Copyright2001OTISGmbHBerlin
NopartofthisdocumentmaybecopiedorreproducedinanyformorbyanymeanswithoutthepriorwrittenconsentofOTISGmbH.
1EventMenu3
2EventDescription4
3SetUpParameter5
3.1FieldParameter(key:
333)5
3.2EngineeringParameter(key:
334)5
3.2.1ProfileParameter5
3.2.2ProfileDescription6
3.2.3ControlParameter7
3.2.4OtherParameter7
4RelayInterfaceParameter8
5InterfacetoRSLboard9
5.1DescriptionofthecontrolsignalsST1,ST2andST3:
10
5.2ErrordescriptionofInterfaceTest(keys324):
11
6SVTOOLShortkeys11
7Abbreviations11
Appendix:
BlankFormforInstallationParameterReports14
1EventMenu
InordertosimplifyinstallationandmaintenancetheDCSSrecordsallunusualeventsasapersistentlogging.Theeventsareclassifiedusingthefollowingconvention:
Example:
E39
YxxEventNumber
EventClass:
I:
Informationonly:
Resultsfromnormaloperation.Forexampleloggingof
powerupevents,reversaloperationetc.
W:
Maintenanceinformationonly:
DCSSisabletohandlethesituation-performancenotaffected.
Inspectionrecommended.Forexample:
Loggingfull
E:
Maintenancerequest:
Seriousevent,performancedegradationexpected.Maintenancerequired.Forexample:
3WireComFail.
Theloggingisavailableinthreedifferentrepresentationformsaslistedbelow.
History:
Showstheeventsintheorderoftheirappearance.Anincludedloggingtimestampgivestherelationtothepresenttime.
Actual:
Nonpersistentloggingofupto16verylastevents,startingwiththeoldestevent,loggingtimestampincluded.AdditionalinformationcanbedisplayedontheSVTOOLbypressingkey:
shift3
EvLog:
Amountofoccurrencesofeachevent-loggingtimestampincluded.RepresentationequalstoDCSS1-4loggings.
Del:
Deletestheloggedevents-clearmemoryfornewloggingperiod.
2EventDescription
Class
No.
Eventname
EventDescription
I
01
StartofLog
EntryindicatinganewLog-Startafterdeletingthepreviouslogging
W
02
LoggingFull
Eventloggingmemoryfull
-deleteloggingtofreememory
E
03
InverterProt
Peakoutputcurrentgreaterthan7A.Ifthiseventoccurs3timeswithin120sec,theDCSSswitchesintolockedmode.
E
04
MotorProtect
Motorcurrentwasfor10sechigherthansetuplimit.Ifthiseventoccurs3timeswithin120sec,theDCSSswitchestolockmode.
I
05
ObstaclDetec
Doorwasstalledduringclosing,thestalleddoorprotectionhasbeenactivatedmorethan10timesinseries.
E
06
EncoderErr
Oneortwotracksoftheencoderaredamaged.DCSSswitchesintoINImode.
Attention:
DuringINI/Nudgprofilesandwhilethedooriscreepingbeforeandafteramainprofile,encodererrorsarenotdetectable
W
07
Overvoltage
DC-Linkmaximumvoltage(450Vdc)exceeded–riskofdamageorlifetimereductionofDCSSpackage
W
08
Undervoltage
Powersupplyvoltageislessthan180Vac–riskofperformancedegration
I
09
PowerUp
IndicatesthattheDCSSisbootingafterpowerdown–
powerupsequence
E
13
3wireComFail
Indicatesthatthechecksequenceforthediscreteinterfacefailedthreetimes.
DCSSissetintolockedmode–Maintenancerequired
I
15
PositionErr
Doorrunsoutofthetoleratedend-positionrangeafterreaching[]or][.
I
17
StartInst
Automaticinstallationstarted
I
18
StopInst
Automaticinstallationstoppedbyusedrequest
I
20
InstSuccess
Automaticinstallationsuccessfulfinalized
W
21
Instfailed
Automaticinstallationterminatedwitherror
I
22
NewProfiles
Indicatesthatprofilesetupwasmodified
I
23
100xReversal
Xx100reversalsoccurred.Usethisinformationasdoormechanismstressindicator
E
24
SystemLocked
DCSSoutoforder,seriouseventoccurred–maintenance
required.DCSSisde-energizedanddoesnotreactoncommands.Rootcausecouldbe:
MotorProtect,InverterProtor3wireComFailevents.
UnlockDCSSperformimgpowerdown–powerupsequenceorSVTOOLkey-sequence‘shift5’
W
25
StalledDoor
Doorstalledduringopeningoperation,
DcssswitchestoInimode
I
26
OpenTimeout
DCSSwasnotabletoopenthedoorwithin15sec
I
27
CloseTimeout
DCSSwasnotabletoclosethedoorwithin15sec
I
28
3wireCom
IndicatessuccessfuldiscreteI/Ochecksequence
3SetUpParameter
3.1FieldParameter(key:
333)
Thismenugrantsaccesstoprofileparameterswhichhelptoadaptthedoorperformanceonthecustomerexpectation.Enterthesub-menu1forprofileset1parametersandthesub-menu2forprofileset2parameters.
name
range
Unit
defaultValue
description
Px:
OpenRunTime
1500.....8000
ms
3500
Tochangetheopenspeedonlythisparametermustbemodified.Thereisnoimpactonotherparameters.
Px:
StartOpnDist
1...150
mm
50
Distancefromcloseddoortostartpointofaccel.
Px:
StartOpnSpeed
2...10
Hz
4
Speedatthebeginofopeningrun
Px:
OpenCrpDist
1...150
mm
20
Creepdistanceaftermainprofile
Px:
OpenCrpSpeed
2...15
Hz
4
Creepspeedatendofopeningrun
Px:
ClsRunTime
2500.....8000
ms
3500
Tochangetheclosespeedonlythisparametermustbemodified.Thereisnoimpactonotherparameters.
Px:
StartClsDist
1...150
mm
20
Distancefromopeneddoortostartpointofaccel.
Px:
StartClsSpeed
2...10
Hz
6
Speedatthebeginofclosingrun
Px:
ClsCrpDist
1...150
mm
50
Creepdistanceaftermainprofile
Px:
ClsCrpSpeed
2...15
Hz
3
Creepspeedatendofclosingrun
Ix:
OpnRunTime
5000
12000
ms
6000*
TochangetheIniopenspeed
Ix:
ClsRunTime
5000
12000
ms
6000*
TochangetheIniclosespeed
Px:
NdgClsRunTime
5000......12000
ms
6000*
Tochangetheclosenudgingspeedprofile
Px:
ClsIdleTorque
10...200
N
50
Forcetoholdthedoorclosedatidlestate
Px:
OpnIdleTorque
10...200
N
60
Forcetoholdthedoorclosedatidlestate
∙dependsondoorwidthsetup
3.2EngineeringParameter(key:
334)
3.2.1ProfileParameter
Thismenuisforwelltrainedadjustersonly.Enterthesub-menu1forprofileset1parametersandthesub-menu2forprofileset2parameters.
name
range
unit
default
value
description
Px:
OpenAccelTime
15...50
%
35
accelerationtimeofmainopenprofile
Px:
OpenDecelTime
15...50
%
35
decelerationtimeofmainopenprofile
Px:
ClsAccelTime
15...50
%
35
accelerationtimeofmaincloseprofile
Px:
ClsDecelTime
15...50
%
35
decelerationtimeofmaincloseprofile
Px:
OpenCreepTorque
0...150
%
107*
torqueatcreepspeedbeforeandafteropenmainprofile
Px:
ClsCreepTorque
0...150
%
107*
torqueatcreepspeedbeforeandafterclosemainprofile
Px:
CloseTorque
0...150
%
80*
torqueduringclosemainprofile
Px:
HaltTorque
0...150
N
60
toquetoholdstoppeddooratposition
Px:
NudgingTorque
0...150
%
107*
torqueduringclosenudgingmainprofile
Px:
IniTorque
0...150
%
107*
torqueduringiniprofilerun
*setbyautomaticlearnrun
3.2.2ProfileDescription
note:
AdetaileddescriptionofallprofiletypeswillbefindintheFieldComponentManual-Guidelines
3.2.3ControlParameter
name
range
unit
default
value
description
Px:
P-Gain
0...300
100
GainfactorofP-Controller
IncreasingoftheP-Gainparameterincreasestheclosedloopimpact.Wrongadjustmentcancause
over-currentsand/orbadtrackingbehavior.
Px:
FeedUp-Gain
0...12
4*
DecreasingoftheFeedUp-Gainparameterresultsinstrongerandfasteraccelerationtocompensatetheslippageduringacceleration.
Px:
FeedDown-Gain
0...12
4*
DecreasingoftheFeedDown-Gainparameterresultsinstrongerandfasterdeceleration.
*setbyautomaticlearnrun
3.2.4OtherParameter
name
range
unit
default
value
description
maxMotorCurrent
800.......5000
mA
4000
limitofmax.motorcurrent.iflimitexceeded3timesformorethan10secDCSSshutsdownandislocked
PassProtLimit
0...100
%
4
sensitivityofstalleddoorprotectionin%
StopDistance
30...150
mm
60
reversalstopdistanceinmm
EndPosRange
10..100
mm
20
toleratedderivationfrom[]or][positioninmm
GSMPosition
50...500
mm
150
GSMactivebefore][inmm
Px:
LockDistance
0...150
mm
50*
Positionwerecar&landingdoorsareclosed,butthelockisstillopen
OpnLockSpeed
0...10
Hz
5
InordertospeeduptheunlockingphasesetparameterhigherthanOpenCreepSpeed
ClsLockSpeed
0...10
Hz
5
InordertospeedupthelockingphasesetparameterhigherthanCloseCreepSpeed
DisabRevDistOpn
0...200
mm
30
reversalisdisabledif:
position>doorwidth-DisabRevDistOpn
DisabRevDistCls
20...200
mm
0
reversalisdisablediflandingdoorislessthan
DisabRevDistClsbeforefullyclosed
*setbyautomaticlearnrun
4RelayInterfaceParameter
ThissetofparameterisonlyavailableiftheDCSS5interfaceisprogrammedforaRelayController(seeSetupConfiguration).
name
range
unit
default
value
description
DOS-Operation
0/1
0
setdifferentoperationofREL3:
0:
setREL3ifdoorreachesprogrammedopenposition
1:
setREL3ifdoorisopening,resetifDOLisreached
EFS-Operation
0/1
0
setdifferentoperationofinputE2,ifactive:
0:
selectasecondspeedprofileatnormalrun
1:
EFSoperation,disablesallreversaldevicesincl.PP
REL1-Distance
1...255
mm
25
DOLsignal,ifposition>(doorwidth-REL1distance)thensetREL1,direction=open
REL2-Distance
1...255
mm
25
DCLsignal,ifpositiondirection=close
REL3-Distance
1...255
mm
20
GHsignal,ifpositiondirection=close
REL4-Close-Dist
1...255
mm
20