GUIDESPEC

ActivePowerCleanSource2

250/500kWDC

FlywheelEnergyStorageforUPSSystems

 

Battery-freeenergystorage

 

TechnicalSpecifications

TableofContents

PART1–GENERAL2

1.01SCOPE2

1.02SYSTEMDESCRIPTION2

1.03QUALITYASSURANCE3

1.04PROPOSAL4

1.05SUBMITTALS4

1.06MANUALS5

1.07WARRANTYANDMAINTENANCECONTRACT5

PART2–PRODUCTS6

2.01ACCEPTABLEMANUFACTURERS6

2.02CONSTRUCTION6

2.03DCFESS7

A.DESCRIPTION:

7

B.OPERATION:

7

C.DCFESSCONSTRUCTION:

9

D.ELECTRICALREQUIREMENTS:

10

E.STANDBYLOSSES:

11

F.ENVIRONMENTALREQUIREMENTS:

11

G.FLYWHEELENERGYSTORAGESUBSYSTEM(flywheel/motor/generator):

12

H.BI-DIRECTIONALCONVERTERS(BDC):

13

I.CONTROLSANDINSTRUMENTATION:

13

2.04.OPTIONS17

A.REMOTENOTIFICATIONandMONITORINGOPTIONS:

17

B.CSVIEW:

17

C.DCDISCONNECT:

18

D.BOTTOMCABLEENTRY:

18

E.MODBUS18

F.SNMP18

PART3–EXECUTION18

3.01SCOPE18

3.02ON-SITEQUALITYCONTROL19

3.03START-UP20

ACTIVEPOWERCLEANSOURCE2

CS2-250--250kWDCFlywheelEnergyStorage

CS2-500--500kWDCFlywheelEnergyStorage

PART1–GENERAL

1.01SCOPE

A.SupplyaDCflywheelenergystoragesystemasdescribedhereintobeintegratedwithanuninterruptiblepowersupply(UPS)systemforthepurposeofmaintainingtheDCbusoftheUPSwithinspecifiedtolerancesduringfailureordeteriorationofthenormalpowersupply.

B.Includestart-upservicesforallequipment.

C.Rigging,installationlaborandinstallationmaterials(includingallinterconnectionsbetweendetachedpiecesofequipment)shallbetheresponsibilityofothers.

1.02SYSTEMDESCRIPTION

A.TheEquipmentshallincludeaDCflywheelenergystoragesystem(DCFESS)configuredasatwoterminalDCpowerstoragesystemandshallbeusedasafunctionalreplacementorsupplementforabankofchemicalbatteriesforstaticorrotaryUPSdesigns.Likeachemicalbatterybank,itshallreceiverechargeandfloatpowerfromthetwoterminalUPSDCbusandshallreturnpowertothesameDCbuswheneverthebusvoltagedroopsbelowaprogrammablethresholdlevel.TheDCFESSshallbecomprisedofthefollowingmajorelementsintegratedintoasingleunit:

1.Asinglecabinetwithoneortwointegralflywheelenergystoragesubsystem(s)(flywheel/motor/generator),bi-directionalACtoDCconverter(BDC),soft-startwalk-incontactorandtwoDCterminals(onepositiveandonenegative).

2.

3.AllcontrolsandaccessoriesnecessaryfortheEquipmenttofunctionproperlyasspecified.

B.TheDCFESSshallprovideatleast13secondsride-throughtimeatratedloadwithoutusingchemicalbatteries.

C.TheDCFESSshallberated250kWor500kW.Powerratingsdecreaselinearlyfrom250kWperwheelto187kWperwheelasdischargevoltagesettingisreducedfrom480to360VDC(i.e.,CS2-500at400VDCdischargehaspowercapacityof400/480x500kW=417kW).Deliveredenergyfromeachwheelremainsconstant.

D.AnoptionalinternalDCdisconnectshallbeavailableasanintegratedpartoftheDCFESSwithoutincreasingthecabinetsizeandshallbeincludedwhenspecified.

1.03QUALITYASSURANCE

A.TheDCFESSand,whenincluded,theDCdisconnectshallbetestedatthefactoryforproperoperation.TheDCFESSshallbefunctionallytestedandshallbeburnedinforaminimumof48hours.Copiesofthefactorytestreportandqualitycontrolprogramdocumentationshallbeprovidedonrequest.

B.TheDCFESSshallbelistedandlabeledbyULinaccordancewiththeapplicablerequirementsofUL1012,UL1778andUL1004.TheDCFESSshallalsobequalifiedforCEMark.AllotherEquipmentshallbelistedandlabeledinaccordancewiththeapplicableULrequirements.

C.DCFESSdesignandconstructionshallconformtothefollowingstandardsasapplicable:

1.UL1012SpecialtyPowerSupplies;UL1778,StandardsforUninterruptiblePowerSupplyEquipment;andUL1004,ElectricMotors.

2.

3.FCCRulesandRegulations47,Part15,SubpartJ,ClassA.

4.

5.IEEE587-1980/ANSIC62.411980,CategoryA&BRecommendedpracticeonsurgevoltagesinlowpowercircuits.

6.NEC.

7.OSHAsafetystandardsforelectricalequipmentandserviceofelectricalequipment.

8.CSAC22.2No.107.1CommercialandIndustrialPowerSupplies.

9.IndustryCanadaICE-003,CanadianEMC.

10.

11.

12.

13.

14.

a.

b.

c.

d.

8.Year2000complianceasdefinedinBSIstandardDISCPD2000-1,AdefinitionofYear2000ConformityRequirementsDocument.

D.AllEquipmentshallbenewandofcurrentdesignandmanufacture.

1.04PROPOSAL

A.Providefirmpriceanddeliverylead-timemeasuredfromthedateoforderreceiptfortheEquipmentandservicesinaccordancewiththerequirementsofthisspecification.

B.ProvideaparagraphbyparagraphspecificationcompliancethatclearlyidentifieswhethertheproposedEquipmentandservicescomplywiththespecification(Comply),complywiththeintentoftheparagraphandprovidetheperformancespecifiedbutdeviateinminordetail(Deviation),ordonotcomply,donotprovidethespecifiedperformanceorsubstantiallydeviatefromthespecificationrequirements(Exception).Iftheproposalcompliesfullywiththerequirementsofaparagraph,thenotation“Comply”shallbeappliedtotheparagraphandnonotationsassociatedwiththatparagraphshallrelievethesupplierfromcomplyingwiththerequirementsoftheparagraph.AnyDeviationorExceptionmustbemarkedwiththelegend“Deviation”or“Exception”,respectively,andexplainedsufficientlytoallowthepurchaseroritsagentstoclearlyevaluatetheeffectandconsequencesoftheDeviationorException.

C.Includeallotherinformationrequiredbythisspecificationtobepartoftheproposal.

1.05SUBMITTALS

A.Providegeneralarrangementdrawingsshowingallexteriordimensions,cableaccess,shippingsplits,andclearances.Showsizes,weights,andrelationshipsbetweenindividualshippingunits,thelocationanddesignationofallfieldwiringterminationareas,andthemaximumnumberandpermissiblesizerangeofpowerconductorswhichcanbeaccommodatedforeachpowertermination,heatrejection,airflow,andlocationofairinletsandoutlets.

B.ProvideassemblyandmountingdetailsforallEquipmentandshippingsplits.

C.Provideelectrical,mechanical,andenvironmentalspecificationsfortheproposedequipment.Alsoincludethisinformationinthebid.

D.Providethesameparagraph-by-paragraphresponsetothesespecificationsinsufficientdetailtoclearlyshowalldeviations.Clearlyidentifyanychangesinthiscompliancecomparedtothecompliancesuppliedwiththeproposal.Thesubmittalmayberejectedifitcontainsanydeviationsorexceptionsnotincludedintheproposal.

E.Provideelectricalone-linedrawingsshowingallpowerandcontrolinterconnectwiring.Includenumberofconductors,powerwiringamperages,arrangementandratingsofallprotectiondevices,andcontrolwiresizeandtype.

F.Providepointtopointinterconnectdrawingsorwirelistsdetailingtheterminationpoints,andterminaldesignationsforallfieldwiringbetweenequipmentorshippingsplits.Thisdrawingwilleithercontainwiringrequirementsorshallbekeyedtotheone-linedrawinginamannerthatclearlydetermineswiringrequirements.

G.Providetwocopiesofalldrawingsatleast30dayspriortoshipment.Shipusermanualswithequipment.

1.06MANUALS

Provide1setofusermanualspersiteofDCFESSdeploymentcontainingsafety,handling,storage,installation,operationandnormalmaintenanceinstructions.Themanualsshouldalsocontainspecifications,requirements,descriptions,andfeaturesforallequipment.

1.07WARRANTYANDMAINTENANCECONTRACT

ThemanufacturershallwarranttheEquipmentagainstdefectinworkmanshipandmaterialsfor12monthsfromdateofequipmentshipmenttotheinitialenduser.

PART2–PRODUCTS

2.01ACCEPTABLEMANUFACTURERS

TheapprovedmanufacturerfortheDCFESSisActivePower,Inc.Nosubstitutionsarepermitted.

2.02CONSTRUCTION

A.Allmaterialsusedshallbenew,ofcurrentmanufacture,highquality,freefromdefectsandshallnothavebeeninprevioususeexceptasrequiredforfactorytesting.

B.AllEquipmentexceptforanyremoteannunciationpanels,remoteEPOpanelsorcomputermonitoringequipment,shallbefree-standingNEMA1constructionorIECequivalent.

C.Cableaccessshallbepermittedfromthetopusingracewayorconduitwithoutmodification.Bottomcableaccessshallbeanoption.

D.ConstructionofEquipmentshallfacilitateliftingwithforklift.ClearanceshallbeprovidedinthebaseofEquipmenttoallowliftingbyforkliftfromthefrontorrear.Theinstallingorriggingcontractorshallprovideappropriateslingsandspreaderbarsifsystemistobeliftedbycrane.

E.AllwiringshallbeinaccordancewithNFPA70,OSHA,andEN.Allpowerconductors,transformerandchokewindingsshallbecopper.Allbusbarconnectionsshallbebetweencopper,silver-platedcopperortin-platedcoppersurfacesandshallbebetweenlikemetals.Connectionsshallbeproperlytorqued.

F.AllcontrolwiringinterconnectionsbetweenshippingsplitsofasinglepieceofEquipmentshallbesuppliedandfittedwithconnectorsorfanningstripsconstructedandidentifiedtopreventincorrectconnection.

G.Allfieldcontrolwiringterminationsshall