Phase3FunctionsfromSIWGRecommendationsDocument
Theresultsofthe3-19-15surveyareshown.DERmanufacturers,implementers,andaggregatorswerecombined,sincemostaggregatorsarealsoimplementers.InthisTable,onlythemajorityvoteisshown(seethepdffilesfordetails).Iftherewasnomajority,IindicatethetwoorthreehighestresultsasH-M,H-O,M-O,orH-M-O.Acoupleoffunctions(F-Wandconnect/disconnectDER)wereleftoutofthesurveybymistake.
AnumberofadditionalfunctionshavebeensuggestedandareaddedtotheendoftheTable.
Q#
Phase3DERFunctionswithCommunications
Description
CommunicationRequirements
Util
H/M/O
DER
H/M/O
Oth
H/M/O
Constraints&Comments
2
MonitorAlarms:
Provideemergencyalarmsandinformation
TheDERsystem(andaggregationsofDERsystems,suchasvirtualpowerplants)providesalarmsandsupportingemergencyinformationviatheFDEMStotheutility.ThisfunctionisfeasibleonlyiftheICTinfrastructureisavailable.
ICT:
DERsystemprovidesalarmsandemergencyinformationtoutilityand/orREP
H
O
H
LargerDERsormultipleDERswithinafacility
3
MonitorDERStatusandOutput:
Providestatusandmeasurementsoncurrentenergyandancillaryservices
TheDERsystem(andaggregationsofDERsystems,suchasvirtualpowerplants)providescurrentstatus,powersystemmeasurements,andotherreal-timedata(possiblyaggregatedviatheFDEMS)totheutility,inordertosupportreal-timeandshort-termanalysisapplications.ThisfunctionisfeasibleonlyiftheICTinfrastructureisavailable.(Revenuemeteringdataisprovidedviaalternatemeans.)
ICT:
DERsystemprovidesstatusandmeasurementvaluestoutilityand/orREP
H
H
H
LargerDERsormultipleDERswithinafacility
4
LimitMaximumRealPower:
LimitmaximumrealpoweroutputatanECPorthePCCuponadirectcommandfromtheutility
TheutilityissuesadirectcommandtolimitthemaximumrealpoweroutputattheECPorPCC.Thereasonmightbethatunusualoremergencyconditionsarecausingreverseflowintothefeeder’ssubstationorbecausethetotalDERrealpoweroutputonthefeederisgreaterthansomepercentageoftotalload.ThecommandmightbeanabsolutewattvalueormightbeapercentageofDERoutput.ThisfunctionisfeasibleonlyiftheICTinfrastructureisavailable.ItmightalsobeusedtoensurefairnessacrossmanyDERsystems.
Autonomous
Local:
MonitorrealpoweroutputatPCC
ICT:
UtilityissuesacommandtolimittherealpoweroutputattheECPorPCC
H
H
O
LargerDERsorlargegroupsofDERswhereICTcapabilitiesareavailable
5
ScheduleOutputatPCC:
Scheduleactualormaximumrealpoweroutputatspecifictimes
Theutilityestablishes(orpre-establishes)aschedule(e.g.on-peak&off-peak)ofactualormaximumrealpoweroutputlevelsattheECPorPCC,possiblycombininggeneration,storage,andloadmanagement.Thereasonmightbetominimizeoutputduringlowloadconditionswhileallowingorrequiringhigheroutputduringpeakloadtimeperiods.
Autonomous
Local:
MonitorrealpoweroutputatECPorPCC.
ICT:
Utilityupdatesthescheduleofactualormaximumrealpowervalues
H
O
H-O
LargerDERsormultipleDERswithinafacility
Frequency-Watt:
Counteractfrequencyexcursionsbeyondnormallimitsbydecreasingorincreasingrealpower
TheDERsystemreducesrealpowertocounteractfrequencyexcursionsbeyondnormallimits(andviceversaifadditionalgenerationorstorageisavailable),particularlyformicrogrids.HysteresiscanbeusedasthefrequencyreturnswithinthenormalrangetoavoidabruptchangesbygroupsofDERsystems.
Autonomous
Local:
Monitorvoltageanomalies
ICT:
Utilityupdatesfrequencyresponsesettings
H
H
H
AllDERsystemsbutmaynotalwaysbeactivated
(Leftoutofsurveybymistake)
6
Voltage-Watt:
Modifyrealpoweroutputautonomouslyinresponsetolocalvoltagevariations
TheDERsystemmonitorsthelocal(orfeeder)voltageandmodifiesrealpoweroutputinordertodampvoltagedeviations.SettingsarecoordinatedbetweentheutilityandDERoperator.Hysteresisanddelayedresponsescouldbeusedtoensureoverreactionsorhuntingdonotoccur.
Autonomous
Local:
Monitorvoltage
ICT:
Utilitymodifiestherealpoweroutputsettings
H
M
M
AllDERsystemsbutmaynotalwaysbeactivated
7
DynamicCurrentSupport:
Counteractvoltageexcursionsbeyondnormallimitsbyprovidingdynamiccurrentsupport
TheDERsystemcounteractsvoltageanomalies(spikesorsags)through“dynamiccurrentsupport”.TheDERsystemsupportsthegridduringshortperiodsofabnormallyhighorlowvoltagelevelsbyfeedingreactivecurrenttothegriduntilthevoltageeitherreturnswithinitsnormalrange,ortheDERsystemrampsdown,ortheDERsystemisrequiredtodisconnect.
Autonomous
Local:
Monitorvoltageanomalies
ICT:
Utilityupdatesdynamiccurrentsettings
H
H
H
AllDERsystemsbutmaynotalwaysbeactivated
8
SetRealPower:
SetactualrealpoweroutputattheECPorPCC
TheutilityeitherpresetsorissuesadirectcommandtosettheactualrealpoweroutputattheECPorPCC(constantexport/importifloadchanges;constantwattsifnoload).Thereasonmightbetoestablishabaseorknowngenerationlevelwithouttheneedforconstantmonitoring.Thisistheapproachoftenusedtodaywithsynchronousgenerators.ThisfunctionisfeasibleonlyiftheICTinfrastructureisavailable.Meterreadscouldprovide15-minuteenergybytheendofthedaycouldprovideproductioninformationforoperationalplanning.
Autonomous
Local:
MonitorrealpoweroutputatPCC.
ICT:
utilityissuesacommandtomodifytherealpoweroutputattheECPorPCCincludingforchargingordischargingstoragesystems
H
O
O
LargerDERsormultipleDERswithinafacility
9
InitiatePeriodicTests:
TestDERfunctionality,performance,softwarepatchingandupdates
InitialDERsoftwareinstallationsandlaterupdatesaretestedbeforedeploymentforfunctionalityandformeetingregulatoryandutilityrequirements,includingsafety.Afterdeployment,testingvalidatestheDERsystemsareoperatingcorrectly,safely,andsecurely.
Off-line,local,orICT:
(maybepriortoinstallationorhandledlocally)TestDERsoftware
H
M
O
RecommendedforallDERsystems,usingappropriatetypesoftesting
CommandDERtoConnectorDisconnect:
Supportdirectcommandtodisconnectorreconnect
TheDERsystemperformsadisconnectorreconnectattheECPorPCC.TimewindowsareestablishedfordifferentDERsystemstorespondrandomlywithinthatwindowtothedisconnectandreconnectcommands.ThisfunctionisfeasibleonlyiftheICTinfrastructureisavailable.
ICT:
UtilityorFDEMSissuesdisconnectorreconnectcommand
M
RecommendedforallDERsystemsbutmaynotalwaysbeactivatedandwouldrequireICTcapabilities(Leftoutofsurveybymistake)
10
ProvideDERNameplateorAs-Builtinformation:
Provideoperationalcharacteristicsatinitialinterconnectionanduponchanges
TheDERsystemprovidesoperationalcharacteristicsduringinitialRule21screening,duringimplementation,orafterits“discovery”andwheneverchangesaremadetoitsoperationalstatus.
Off-lineorICT:
(maybepriortoinstallation)ProvideDERcharacteristicsinformationtoutility
O
M
H
RecommendedforallDERsystems.Sincecommunicationscapabilityismandatory,canbeaddedlater
11
ScheduleDERFunctions:
Schedulerealpowerandancillaryserviceoutputs
TheDERsystemreceivesandfollowsschedulesforrealpowersettings,reactivesettings,limits,modes(suchasautonomousvolt/var,frequency-watt),andotheroperationalsettings.
Autonomous
ICT:
Utility,REP,orFDEMSissuesschedulestoDERsystem
H
O
M
RecommendedforallDERsystemsbutmaynotalwaysbeactivated
12
ScheduleStorage:
Setorschedulethestorageofenergyforlaterdelivery,indicatingtimetostartcharging,chargingrateand/or“charge-by”time
ForaDERsystemthathasstoragecapabilities,suchasbatterystorageoracombinedPV+storagesystemorafleetofelectricvehicles.Presettime-of-chargevaluescanbeestablished.SettingsarecoordinatedbetweentheutilityandDERoperator.Differentscenarioscouldinclude:
∙Lowloadconditionsatnightarecausingsomerenewableenergytobewasted,sochargingenergystorageDERsystemsatthattimemakespowersystemoperationsmoreefficient.
∙DERcontrollerchargesatthespecifiedrate(lessthanorequaltothemaximumchargingrate)untilthestate-of-charge(SOC)reachesaspecifiedlevel.
∙DERcontrollerchargesatthenecessaryrateinordertoreachthespecifiedSOCwithinthe“charge-by”time.
Autonomous
ICT:
Utilityupdatesthestoragesettingsand/orschedule
H-M-O
O
H
RecommendedforDERsystemswithstoragecapabilities
13
SmoothFrequencyDeviations:
Smoothminorfrequencydeviationsbyrapidlymodifyingrealpoweroutputtothesedeviations
TheDERsystemmodifiesrealpoweroutputrapidlytocounterminorfrequencydeviations.Thefrequency-wattsettingsdefinethepercentageofreal-poweroutputtomodifyfordifferentdegreesoffrequencydeviationsonasecondorevensub-secondbasis
Autonomous
Local:
Monitorfrequency
ICT:
Utilityupdatesthefrequency-wattsettings
H-M
O
H-O
RecommendedforallDERsystemsbutmaynotalwaysbeactivated
14
BackupPower:
Providebackuppowerafterdisconnectingfromgrid
TheDERsystem,includingenergystorageandelectricvehicles,hastheabilitytoproviderealpowerwhenthesiteisdisconnectedfromgridpower.Thereasonisforprovidingbackuppowertothefacilityandpossiblyblackstartcapabilities.
Autonomous
Local:
Monitorvoltage,frequency,andconnectedload
O
O
O
Decisio