1、 杭州汽轮机股份有限公司2004/10/20GOVERNOR SERIAL NUMBER:APPLICATION:山东机械设备进出口集团公司 TURBINE STARTMANUAL START? Yes No dflt= NO(Yes/No)If YES, selects a manual start mode where the operator controls the turbine speed from zero up to the minimum control speed. The Start Sequence would be: Push RUN. The actuators a
2、utomatically move to max. position. Lastly, the operator slowly opens the T&T valve until the governor takes control.AUTOMATIC START? Yes No dflt= NO(Yes/No)If YES, selects an automatic start mode where the 505 controls the turbine speed from zero up to the minimum control speed. The Start sequence
3、would be: Open the T&T valve, then push RUN. The HP valve limiter opens automatically until the governor takes control.SEMIAUTOMATIC START? Yes No dflt= NO(Yes/No)If YES, selects a semiautomatic start mode where the 505 valve limiter must be opened slowly by the operator to open the control valve an
4、d bring the turbine speed from zero up to the minimum control speed. The Start Sequence would be:T valve, then push RUN. The valve limiter must then be raised by the operator until governor takes control. (One of the three start modes must be selected before the unit will run)RATE TO MIN= RPM/SEC df
5、lt=10.0(0.1,500)Rate at which speed setpoint moves to lowest controlling speed on start. The min controlling speed will be either idle, if idle/rated is used, or low idle, if the auto start sequence is used. If neither of this startup features is used, the min speed will be the minimum governor spee
6、d setpoint.HP VALVE LIMITER RATE= 1 %/SEC dflt=5.0(0.1,25)Rate at which the valve limiter moves. When using a semiautomatic or automatic start, this setting should be very slow-typically less than 2%/sec. When using a manual start, this setting is less critical and can be left at the default of 5%/s
7、ec.USE IDLE/RATED? Yes No dflt= NO(Yes/No)If NO, skip to Use Auto Start Sequence. If YES, the control will ramp from a programmable Idle speed to a programmable Rated speed setpoint when Rated is selected through keypad, ModBus or external switch.IDLE SETPT= 600 RPM dflt=1000(0.0,20000)Lowest contro
8、l setpoint when using the Idle/Rated function.RATED SETPT= 2820 RPM dflt=0.0(0.0,20000)(Must be greater than or equal to the Minimum Governor Setting)IDLE/RATED SETPT RATE 15 RPM/SEC dflt=5.0(0.1,100)Rate at which the speed setpoint moves between Idle and Rated speed setpoints when using the Idle/Ra
9、ted commands.USE AUTO START SEQUENCE? Yes No dflt=No(Yes/No)If YES and run is selected, the 505 automatically accelerates the speed setpoint to a programmable low idle speed and holds for programmable time then ramps to a programmable high idle speed and holds for a programmable time then ramps to a
10、 programmable rated speed setpoint. The start sequence can be actuated or halted through the keypad, ModBus or external switch. COLD START(xx HRS)= HRS dflt=10(0.0,200)If this much time has expired after a trip condition, then the control will use the cold start values.If less than this time has exp
11、ired, the control will interpolate between the hot and cold start values to determine rates and hold times. HOT START(xx HRS)= HRS dflt=1.0(0.0,200)Maximum time allowed after a trip for the hot start sequence curves to be used. If less than this time has expired then the control will use the hot sta
12、rt values.(Must be less than or equal to the Cold Start Hours)LOW IDLE SETPT= RPM dflt=1000(0.0,20000)The first hold speed when using the automatic start sequence. The speed setpoint will remain at this setting until the low idle delay/hold time has expired.LOW IDLE DELAY (COLD)= MIN dflt=1.0(0.0,50
13、0)Programmable time in minutes the turbine will delay at the low idle speed when a cold start has been determined.LOW IDLE DELAY (HOT)= MIN dflt=1.0(0.0,500)Programmable time in minutes the turbine will delay at the low idle speed when a hot start is determined. If the turbine has been shutdown for
14、longer than the Hot time but shorter than the Cold time, the control will interpolate between the Hot and Cold delays to determine the low idle hold time.Low Idle Delay-ColdRATE TO HI IDLE(COLD)= RPM/SEC dflt=1.0(0.1,100)Programmable rate at which the Speed setpoint will ramp from low idle speed to
15、high idle speed when a cold start is determined.RATE TO HI IDLE(HOT)= RPM/SEC dflt=1.0(0.1,100)Programmable rate at which the Speed setpoint will ramp from low idle speed to high idle speed when a hot start is determined. If the turbine has been shutdown for longer than the Hot time but shorter than
16、 the Cold time, the control will interpolate between the Hot and Cold rates to determine the acceleration rate to the hi idle setpoint.Rate to Hi Idle-ColdHI IDLE SETPT= RPM dflt=0.0(0.0,20000)The second hold speed when using the automatic start sequence. The speed setpoint will remain at this setti
17、ng until the hi idle delay/hold time has expired.(Must be greater than Low Idle Setting) HI IDLE DELAY TIME(COLD)= MIN dflt=1.0(0.0,500)Programmable time in minutes the turbine will delay at the high idle speed when a cold start has been determined.HI IDLE DELAY TIME(HOT)= MIN dflt=1.0(0.0,500)Progr
18、ammable time in minutes the turbine will delay at the high idle speed when a hot start is determined. If the turbine has been shutdown for longer than the Hot time but shorter than the Cold time, the control will interpolate between the Hot and Cold delays to determine the hi idle hold time.Hi Idle
19、Delay-ColdRATE TO RATED SETPT(COLD)= RPM/SEC dflt=5.0(0.1,100)Programmable rate at which the Speed Setpoint will ramp from high idle speed to min governor speed when a cold start is determined.RATE TO RATED SETPT(HOT)= RPM/SEC dflt=5.0(0.1,100)Programmable rate at which the Speed Setpoint will ramp
20、from high idle speed to min governor speed when a hot start is determined. If the turbine has been shutdown for longer than the Hot time but shorter than the Cold time, the control will interpolate between the Hot and Cold rates to determine the acceleration rate to the rated setpoint.Rate to Rated-
21、ColdRATED SETPT= RPM dflt=3600(0.0,20000)AUTO HALT AT IDLE SETPTS? Yes No dflt= No(Yes/No)Select YES followed by ENTER key to automatically halt the auto start sequences at the idle setpoints. Select NO to allow the control to perform its automatic start sequence routine without interruption.EXTERNA
22、L TRIP IN TRIP RELAY? Yes Y No dflt= Yes (Yes/No)Select YES followed by ENTER key to allow the external trip input(s) to de-energize the Trip Relay output. When set to NO, an external trip contact input to the 505E will shut down the 505E control but will not de-energize the 505Es trip relay output.
23、RESET CLEARS TRIP OUTPUT? Yes Y No dflt= No(Yes/No)When Yes, a Reset command will energize the trip relay output even when a trip condition is still sensed by the 505E-typically due to the external trip input. When NO, the trip relay output will be de-energized on a 505E trip and will not energize u
24、ntil all trips have cleared and a Reset command is given. SPEED CONTROLNOTEThe maximum turbine speed is 20000 rpm and the maximum speed input frequency is 15000 hertz.TEETH SEEN BY MPU= 60 dflt=60.0(1,300)Number of teeth on gear that the speed probe is mounted on.MPU GEAR RATIO= 1.0 dflt=1.0(0.05,20
25、0)The ratio of the MPU gear to the turbine shaft. This gear ratio is the result of dividing the speed of the MPU gear by the speed of the turbine shaft.FAILED SPEED LEVEL= RPM dflt=250(0.5,1000)Speed probe input failure level. If speed drops below this level the control will determine the speed inpu
26、t device is failed.(Must be greater than or equal to 0.0204 x Overspeed Test Limit setting)USE SPEED INPUT#2? Yes No dflt= NO(Yes/No)Speed Input failure level. If speed drops below this level the control will determine the speed input device is failed.OFF-LINE PROPORTIONAL GAIN= 5.0 dflt=5.0(0.0,100
27、)Used to set speed/load control response, when the Gen and Utility breaker contacts are open and the turbine speed is below Min. governor speed or when the Select Dynamics function is used and the contact is open.OFF-LINE INTEGRAL GAIN= 0.5 dflt=0.5(0.0,50)Used to set speed/load control response whe
28、n the Gen and Utility breaker contacts are open and the turbine speed is below Min governor speed or when the Select Dynamics function is used and the contact is open.OFF-LINE DERIVATIVE RATIO= 100 dflt=5.0(0.01,100)Used to set speed/load control response when the Gen and Utility breaker contacts ar
29、e open and the turbine speed is below Min. governor speed or when the Select Dynamics function is used and the contact is open.ON-LINE PROPORTIONAL GAIN= 5 dflt=5.0(0.0,100)Used to set speed/load control response when the GEN and Utility breaker contacts are closed(if GEN set) or the turbine is abov
30、e Min. governor speed (if not a GEN set) or when the Select Dynamics function is used and the contact is closed.ON-LINE INTEGRAL GAIN= 0.5 dflt=0.5(0.01,50)Used to set speed/load control response when the GEN and Utility breaker contacts are closed (if GEN set) or the turbine is above Min. governor speed (if not a GEN set) or when the Select Dynamics function is used and the contact is closed.ON-LINE DERIVATIVE RATIO= 100 dflt=5.0(0.01,100)Used to set speed/load control response when the GEN and Utility breaker contacts are closed (if GEN set) or