ASNZS30005

SECTION5 EARTHINGARRANGEMENTSANDEARTHINGCONDUCTORS

第5部分接地布置和接地导体

5.1GENERAL概述

TherequirementsofthisSectionapplytotheperformanceoftheearthingarrangementsintendedtosatisfythesafetyandfunctionalrequirementsoftheelectricalinstallationinaccordancewithSection1.

5.2EARTHINGARRANGEMENTS接地布置

5.2.1General概述

Earthingarrangementsmaybeusedjointlyorseparatelyforprotectiveorfunctionalpurposes,accordingtotherequirementsoftheelectricalinstallation.

5.2.2Forprotectivepurposes

Earthingarrangementsforprotectivepurposesshallbecomprisedofprotectiveearthingconductorsusedwithovercurrentprotectivedevicesprovided,intheactive,forprotectionagainstindirectcontactandovercurrent.

NOTE:

Theprotectiveearthingconductorsshouldbeincorporatedinthesamewiringenclosureastheassociatedactiveconductorsorinthenearvicinity.

5.2.3Forfunctionalpurposes出于功能目的

Earthingarrangementsforfunctionalpurposesshallbecomprisedoffunctionalearthingconductorsprovidedtoensurecorrectoperationofelectricalequipmentortopermitreliableandproperfunctioningofelectricalinstallations.

NOTE:

Wherea‘cleanearth’isspecifiedforaparticularitemofelectricalequipment,themanufactureroftheelectricalequipmentshouldbeconsultedinordertoconfirmthenecessaryarrangements.

5.2.4Forcombinedprotectiveandfunctionalpurposes

Whereearthingforcombinedprotectiveandfunctionalpurposesisrequired,therequirementsforprotectivepurposes(seeClause5.2.2)shallprevail.

5.2.5Selectionandinstallation选择和安装

Theselectionandinstallationoftheequipmentoftheearthingarrangementsshallbesuchthat—

(a)thevalueofearthingresistanceisinaccordancewiththeprotectiveandfunctionalrequirementsoftheelectricalinstallationandexpectedtobecontinuouslyeffective;and

 (b)earth-faultcurrentsandearth-leakagecurrentscanbecarriedwithoutdanger,particularlyfromthermal,thermomechanicalandelectromechanicalstresses;and

(c)itisadequatelyrobustorhasadditionalmechanicalprotectionappropriatetotheassessedconditionsofexternalinfluenceinaccordancewithClause3.3.

5.2.6Precautions防范措施

Precautionsshallbetakenagainsttheriskofdamagetotheearthingarrangementandothermetallicpartsoftheelectricalinstallationthroughelectrolysisorgalvanicaction.

5.3MULTIPLEEARTHEDNEUTRAL(MEN)SYSTEM多重接地中线系统

ThesystemofearthingthatshallbedeemedtosatisfytherequirementsofClause5.1isthemultipleearthedneutral(MEN)systeminwhichthepartsofanelectricalinstallationrequired,underthisStandard,tobeearthedareconnectedtothegeneralmassofearthand,inaddition,areconnectedwithintheelectricalinstallationtotheneutralconductorofthesupplysystem.

NOTES:

1ExamplesoftheMENsystemofearthingareshowninFigures5.1and5.2.

2Alternativeearthingsystemsthatsatisfythegeneralsafetyandfunctionalrequirementsmaybeused.

5.4EARTHINGREQUIREMENTS接地要求

5.4.1General概述

Theexposedconductivepartsofelectricalequipmentshallbeearthedwheretheelectricalequipmentis—

(a)installedormightoperateinanearthedsituation;or

(b)notinstalledinanearthedsituationbutanyexposedconductivepartoftheelectricalequipmentiselectricallycontinuouswithconductivematerialwhichislocatedinanearthedsituation.

NOTE:

Thetermexposedconductivepartdoesnotapplytothefollowing:

(a)Conductivepartswithinanenclosurewherethepartscannotbetouchedunlessakeyoratoolisrequiredtoremovethecoversoftheenclosure.

(b)Conductivepartswithinelectricalequipmentwherethepartscannotbetouchedinnormaluseandmovementoftheelectricalequipmentduetoitsconfigurationandsize,e.g.sometypesofwashingmachines.

(c)Conductivepartswhichareseparatedfromlivepartsby—

(i)doubleinsulation;or

(ii)otherconductivepartswhichareearthed.

(d)Conductivepartswhichareintheformofnameplates,screwheads,coversandsimilarattachmentsthatcannotbecomeliveintheeventoffailureofinsulationofliveparts,duetothemannerinwhichtheyaresupportedandfixed.

NOTE:

Onlysinglephaseconnectionsshownforclarity.

FIGURE5.1MULTIPLEEARTHEDNEUTRAL(MEN)SYSTEMOFEARTHING—MENLINKATCUSTOMER’SMAINSWITCHBOARD

NOTE:

DistributionasFigure5.1

FIGURE5.2MULTIPLEEARTHEDNEUTRAL(MEN)SYSTEMOFEARTHING—MENLINKREMOTEFROMCUSTOMER’SMAINSWITCHBOARD

5.4.2Connectionofelectricalequipmenttoearth电气设备接地连接

Electricalequipmentrequiredtobeearthedshallbearrangedforconnectionto—

(a)protectiveearthingconductorsintheformofcables,cords,busbarsorsimilarformsofcurrent-carryingmaterial;or

(b)anotherearthingmediumsuchasmetallicpartsofcables,wiringenclosures,switchboardframeworkorthelike.

5.4.3Resistanceoftheearthingsystem接地系统电阻

Theresistancefromanypointontheelectricalinstallationrequiredtobeearthedtothepointwherethemainearthingconductorisconnectedtotheneutralconductorofthesupplysystemshallbelowenoughtopermitthepassageofcurrentnecessarytooperatethecircuitprotectivedevices.

Theresistanceofthemainearthingconductorshallbenotmorethan0.5?

.

NOTE:

AsdescribedinAppendixB,themaximumresistanceoftheprotectiveearthingconductorassociatedwithanyparticularcircuitdependsonthetypeandratingoftheprotectivedeviceandtheimpedanceoftheliveconductorsthatcomprisethecircuit.

5.5EARTHINGCONDUCTORS接地导线

5.5.1Size尺寸

5.5.1.1General概述

ThesizeofanearthingconductorshallbesuchthatitmeetstherequirementsofClause5.2.

NOTE:

Guidanceonthedeterminationofthemaximumlengthofacircuit,inrelationtothecharacteristicsofprotectivedevicesandthesizeoftheprotectiveearthingconductor,isprovidedinAppendixB.

5.5.1.2Minimumsize最小尺寸

Theminimumsizeofanearthingconductorshallbedeterminedasfollows:

(a)GeneralExceptwherevariedbyItems(b)to(f),theminimumsizeofanycopperearthingconductorrequiredfortheprotectionofanyportionofanelectricalinstallationshallbedeterminedfromTable5.1

inrelationtothecross-sectionalareaofthelargestactiveconductorsupplyingtheportionoftheelectricalinstallationtobeprotected.

ThedeterminationmethodusingTable5.1mayalsobeappliedinthefollowingsituations:

(i)Wheretheactiveconductorsinamultiphasecircuitcomprisedifferentsizeconductors,theearthingconductorshallbedeterminedinrelationtothecross-sectionalareaofthelargestactiveconductortobeprotected.

 (ii)Wheretheactiveconductorcomprisesanumberofconductors,connectedinparallel,theearthingconductorshallbedeterminedinrelationtothesummationofthecross-sectionalareasoftheindividualconductorsformingthelargestactiveconductortobeprotected.

Wherethesummationofcross-sectionalareasdoesnotcorrespondexactlywiththenominalsizeoftheactiveconductorgiveninTable5.1,theconductorshallbedeterminedinrelationtothenearestlargersizeofactiveconductor.

TABLE5.1MINIMUMCOPPEREARTHINGCONDUCTORSIZE

Nominalsizeofactiveconductor

Nominalsizeofcopperearthingconductor

Withcopperactiveconductors

Withaluminiumactiveconductors

1

1.5

2.5

1*

1.5*

2.5

-

-

-

4

6

10

2.5

2.5

4

-

2.5

2.5

16

25

35

6

6

10

4

6

6

50

70

95

16

25

25

10

10

16

120

150

185

35

50

70

25

25

35

240

300

400

95

120

120

50

70

95

500

630

120

120

95

120

*Theseearthingconductorsmaybeusedonlywhereincorpratedinamulticorecableorflexiblecord,otherthanalifttravelingcable,inaccordancewithClause5.5.1.2(e)(ii)and(iii).

(b)CalculationAsanalternativetothedeterminationmethoddescribedinItem(a),theminimumsizeofanearthingconductorrequiredmaybedeterminedbycalculationprovidedthataccurateinformationisobtainedonthevalueoftheprospectivefaultcurrent,thedisconnectingtimeoftheprotectivedevice,andconductorandinsulationcharacteristics.

NOTE:

AsuitableequationforthecalculationofconductorsizesunderfaultcurrentconditionsisgiveninClause5.6.7.4.3.

(c)MainearthingconductorIngeneral,theminimumsizeofthemainearthingconductorshallbedeterminedinaccordancewithItem(a)andTable5.1inrelationtothecross-sectionalareaofthelargest

activeconductoroftheconsumersmains.

Thesizeofthemainearthingconductorneednotbedeterminedinrelationtothesizeofthelargestactiveconductoroftheconsumersmainsunderthefollowingconditions:

(i)Wheredoubleinsulationismaintainedbetweenthepointofsupplyandtheloadterminalsoftheprotectivedevicesonthesubmainsandfinalsubcircuitsoutgoingfromthemainswitchboard,theminimumsizeofthemainearthingconductormaybedeterminedinrelationtothecross-sectionalareaofthelargestactiveconductorofthelargestoutgoingsubmainorfinalsubcircuit.

(ii)Wherethecross-sectionalareaoftheconsumersmainsislargerthanthatrequiredtocarrythemaximumdemandoftheinstallationbecauseofvoltage-droplimitations,theminimumsizeofthemainearthingconductormaybedeterminedinrelationtothecross-sectionalareaoftheminimumcablesizerequiredtocarrythemaximumdemand.

Inanycase,thecross-sectionalareaofacoppermainearthingconductorshallbenotlessthan4mm2.

(d)AerialearthingconductorTheminimumsizeofanearthingconductorinstalledasanaerialconductorshallbedeterminedinaccordancewithItem(a)andTable5.1providedthatthecross-sectionalareaoftheearthingconductorsodeterminedshallbenotlessthanthesizespecifiedinCla