杭州汽轮机股份有限公司

2004/10/20

GOVERNORSERIALNUMBER:

APPLICATION:

山东机械设备进出口集团公司

TURBINESTART

MANUALSTART?

YesNodflt=NO(Yes/No)

IfYES,selectsamanualstartmodewheretheoperatorcontrolstheturbinespeedfromzerouptotheminimumcontrolspeed.TheStartSequencewouldbe:

PushRUN.Theactuatorsautomaticallymovetomax.position.Lastly,theoperatorslowlyopenstheT&

Tvalveuntilthegovernortakescontrol.

AUTOMATICSTART?

YesNodflt=NO(Yes/No)

IfYES,selectsanautomaticstartmodewherethe505controlstheturbinespeedfromzerouptotheminimumcontrolspeed.TheStartsequencewouldbe:

OpentheT&

Tvalve,thenpushRUN.TheHPvalvelimiteropensautomaticallyuntilthegovernortakescontrol.

SEMIAUTOMATICSTART?

YesNodflt=NO(Yes/No)

IfYES,selectsasemiautomaticstartmodewherethe505valvelimitermustbeopenedslowlybytheoperatortoopenthecontrolvalveandbringtheturbinespeedfromzerouptotheminimumcontrolspeed.TheStartSequencewouldbe:

Tvalve,thenpushRUN.Thevalvelimitermustthenberaisedbytheoperatoruntilgovernortakescontrol.

(Oneofthethreestartmodesmustbeselectedbeforetheunitwillrun)

RATETOMIN=RPM/SECdflt=10.0(0.1,500)

Rateatwhichspeedsetpointmovestolowestcontrollingspeedonstart.Themincontrollingspeedwillbeeither'

idle'

ifidle/ratedisused,or'

lowidle'

iftheautostartsequenceisused.Ifneitherofthisstartupfeaturesisused,theminspeedwillbetheminimumgovernorspeedsetpoint.

HPVALVELIMITERRATE=1%/SECdflt=5.0(0.1,25)

Rateatwhichthevalvelimitermoves.Whenusingasemiautomaticorautomaticstart,thissettingshouldbeveryslow--typicallylessthan2%/sec.Whenusingamanualstart,thissettingislesscriticalandcanbeleftatthedefaultof5%/sec.

USEIDLE/RATED?

YesNodflt=NO(Yes/No)

IfNO,skiptoUseAutoStartSequence.IfYES,thecontrolwillrampfromaprogrammableIdlespeedtoaprogrammableRatedspeedsetpointwhenRatedisselectedthroughkeypad,ModBusorexternalswitch.

IDLESETPT=600RPMdflt=1000(0.0,20000)

LowestcontrolsetpointwhenusingtheIdle/Ratedfunction.

RATEDSETPT=2820RPMdflt=0.0(0.0,20000)

(Mustbegreaterthanorequaltothe'

MinimumGovernor'

Setting)

IDLE/RATEDSETPTRATE15RPM/SECdflt=5.0(0.1,100)

RateatwhichthespeedsetpointmovesbetweenIdleandRatedspeedsetpointswhen

usingtheIdle/Ratedcommands.

USEAUTOSTARTSEQUENCE?

YesNodflt=No(Yes/No)

IfYESandrunisselected,the505automaticallyacceleratesthespeedsetpointtoaprogrammablelowidlespeedandholdsforprogrammabletimethenrampstoaprogrammablehighidlespeedandholdsforaprogrammabletimethenrampstoaprogrammable

ratedspeedsetpoint.Thestartsequencecanbeactuatedorhaltedthroughthekeypad,ModBusorexternalswitch.

COLDSTART(>

xxHRS)=HRSdflt=10(0.0,200)

Ifthismuchtimehasexpiredafteratripcondition,thenthecontrolwillusethecoldstartvalues.Iflessthanthistimehasexpired,thecontrolwillinterpolatebetweenthehotandcoldstartvaluestodetermineratesandholdtimes.

HOTSTART(<

xxHRS)=HRSdflt=1.0(0.0,200)

Maximumtimeallowedafteratripforthehotstartsequencecurvestobeused.Iflessthanthistimehasexpiredthenthecontrolwillusethehotstartvalues.

(Mustbelessthanorequaltothe'

ColdStart'

Hours)

LOWIDLESETPT=RPMdflt=1000(0.0,20000)

Thefirstholdspeedwhenusingtheautomaticstartsequence.Thespeedsetpointwillremainatthissettinguntilthelowidledelay/holdtimehasexpired.

LOWIDLEDELAY(COLD)=MINdflt=1.0(0.0,500)

Programmabletimeinminutestheturbinewilldelayatthelowidlespeedwhenacoldstarthasbeendetermined.

LOWIDLEDELAY(HOT)=MINdflt=1.0(0.0,500)

Programmabletimeinminutestheturbinewilldelayatthelowidlespeedwhenahotstartisdetermined.IftheturbinehasbeenshutdownforlongerthantheHottimebutshorterthantheColdtime,thecontrolwillinterpolatebetweentheHotandColddelaystodeterminethelowidleholdtime.

LowIdleDelay-Cold'

RATETOHIIDLE(COLD)=RPM/SECdflt=1.0(0.1,100)

ProgrammablerateatwhichtheSpeedsetpointwillrampfromlowidlespeedtohighidlespeedwhenacoldstartisdetermined.

RATETOHIIDLE(HOT)=RPM/SECdflt=1.0(0.1,100)

ProgrammablerateatwhichtheSpeedsetpointwillrampfromlowidlespeedtohighidlespeedwhenahotstartisdetermined.IftheturbinehasbeenshutdownforlongerthantheHottimebutshorterthantheColdtime,thecontrolwillinterpolatebetweentheHotandColdratestodeterminetheaccelerationratetothehiidlesetpoint.

RatetoHiIdle-Cold'

HIIDLESETPT=RPMdflt=0.0(0.0,20000)

Thesecondholdspeedwhenusingtheautomaticstartsequence.Thespeedsetpointwillremainatthissettinguntilthehiidledelay/holdtimehasexpired.

(Mustbegreaterthan'

LowIdle'

Setting)

HIIDLEDELAYTIME(COLD)=MINdflt=1.0(0.0,500)

Programmabletimeinminutestheturbinewilldelayatthehighidlespeedwhenacoldstarthasbeendetermined.

HIIDLEDELAYTIME(HOT)=MINdflt=1.0(0.0,500)

Programmabletimeinminutestheturbinewilldelayatthehighidlespeedwhenahotstartisdetermined.IftheturbinehasbeenshutdownforlongerthantheHottimebutshorterthantheColdtime,thecontrolwillinterpolatebetweentheHotandColddelaystodeterminethehiidleholdtime.

HiIdleDelay-Cold'

RATETORATEDSETPT(COLD)=RPM/SECdflt=5.0(0.1,100)

ProgrammablerateatwhichtheSpeedSetpointwillrampfromhighidlespeedtomin

governorspeedwhenacoldstartisdetermined.

RATETORATEDSETPT(HOT)=RPM/SECdflt=5.0(0.1,100)

ProgrammablerateatwhichtheSpeedSetpointwillrampfromhighidlespeedtomingovernorspeedwhenahotstartisdetermined.IftheturbinehasbeenshutdownforlongerthantheHottimebutshorterthantheColdtime,thecontrolwillinterpolatebetweentheHotandColdratestodeterminetheaccelerationratetotheratedsetpoint.

RatetoRated-Cold'

RATEDSETPT=RPMdflt=3600(0.0,20000)

AUTOHALTATIDLESETPTS?

YesNodflt=No(Yes/No)

SelectYESfollowedbyENTERkeytoautomaticallyhalttheautostartsequencesattheidlesetpoints.SelectNOtoallowthecontroltoperformitsautomaticstartsequenceroutinewithoutinterruption.

EXTERNALTRIPINTRIPRELAY?

YesYNodflt=Yes(Yes/No)

SelectYESfollowedbyENTERkeytoallowtheexternaltripinput(s)tode-energizetheTripRelayoutput.WhensettoNO,anexternaltripcontactinputtothe505Ewillshutdownthe505Econtrolbutwillnotde-energizethe505E’striprelayoutput.

RESETCLEARSTRIPOUTPUT?

YesYNodflt=No(Yes/No)

WhenYes,aResetcommandwillenergizethetriprelayoutputevenwhenatripconditionisstillsensedbythe505E-typicallyduetotheexternaltripinput.WhenNO,thetriprelayoutputwillbede-energizedona505Etripandwillnotenergizeuntilalltripshaveclearedanda‘Reset’commandisgiven.

SPEEDCONTROL

NOTE

Themaximumturbinespeedis20000rpmandthemaximumspeedinputfrequencyis15000hertz.

TEETHSEENBYMPU=60dflt=60.0(1,300)

Numberofteethongearthatthespeedprobeismountedon.

MPUGEARRATIO=1.0dflt=1.0(0.05,200)

TheratiooftheMPUgeartotheturbineshaft.ThisgearratioistheresultofdividingthespeedoftheMPUgearbythespeedoftheturbineshaft.

FAILEDSPEEDLEVEL=RPMdflt=250(0.5,1000)

Speedprobeinputfailurelevel.Ifspeeddropsbelowthislevelthecontrolwilldeterminethespeedinputdeviceisfailed.

(Mustbegreaterthanorequalto0.0204xOverspeedTestLimitsetting)

USESPEEDINPUT#2?

YesNodflt=NO(Yes/No)

SpeedInputfailurelevel.Ifspeeddropsbelowthislevelthecontrolwilldeterminethespeedinputdeviceisfailed.

OFF-LINEPROPORTIONALGAIN=5.0dflt=5.0(0.0,100)

Usedtosetspeed/loadcontrolresponse,whentheGenandUtilitybreakercontactsareopenandtheturbinespeedisbelowMin.governorspeedorwhentheSelectDynamicsfunctionisusedandthecontactisopen.

OFF-LINEINTEGRALGAIN=0.5dflt=0.5(0.0,50)

Usedtosetspeed/loadcontrolresponsewhentheGenandUtilitybreakercontactsareopenandtheturbinespeedisbelowMingovernorspeedorwhentheSelectDynamicsfunctionisusedandthecontactisopen.

OFF-LINEDERIVATIVERATIO=100dflt=5.0(0.01,100)

Usedtosetspeed/loadcontrolresponsewhentheGenandUtilitybreakercontactsareopenandtheturbinespeedisbelowMin.governorspeedorwhentheSelectDynamicsfunctionisusedandthecontactisopen.

ON-LINEPROPORTIONALGAIN=5dflt=5.0(0.0,100)

Usedtosetspeed/loadcontrolresponsewhentheGENandUtilitybreakercontactsareclosed(ifGENset)ortheturbineisaboveMin.governorspeed(ifnotaGENset)orwhentheSelectDynamicsfunctionisusedandthecontactisclosed.

ON-LINEINTEGRALGAIN=0.5dflt=0.5(0.01,50)

Usedtosetspeed/loadcontrolresponsewhentheGENandUtilitybreakercontactsareclosed(ifGENset)ortheturbineisaboveMin.governorspeed(ifnotaGENset)orwhentheSelectDynamicsfunctionisusedandthecontactisclosed.

ON-LINEDERIVATIVERATIO=100dflt=5.0(0.01,100)

Usedtosetspeed/loadcontrolresponsewhentheGENandUtilitybreakercontactsareclosed(ifGENset)or