1、HB2英文使用说明书803551 General Descriptions80951.1 Series HB2 three-phase induction motors are designed and manufactured into flameproof type according to the specification in European Standards.EN60079-0:2004 Electrical Apparatus for Explosive Gas Atmospheres General RequirementsEN60079-1:2004 Electrical
2、 Apparatus for Explosive Gas Atmospheres Flameproof Enclosure“d”They are applicable to the locations being presence of methane, ethanol, coal gas and ethylene explosive gases and vapors and can be used as drivers. The mark of explosion protection is Eexd I or EExdII BT4.1.2 The legible and durable r
3、aised sign“EEx”or“Ex”should be marked on the distinct position of the enclosure of motors. The Ex mark consists of sign, type, group and temperature class.1.3 The output ratings, the mounting dimensions and correlation of this series motors conform to DIN 42673.For special requirements, see outline
4、drawing.1.4 Explanation of type designation of HB2 132 S1-2 us as follows:2 Service Condition 2.1 Circumstance Conditions2.1.1Ambient temperature: subject to seasonal variations but not exceeding-20+40.2.1.2 Altitude: up to 1000m;2.1.3 The highest relative humidity of the environmental air is not ex
5、ceeding 95%(when air temperature is at +25 ).2.1.4 Coal mines (non-coalface) and Zone 2 explosion hazard locations where present mixtures of flammable gas-or vapor-air with ignition temperature T1T4.2.2 Electrical Conditions2.2.1 Frequency: 50HZ or 60Hz2.2.2 Voltage:For frame-size 80280 motors: 380V
6、,400V,380/400V,400/690V.For frame-size 315355 motor: 380V,400V,380/400V,400/690V.2.2.3 The duty type is S1(continuous running duty-type).2.2.4 The stator windings are of Class F or Class H insulation systems.Note: When the working conditions and electrical conditions do not conform to eh specificati
7、ons in 2.12.2,see the specifications indicated on the motors nameplate and auxiliary marking plate.3 Construction Features 3.1 The degree of protection and mounting arrangement of this series motors are IMB3,IMB35,IMB5,IMV1,or manufactured according to customers specified requests.3.2 The degree of
8、protection of motor main body enclosure is IP44,IP54and IP55.And for the flameproof structure, see Figure1.3.3 The cooling form of the motor: IC411 total enclose self-fan cooling for frame size 80-355 motor.3.4 The motor fans are made form reinforced acrylic plastering,HT150 gray cast iron or weldin
9、g of steel plate. For plastic fan, the resistance measured according to the method specified in 60079-0:2004shall not greater than 1G.3.5 The stator windings use polyester enamel round copper wire (Class F) or polyimide enamel round copper wire (Class H).The complete wound stator cores are vacuum-pr
10、essure-impregnated(VPI) to make them be a solid integral. This process enables the windings to possess excellent electrical and mechanical properties, high moisture-resistant ability and thermal stability.3.6The motors rotor adopts squirrel cage type. The aluminum motor rotor is fixed on the shaft b
11、y means of shrink fit and balanced well to make motors operate smoothly with little nose and vibration.3.7 The motors are provided with a cylindrical shaft extension and transmit by means of coupling or spur-gear unit. For spur gearing, the gear pitch diameter should not less than 3 times of shaft e
12、xtension diameter. Two shaft extension or special shaft-extension motors can also be produced by ordering request.3.8The terminal box is located in the top of the motor. The terminal boxes are designed and fabricated with either three or six terminals with one or two entries. Another galvanized stee
13、l or copper screw in the box is fixed for inside earthing. The entries of the terminal box are suitable for rubber-insulated cable, conduit entry and explosion-proof flexible pipe (armouring cable). The protection degree of terminal boxes id IP55.For the construction of terminal box, see Figures23.4
14、 Explosion Protection Features4.1 These series motors are so designed in mechanical construction that should the explosive mixture inside the motors be ignited by some cause or other ,the flame poof enclosures are capable of withstanding the explosion, and of preventing the sparks inside passing thr
15、ough the flameproof join surfaces and the ignition of explosive mixture surrounding the enclosures by sparks.4.1.1 The parts constituting flameproof enclosure shall be tested hydrostatically according to the specification in EN60079-1:2004 to ensure them to withstand the maximum explosion pressure.4
16、.1.2 Exercise strict control over the flameproof joint surfaces length, gap or diameter clearance, the surface roughness between the surfaces of all the pats constituting the flameproof enclosure and the electric clearance and creepage distance between the bare conducting parts and the metallic encl
17、osure the cable from harm.4.2 In order to ensure flameproof property of the enclosure, the bolts jointing the flameproof enclosure should be provided with spring washers to prevent working loose. After fastening bolts in bolt blind hole, the thread allowance should be remained between the screw or b
18、olt tail and the thread-hole bottom. The thickness of metal surrounding bolt blind holes on enclosures should not be less than 1/3 of the bolt diameter, but at least 3mm.4.3 When the cable is inlet through the terminal box, the cable entry should be sealed with elastic sealing gasket. The sealing ga
19、sket is made of rubber Shore-Hardness 4550 o. The material should withstand the aging test specified in EN60079-0:2004.The diameter of the cable brought into the terminal box shall conform to that of the bore in the sealing gasket. Several different concentric round slots are made in the sealing gas
20、ket and the values of the minimum outside diameter of cable corresponding to each round slot are marked on the outer surface of the sealing gaskets. The bear diameter of sealing gasket . The bear diameter of sealing gasket can be adjusted according to cable diameter. The coupler should be so tighten
21、ed that no gaps exist between the sealing gasket and the cable, between the sealing gasket and enter of terminal box and between the sealing gasket and chamber of gasket ring. Otherwise the flameproof property of the enclosure would be lost.4.4 the insulating parts of terminal bushing and connecting
22、 plate in the terminal box are made of insulating material being of Degree II tracking resistance.4.5 Earth: Earthing of motor is the important measurement to prevent leakage electric sparks to ensure safety. A steel or copper galvanized bolt uses as an earth terminal and also an earthing sign board
23、 fitted on distinct position of the motor enclosures.4.6 Flameproof parts the frame, the end shields, the shaft(rotor),the inner bearing covers, the bottom section of terminal box, the base of terminal box, the cover of terminal box, the terminal bolts ,the seal gasket, the terminal sleeve, see Figu
24、res13.5 Installation and Operating5.1 Preparations15.1.1 Before opening the packing cases, check if the package is in good shape.5.1.2 After opening the packing cases, clean up the dust on the motors and anti-rusting agent on the shaft extension and flange spigot carefully.5.1.3 Check whether the da
25、ta on the nameplate (and auxiliary marking plate)conform to the purchase contract and field situations.5.1.4 The following points must be observed before installing flameproof motors. No operation is allowed if these points is unsatisfactory.a) The sign“Ex”and the certificates series number must hav
26、e been attached to the motor Check whether the mark of explosion protection is confirm to the explosion gas location where the motor is intended to use.b) All the bolts are tightened and spring washers are present. All parts of the flameproof enclosure are connected firmly;c) No cracks or defects af
27、fecting the flameproof property could be found on all the flameproof parts.(For the new motor having not been used ,this item can be omitted.)d) For the motor with grease drain and replenish device, the grease replenish pipes shall de unlocked.e) For the motor with bearing temperature detector, afte
28、r the device being set up ,be sure that its flexible cord shall not touch with the fan to prevent the motor from accident.5.2 For the motor being long-distance transported and long-time stored, prior to using, the insulation resistance values between stator windings and enclosure shall not lower tha
29、n 3XUN/1000(UN: rated voltage in V),otherwise the motor must be dried until the insulating resistance value achieves the specified one.5.3 During the motor being mounted, care must be exercised in lining up, as misalignment can be detrimental to bearings and shaft in both the motor and driven equipm
30、ent. Check whether the coupling or screw and pin on spur gearing is fastened, the until runs smoothly and jam, shift and abnormal noise is present or not.5.4 Check whether the motors bearings are short of grease, the bearing are short of grease and the enclosure earths or connects with zero line rel
31、iable etc.5.6 Check whether the protective devices conform to the requirements and they are installed firmly and reliably.5.7 Check whether the connection on the driven equipment is correct, force-supplied rotation on the driven equipment is smooth, the touching heads contact well, the metallic encl
32、osure of the driven equipment is smooth, the touching heads contact well, the metallic enclosure of the driven equipment earths or connects with zero line reliably etc.5.8 Check whether three-phase power supply voltage is normal. No phenomenon of over-high or over-low voltage and unsymmetry of three phase voltage is present.5.9 Connecting with Electric Source5.9.1 The bottom section of terminal box is located on the top of the motor. The gland (for the rubber-insulated cable, it is bell-shaped hole; while for conduit cable entry, it is a pipe-th