Fireprotection–High-risebuilding-Designrequirements
1Scopeofapplication
ThisStandardspecifiesbasicrequirementsforfirefightingandprotectionwhendesigningfornewconstruction,renovationorenlargementofhigh-risecivilworks..
ThisStandardisnotappliedforconstructionworkswithheightover100mandtheaters,gymnasiumsandmeetinghalls.
2.Extractedstandards
TCVN2622:
1978Firefightingandprotectionforhousesandbuildings–Designrequirements
TCVN5738:
1993Firealarmsystem–Technicalrequirements
TCVN5760:
1993Fire-fightingsystem–Generalrequirementsfordesign,installationandutilization
TCVN5717:
1993Lightningprotectionrods
TCVN4756:
1989Normsofelectricalequipmentgroundingandairing.
3Terminologyanddefinitions
3.1High-risebuildingsrefertobuildingsandpublicworkswithheightfrom25mto100m(equivalentto10floorsto30floors)
3.2Buildingheightistheheightcalculatedfromsidewalksurfacetotheloweredgeoftheguttersoreaves.
Topofmachineroom,watertank,machineroomoflift,mechanicalequipment,smoke-exhaustingequipmentontheroofshallnotbeincludedintheheightornumberoffloorsofhigh-risebuildings.
Basementorhalf-undergroundbasementofwhichtheceilingishigherthantheoutersidewalksurfacebynotmorethan1.5m,shallnotbeincludedinthenumberoffloorsofsuchhigh-risebuilding.
4Generalregulations
4.1Thefire-fightingandprotectiondesignforhigh-risecivilworksshallconformtotherequirementsinthisstandardandotherrelevantfirefightingandprotectionstandards.
4.2Whendesigningfirefightingandprotectionfornewconstruction,renovationorenlargementofhigh-risebuildings,itisrequiredtobaseontheplanningofthewholeareaorsectionandcloselycoordinatewiththefire-fightingandprotectiondesignsolutionoftheadjacentwork(arrangementoftrafficroads,fire-fightingwatersupplypipelinesystem,firealarminformation,etc.)
High-risebuildingdesignshallbeapprovedfordesignandfire-fightingequipmentbytheauthoritiesconcerned.
5.Requirementsforfireresistance
5.1High-risebuildingsshallbedesignedwithFire-resistantRate1andminimumfire-resistantlimitofthemaincomponentsaswellasmaterialsformakingsuchcomponentsasstatedinTable1
Table1
Buildingfire-resistantrate
Fire-resistantlimit,minutes
Supportingwallcolumn,liftchamberwall,fireprotectionwall
Landing,stairsandotherliftcomponents
Nonsupportingouterwall
Nonsupportinginnerwall(partition)
Floorplateandotherfloorsupportingcomponents
Floorplateandotherroofsupportingcomponents
I
150
60
30
30
60
30
Note:
Thesteelstructureforbasement,roofandfloorshallbeprotectedbynon-flammablematerials/componentswithfireresistantlimitnotlessthan60min.
5.2Theminimumfireresistantlimitofotherfireprotectionpartsisasfollows:
-Door,windowandgateatfire-protectionwallshallbemadeofnon-flammablematerialswithfireresistantlimitnotlessthan45minutes.
-Thefireprotectionpartitionsshallbemadeofnon-flammablematerialswithfireresistantlimitnotlowerthan45minutes.
-Door,windowatfireprotectionpartition,fireprotection;firedoortobasement,roofdoorshallbemadeofnon-flammablematerialswithfireresistantlimitnotlessthan40minutes.
-Fireprotectionfloor(floorbetweenstoreys,floorofcellar,floorofmezzanine)shallbemadeofnon-flammablematerialswithfireresistantlimitnotlessthan60minutes.
5.3Forotherdoors,windows,roofdoors,floorsandpartitionswhicharenotstatedinItems5.1,5.2andwall/ceilingdecorationobjects,itisallowedtobemadeofflammablematerials.
5.4Loadresistantcomponentsofstairs(beam,landing,stair)shallbemadeofnon-flammablematerialswithfireresistantlimitnotlessthan60minutes.
5.5Wallandflooroftheliftwellarrangedindoorsshallbemadeofnon-flammablematerialswithfireresistantlimitnotlessthan60minutes.
Inthecaseofbeingarrangedoutdoors,suchwallsandfloorsshallbemadeofnon-flammablematerialswithfireresistantlimitnotlessthan30minutes.
5.6Roofsofthebuildingsareallowedtobemadeofflammableheat-insulatingmaterialsonthesurfaceofconcreteslabs,concretebeamsandcementasbestossheets.
5.7Inapartment-styledbuildings,thepartitionsbetweenunits/blocksshallbemadeofnon-flammablematerialswithfire-resistantlimitnotlessthan60minutes.Thepartitionsbetweenapartmentsshallbemadeofnon-flammablewithfire-resistantlimitnotlessthan40minutes.
5.8Partitionsinmid-corridorofthebuildingshallbemadeofnon-flammablematerialswithfire-resistantlimitnotlessthan30minutes.
5.9Floorandceilingwhichseparatewall-footstoryshallbemadeofnon-flammablewithfire-resistantlimitnotlessthan90minutes.
5.10Liftchamberfloor,lobbywithpassagefromstairsorlobbytoaspaceshallbemadeofnon-flammablewithfire-resistantlimitnotlessthan60minutes.
6.Fireprotectionrequirements
6.1Eachstoreyofhigh-risebuildingshallbedividedintocompartments.EachcompartmentshallhavemaximumareaasstatedinTable2
Table2
Typeofhousesandbuildings
Max.allowedareaofeachcompartment,m2
-Houses,hotelswithmorethan19storeysandotherpublicworkswithheightfrom50mupwards.
-Houses,hotelsfrom10to18storeysandotherpublicworkswithheightunder50m.
-Basement
1000
1500
500
Note:
-AreaofeachcompartmentstatedinTable2canbedoubledifsuchcompartmentsaredesignedwithautomaticfirefightingsystem.Incaseautomaticfirefightingsystemisdesignedforpartofahold,theareaofsuchpartshallbedoubled.
6.2Thefireprotectionwallsshallbebuiltfromfoundationorfoundationbeamuptotopofbuildingheight,cuttingthroughallcomponentsandfloors.Itisallowedtobuildfireprotectionwalldirectlyonframestructureiftheframefire-resistantlimitislargerthanthatofthefireprotectionwall.
6.3Thefireprotectionwallshallbeensuredofdurability,notbeingcollapsedwhenthereisimpactfromonesideduetotheburningoffloor,rooforothercomponents.
6.4Nodoorshallbearrangedatfireprotectionwalls.Incaseitisnecessarytoarrangedoorsatfireprotectionwalls,therequirementinItem5.2shallbemet.
6.5Itisnotallowedtoplaceflammablegas/liquidconductpipesthroughthefireprotectionwall,floororpartition.
6.6Forotherservicepipes,whenplacingthemthroughthefire-protectionwall,floororpartition,itisrequiredtoplaceautomaticfireprotectionvalveatthepenetrationtopreventthefirefromspreadingalongthepipes.Aroundthepipeslocatedclosetothefireprotectionwall,floorandpartition,itisrequiredtoplasterwithnon-flammablemortarwithfireresistantlimitequivalenttothatoffireprotectionwall,floororpartition.
6.7Thestructuressurroundingliftwells,machinerooms,ditches,wells,nicheswhereconduitpipesareinstalledshallensurefireprotectionrequirementswithfireresistantlimitnotlessthan100minutes.Whenplacingbufferingholdsforthelift,thepartitionsshallhaveafire-resistantlimitnotlessthan45minutes.
6.8ItisnotpermittedtoarrangefireprotectionwallsatthetransitioncornerofaU-shapedorL-shapedhigh-risebuilding.Incaseafireprotectionwallispositionedclosetoatransitioncorner,thedistancebetweenthewindowandthefireprotectionwallshallnotbelessthan4m.Ifthewindowismadeofnon-flammablematerialswithfireresistantlimitnotlessthan60minutes,nodistanceshallberestricted.
6.9Toensurenofirespreading,afireprotectionwallshallbedesignedbetweenfloors.Theservicespipesconnectingafloortoanothershallbemadeofnon-flammablematerialsandacheckplatemustbeavailableoncerequired.
7Planarrangement
7.1High-risebuildingshallensureafire-fightingandprotectionspaceconformingtoTCVN2622:
1978andshallhaveanemptyareainfrontofthewaysoutatFloor1(Groundfloor)forsafeexit.ConstructionareaandmaximumlengthofthebuildingisstipulatedinTable3.
Table3
Typeofhigh-risebuilding
Constructionarea,m2
Maximumlength,m
Withfireprotectionwall
Withoutfireprotectionwall
Notstipulated
2200
Notstipulated
110
7.2Inabuildingwherethereareshop-windows,publicroom,kindergarten,roomseparationshallbemadewithnon-flammablewallandfloorwithfireresistantlimitnotlessthan45minutes.
7.3Oil,gasfurnaces,transformers,highvoltageelectricequipmentshallnotbeplacedinhigh-risebuildingsbutinaseparateroomoutside.
Inspecialcasewhenitisrequiredtoplacetheminside,then
1)thegas,oilfurnacesshallnotbeplacedabove,nexttoorbeneathacrowdedroom.Thepartitionsbetweenthefurnacesandotherroomsshallbemadeofnon-flammablematerialswithfireresistantlimitnotlessthan150minutes.Floorandotherseparatedpartsshallalsobemadeofnon-flammablematerialswithfireresistantlimitnotlessthan60minutes.
2)thefurnaces,transformersshallbelocatedinFloor1withdirectexit.
3)equipmentusingoilmusthaveoilspillageroomstructure.
7.4Roomstobeusedashall,kindergartenshallonlybelocatedinFloors1,2or3andneartheexits.
7.5Roomswhichareoftencrowdedwithpeopleshallnotbelocatedinthebasement.Ifitisnecessarytolocateinthebasement,thentheroomareashallnotbelargerthan300m2andthereshallbeatleast2directexits.
7.6Ifacar-parkislocatedinahigh-risebuildin