明························································6
3.1面板说明···················································6
工作状态说明···············································7
4.使用调整························································8
5.报警处理························································8
6.故障诊断与处理··················································8
7.维护维修·······················································9
1.引言
本手册详细阐明了如何安装、操作、维护UC-KB-2008型可燃气体报警控制器(见图1)。
1.1简述
UC-KB-2008可燃气体报警控制器(以下简称控制器),它与具有防爆性能的UC-KT-2010型可燃气体探测器(以下简称探测器)配合使用。
探测器固定安装在可能有可燃气体泄露的室内、外危险场所。
控制器接受探测器传来的电信号,并对之进行滤波、模数转换、线性化、浓度计算等一系列处理工作,得到当前可燃气体的浓度值。
当浓度值达到预先设定的报警值时,控制器即可发出声、光报警及控制信号,提示操作人员采取安全对策或自动启动相关设备,从而避免发生爆炸事故。
控制器具有比较完善的自诊断功能,可对系统的各种故障进行处理,以便及时维修。
控制器设计符合国标GB16808-1997《可燃气体报警控制器技术要求和试验方法》,经过公安部消防产品合格评定中心评定,获得产品型式认可证书,编号:
073064851134ROS。
经过北京市相关质量技术监督部门的考核,获得制造计量器具许可证,证号:
京[制]01120010号。
1.2技术指标
供电电压:
交流(187~242)V。
检测范围:
(0~99)%LEL。
线性误差极限:
±5%LEL。
功耗:
≤30W。
工作温度:
(0~40)℃
工作湿度:
≤95%
通道容量:
1点
报警设置:
低限报警25%LEL,高限报警50%LEL(用户可自行设定)
触点输出:
每路探头有高、低限报警均有2组无源常开触点(电容量220V2A)
标定气样:
甲烷(或由用户指定)
传输距离:
≤1km(线阻小于20Ω)
箱体规格:
170mm×54mm×200mm
重量:
1kg
1.3主要功能
1.各通道均可独立设置其工作状态,包括通道单位、量程、报警上下限设定值等。
2.各通道上下限报警均对应相应的联动输出。
3.控制器具有自检功能,可对机器的重要部件和面板上所有指示灯进行检查。
4.当有下列情形之一时,控制器能在30s内发出与报警信号有明显区别的声、光故障信号:
a,探测器与控制器连接线断路。
b,探测器内部元件失效。
c,控制器主要元件失效。
图1控制器外观尺寸
图2控制器安装开口尺寸
2安装
2.1安装尺寸(如图2)
2.2安装方式
将控制器插入监视面板的开口处,然后用上下两个长螺杆将控制器固定在监视面板上。
控制器没有防爆性能,安装位置应远离危险场所。
2.3接线
控制器的后端盖,可见如图3的接线端子板。
电源线(接线端子L、N):
电源电压220VAC,电源线应采用仪表用动力电缆,线径在1.0mm2以上。
接地线电阻不大于10Ω。
注意:
L-火线,N-零线
信号线:
信号线采用3芯仪表用控制电缆,线径及传输距离见表1。
将控制器上的P,S,G分别与探测器的P,S,G相连。
表1 线径及传输距离
电缆横截面(mm)
0.75
1.0
1.5
最远传输距离(M)
500
750
1000
注意:
1、控制器与探测器连接时,注意控制器P,S,G与探测器P,S,G相对应,切勿接反!
2、安装布线工程应符合GB50093-2002《工业自动化仪表施工验收规范》或《中华人民共和国危险场所电气安装规范》。
联动输出接线:
每一检测通道有两个报警控制输出,高限报警的控制输出端子为D、E,低限报警的控制输出接线端子为A、B。
输出信号为无缘触点信号,联动接线线径应根据所连接设备的具体情况选定(不可直接接220VAC)。
图3控制器接线板示意图
3、操作说明
3.1面板说明
3.1.1面板示意图(见图4)
图4操作面板示意图
3.1.2指示灯说明(见表2)
表2指示灯说明
指示灯说明
颜色
功能
高限报警
红
发生高限报警时,该指示灯亮;返回监控态后,按复位键熄灭。
低限报警
红
发生低限报警时,该指示灯亮;返回监控态后,按复位键熄灭。
故障
黄
探测器存在故障时,该指示灯亮
电源
绿
控制器通电时,该指示灯亮
3.1.2指示灯说明(见表3)
表3功能键说明
键名
功能
消声
当控制器发生报警或故障时,按下此键可以消除声音报警/故障信号。
复位
按下此键,可使控制器所有报警/故障复位。
自检
当控制器处于监控状态时,按下此键,即对控制器面板指示灯、显示器、声报警进行功能检查。
3.2工作状态说明
3.2.1系统初始化状态
控制器加电,控制器进入系统初始化,此时“通道”,“%LEL”。
初始化状态大约持续100秒后,系统进入监控状态。
3.2.2监控状态
在监控状态下,“%LEL”显示相应通道的浓度值,同时“电源”指示灯亮。
3.2.3自检态
在监控状态下,按自检键,进入自检状态。
此时,面板上所有的指示灯和LED都点亮,蜂鸣器响。
3.2.4报警态
在监控状态下,如通道的可燃气体浓度超过低限报警浓度,控制器即进入报警态。
此时低限报警指示灯亮,“%LEL”显示相应浓度值,同时报警蜂鸣器响。
若通道的可燃气体报警浓度超过高限报警值,则高限报警指示灯亮。
报警后处理措施见<5.报警处理>。
3.2.5故障态
在监控状态下,若通道或控制器内部发生故障,控制器即进入故障态。
此时故障指示灯亮,故障蜂鸣器响。
故障诊断与处理见<6.故障诊断与处理>。
使用调整
在检查安装接线准确无误后,打开电源开关,控制器进入系统初始化状态,大约100秒后,进入监控状态。
如果控制器存在故障,按《6故障诊断与处理》进行处理。
如果存在零点漂移,按《4.4零点调整》进行调整。
报警系统进入正常运行状态。
4.1零点调整
若某一通道的零点漂移过大(超过5%LEL),则必须进行零点调整。
零点调整可用一字型螺丝刀调整相应通道的零点调整电位器(顺时针增大),使得当前通道的浓度在0±1%LEL之间摆动即可。
报警处理
5.1在监控状态下,控制器进行巡检。
当通道发生报警时,控制器进入报警状态。
当发生报警的通道达不到报警浓度时,控制器返回监控状态。
、
在报警状态下,按“消声”键,清除报警蜂鸣声,同时消声指示灯亮,当控制器返回监控状态后,消声指示灯灭;在消声状态,再按一次“消声”键,消声状态清除,报警蜂鸣器响,消声指示灯灭。
故障诊断与处理
6.1在故障状态下,故障指示灯亮。
此时可以按“消音”键去除故障声音信号。
在故障状态下,“%LEL”显示“--”说明该通道有故障。
可采取以下措施排除通道故障。
检查控制器与探测器的连线是否正常;
若连线无误,用万用表测量S、G间电压在0.2~1V之间.若有异常则表示探测器故障;若无异常,请通知本公司进行处理。
故障处理完后,可以按“复位”键返回监控态。
7.维护维修
警告:
在进行维护之前必须保证周围环境不存在爆炸或有毒气氛!
7.1日常维护
当系统安装完成后,在正常使用过程中,应由专业人员每年对探测器进行二至三次标准气调校,检查控制器动作是否正常。
若探测器达到使用年限,应及时更换,否则容易造成零漂过大、误报等问题,影响正常生产活动。
注意环境清洁,如防尘、防水,防油烟等。
UC-KT-2010型气体探测器
目录
1.简述······························································2
2.技术指标··························································3
3.安装接线··························································4
4.维护维修·························································6
1简述
UC-KT-2010型可燃气体探测器(以下简称探测器,如图1)主要由传感器、信号处理电路板和隔爆外壳组成。
探测器固定安装在油库、液化气站,喷漆车间、燃气配输等可燃气体生产、使用、贮存等室内外危险场所。
探测器为隔爆型,其设计符合国标GB3836.2-2000《爆炸性气体环境用电气设备-第2部分:
隔爆型“d”》,经化学工业电气产品防爆质量监督检验中心检验合格,防爆证号:
CE061187,防爆标志:
ExdIICT6;
探测器经过北京市相关质量技术监督部门的考核,获得制造计量器具许可证,证号:
京[制]01120010号。
经过公安部消防