Annex01 ScopeTSOutdoor Cabinet to BASE文档格式.docx
《Annex01 ScopeTSOutdoor Cabinet to BASE文档格式.docx》由会员分享,可在线阅读,更多相关《Annex01 ScopeTSOutdoor Cabinet to BASE文档格式.docx(14页珍藏版)》请在冰豆网上搜索。
BatteryCabinets
b.Thecabinetshouldpossessafan–cooledoraDCAirConditionedsystem
c.Cabinetmanufacturershallprovideareturnpolicyattheendofthecabinetlife.
d.Externalambienttemperatureonsiteswherethesystemsaretobeimplementedisexpectedtorangefrom30°
Cto40°
C.
e.Thecabinetmustpossess:
∙ProvisionforMains,DG,DCDG,Solar,BatteryBank
∙ACDB
∙DCDB
∙Electro-mechanicalLock
∙SpaceforRectifierModules
∙SpaceforMicrowaveTransmissionRack
∙SpaceforBTS
∙Spacefor24cells/48cells2VBattery
∙CoolingSystem(DCFan/HeatExchanger/AirConditioner)
f.Cabinetmanufacturershallshowthecertificateorformaltechnicalmanualsheetwhichstate:
∙TypeofCoolingSystem
∙PowerConsumptionofCoolingSystem
∙ApplicableStandardsofManufacture
∙Guaranteedambienttemperaturedifferential/kWLoad
∙Othertechnicalclarification
g.Specificationsoftheequipmenttobeplacedinsidethecabinetareasfollowsforclearunderstanding(example)/asperOEMstandardequipmentdimension:
BatteryModel
Length(mm)
Width(mm)
Height(mm)
TotalHeight(mm)
GFM-400HJC
164
179
362
370
GFME-400JC
VTJ-150
551
110
288
OPzV420
145
206
471
503.5
BatteryRackDimensions
396
1352
874
560
680
700
477
1412.4
854.8
BTSModel
HuaweiBTS3900
450
600
900
NSNFlexiBTS
1750
EricssonRBS6201
483
1435
Note:
Consideringrectifiersystem:
EltekFlatpack/equivalent/aspersupplierOEMrecommendationerctifiersystem
2.TECHNICALCOMPLIANCESTATEMENT:
2.1.1Bidderwillmentionallrequiredvaluesandcompliance(Yes/No)withremarkstoclarifyanydiscrepancyanddeviationfromedotcoBangladeshCo.ltdspecificationinhisofferinthecompliancestatement.
2.1.2BlankfieldwillbeconsideredasNonCompliance.
TechnicalSpecificationofOutdoorCabinet:
S/N
Material
Description
Vendorwillmention
Vendor'
sRemark
A
EquipmentCabinet
1
InternalSpace(inHU)
40/42HU/asperOEM
42U
2
ExternalDimension
LXWXHinmm
650*650*1850
3
19"
rackandbaseforBTScabinet
Vendorwillprovideasrequired
Yes
4
IP55/equivalent
Compatibility
Yes
5
Numberofskin
1or2
6
Insulationmaterial
Typeofmaterial
7
Cabinetmaterial
8
CoolingSystemtype
HEX/Thermosiphon/Equivalent
9
CoolingPowerConsumptionRated(W)
InWatt
10
CoolingPowerConsumptionAverage(W)
11
CoolingSystemCapacityin(kW)
InkW
12
HeatExchangerconductivity(W/K)
InW/K
13
Ambientoperatingtemperaturerange°
C
In°
14
Insidetemperature
40°
Cmaximum/Ambient+X°
15
Roxtecwith20holes
Nos
16
Roxtecatuppersideandlowerside
bothoptionrequired
Yes/No
17
Powercableentryatbeneath
18
Groundingbarwith10holes
19
Cableladdertype
Type
20
Sensorandalarm
Door
21
Water
22
Smoke
23
Coolingsystemfailure
24
Doorlock
Yes/
25
Padlock
26
Baseofthecabinet
27
Degreeofprotection
Environmental
28
StandardCertification
Telecomstandardcertification
29
TotalWeight
Inkg
30
Expectedworkinglifeofcabinet
InYear
31
Expectedworkinglifeofcoolingsystem
MTBF
32
HSCodeoftheproduct
Indetail
B
BatteryCabinet
Batteryterminalaccessiblefromdoor
DCRefrigerator/Other
Insidetemperature°
25°
Spacefor(175X185X375VRLA2VCell)
Noofcell(24/48)
Groundingbar
ExtraSpacewith19"
Rackwith25°
Ccooling
HU
GeneralItems
Submitelectronicandhardcopyofallrelevanttechnicaldocuments
Supplierwillprovidestandarddocuments,photographs,tables,graphstosupportcompliance
ServiceLevelAgreement
AsperBTSequipmentSLA
Warranty
5yearscompletereplacementwarranty
Preventivemaintenance
SupplierwillprovidestandardpreventivemaintenanceaspermanufacturersrecommendationthroughoutthewarrantyperiodFOC
ResponseTime
EmergencyService
(i)Theabovementiontechnicaldatamayvary/additionaldatamaybeincludedasperOEMstandardrecommendation/designguidelineconsideringsafetyandquality
(ii)SuppliermayalsoprovidetheirbetterproductofferforOutdoorCabinetwithdetailstechnicaldatasheetasoptionalalongwiththisoffer.
2.1.3SampleschematicDiagramofOutdoorCabinetforclearunderstanding:
3DeliveryReadinessDate
Minimum4weeksandMaximum8weeksweek’safterpurchaseorderareissued
4DeliveryLocation
TheProductistobedeliveredtoChittagong/asperinstructionofedotcoBangladeshCo.ltd,Bangladesh.
5PerformanceorAcceptancecriteriaorfactors
AnyindependentDeliverableoftheScopeofServicewillbesubjecttoAcceptancetesting.
ThePartieswillmutuallyagreeanAcceptanceTestProcedureforfulfillingtheSpecifications.TheSuppliershallprovidesuchAcceptancetestProceduretothePurchaser.
Acceptancetestings