给水管网课程设计.docx
《给水管网课程设计.docx》由会员分享,可在线阅读,更多相关《给水管网课程设计.docx(36页珍藏版)》请在冰豆网上搜索。
给水管网课程设计
给水管网课程设计
说明书
姓名:
李悦
学号:
20070130211
专业班级:
给排水工程二班
目录
Ⅰ.给水管网课程设计任务书·········································3
一、设计项目·····················································3
二、设计任务·····················································3
三、设计资料·····················································3
Ⅱ.给水管网设计计算说明书·········································5
一、输配水系统布置···············································5
二、设计用水量及调节构筑物相关计算······························5
1设计用水量计算············································5
2设计用水量变化规律的确定··································7
3清水池、水塔调节容积的计算·································7
三、经济管径确定················································11
1沿线流量及节点流量·······································11
2初始分配流量·············································13
3管径的确定···············································13
四、管网水力计算···············································15
1初步分配流量·············································15
2管网平差··················································15
3控制点与各节点水压的确定·································15
4泵扬程与水塔高度的计算···································17
五、泵的选择····················································19
1最高时工况初选泵·········································19
2最大转输工况校核·········································19
3消防工况校核·············································21
4泵的调度··················································24
六、成果图绘制··················································-
参考文献··································································25
Ⅰ.给水管网课程设计任务书
一、设计项目
某市给水管网课程设计
二、设计任务
根据所给资料,应完成下列任务:
1、进行输配水系统布置,包括确定输水管、干管网、调节水池(如果设置的话)的位置和管网主要附件布置;
2、求管网、输水管、二级泵站的设计用水量与调节水池的容积;
3、计算确定输水管和管网各管段管径;
4、进行管网水力计算;
5、确定二级泵站的设计扬程,如果有水塔,确定水塔的设计高度;
6、确定二级泵站内水泵的型号与台数(包括备用泵),并说明泵站在各种用水情况下的调度情况;
7、画出管网内4~6个节点详图。
三、设计资料
1、某市规划平面图一张。
2、某市规划资料。
某市位于湖南的东部,濒临湘江。
近期规划年限为6年,人口数为12万,城区大部分房屋建筑控制在6层。
全市内只有两家用水量较大的工业企业,其用水量及其他情况详见表1。
表1工业企业近期规划资料
企业
项目
1
2
1.企业用水量(米
/日)
2400
3600
工业用水对水质要求
同生活饮用水
同生活饮用水
工业用水对水要求
不小于24米
不小于24米
2.工厂房屋耐火等级
二
三
工程生产品危险等级
丙
乙
工厂房屋最大体积(m2)
10000(厂房)
5000(库房)
工厂面积(公顷)
24
20
3、补充说明
1)管网管径原则上按简化公式
计算确定,式中,经济因素f=0.92,管线造价中的指数α=1.8。
2)工业企业每小时耗用生产用水量相同。
铁路车站每天用水量为2000吨,按均匀用水考虑。
3)不论设计年限内最高日用水量是多少,均嘉定其用水量变化如表2所示。
4)城市生活污水和工业废水经适当处理后排入水体下游。
河流水量充足,能做给水水源,水厂位置如平面图所示。
5)冰冻深度0.2米,地下水离地面3米。
6)其他资料见平面图。
表2最高日内小时用水量变化
时间
0~1
1~2
2~3
3~4
4~5
5~6
6~7
7~8
8~9
9~10
10~11
11~12
占日用水量比例(%)
1.60
1.47
1.43
2.36
2.36
4.15
5.14
5.96
6.1
5.89
5.07
5.35
时间
12~13
13~14
14~15
15~16
16~17
17~18
18~19
19~20
20~21
21~22
22~23
23~24
占日用水量比例(%)
5.35
5.35
5.27
5.52
5.75
6.03
5.72
5.00
3.19
2.69
2.58
1.87
Ⅱ.给水管网设计计算说明
第一节输配水系统布置
根据所给资料,结合城镇规划并考虑经济性和供水可靠性的要求,决定了采用城区环状给水、郊区及河边树状给水的布置形式,在高地布置水塔,水塔自工业企业No.1接入管网,水厂至管网双管输水。
第二节设计用水量及其调节构筑物相关计算
1设计用水量计算:
基本数据:
由原始资料该城市位于湖南,在设计年限内人口数12万,查《室外排水设计规范》可知该城市位于一分区,为中小城市。
城市的未预见水量和管网漏失水量按最高日用水量的20%计算;
1.1.1居民最高日生活用水量Q1:
Q1=qNf
Q1―—城市最高综合生活用水,m3/d;
q――城市最高综合用水量定额,L/(cap.d);
N――城市设计年限内计划用水人口数;
f――城市自来水普及率,采用f=100%
所以:
Q1.1=230×12×104×100%/1000
=27600m3/d
1.1.2铁路车站每天用水量Q1.2=2000m3/d。
得Q1=Q1.1+Q1.2=29600m3/d。
1.2工业区的用水量计算
由所给资料得知,工厂No.1企业总用水量为2400m3/d,工厂No.2的企业总用水量为3600m3/d。
总计,Q2=2400+3600=6000m3/d。
1.3浇洒道路用水量计算
按城市浇洒道路用水量标准q=1L/(㎡.次),每天两次,
用水量公式:
=qNn/1000(n代表次数,N代表浇洒道路面积),
=1*1434721.162*2/1000
=2870m3。
1.4绿化用水量计算
按城市大面积绿化用水量定额q=1.5L/(㎡.次),每天两次,用水量公式
=qNn/1000(n代表次数,N代表绿化用水面积),=1.5*454356.5206*2/1000
=1360m3。
1.5未预见用水量的计算
按最高日用水量的20%算。
而最高日的用水量包括居民的综合生活用水量;工业区用水量;浇洒道路和绿化用水量。
相应的未预见用水总量。
1.6最高日设计流量Qd:
Qd =1.2×(Q1+Q2+Q3+Q4)
=1.2×(29600+6000+2870+1360)
=47796m3/d
最高日最高时用水量Qh
Qh=Kh×Qd/86.4
=1.46×47796/86.4
=807.66L/s
(时变化系数由原始资料知Kh=1.46)
1.7消防用水量:
城镇、居住区室外的消防用水量:
火灾次数:
2
一次灭火用水量:
45L/s
城镇消防用水量为90L/s
工厂消防用水量:
No.1火灾次数:
1
一次灭火用水量25L/s
No.2火灾次数:
1
一次灭火用水量:
30L/s
2设计用水量变化规律的确定
根据所给资料,绘制出日用水量曲线,综合实际情况,决定采用分级供水:
20~次日5时共9小时,泵站供水量为2.78%Qd,用户为用水量输送至水塔;5~20点共15小时,泵站供水量为5.00%Qd,不足水量用水塔供给。
3清水池、水塔调节容积的计算
由用水量变化曲线与分级供水线求得清水池与水塔的调剂容积,如下表:
清水池与水塔调节容积计算
时间
用水量(%)
二级泵站供水量(%)
一级泵站供水量(%)
清水池调节容积(%)
清水池调节容积(m3)
水塔调节容积(%)
水塔调节容积(m3)
0-1
1.6
2.78
4.17
-1.39
-664.36
-1.18
-563.99
1–2
1.47
2.78
4.17
-1.39
-664.36
-1.31
-626.13
2–3
1.43
2.78
4.16
-1.38
-659.58
-1.35
-645.25
3–4
1.43
2.78
4.17
-1.39
-664.36
-1.35
-645.25
4–5
2.36
2.77
4.17
-1.40
-669.14
-0.41
-195.96
5–6
4.15
5.00
4.16
0.84
401.49
-0.85
-406.27
6–7
5.14
5.00
4.17
0.83
396.71
0.14
66.91
7–8
5.69
5.00
4.17
0.83
396.71
0.69
329.79
8–9
6.1
5.00
4.16
0.84
401.49
1.10
525.76
9–10
5.89
5.00
4.17
0.83
396.71
0.89
425.38
10–11
5.07
5.00
4.17
0.83
396.71
0.07
33.46
11–12
5.35
5.00
4.16
0.84
401.49
0.35
167.29
12–13
5.35
5.00
4.17
0.83
396.71
0.35
167.29
13-14
5.35
5.00
4.17
0.83
396.71
0.35
167.29
14-15
5.27
5.00
4.16
0.84
401.49
0.27
129.05
15-16
5.52
5.00
4.17
0.83
396.71
0.52
248.54
16-17
5.75
5.00
4.17
0.83
396.71
0.75
358.47
17-18
6.03
5.00
4.16
0.84
401.49
1.03
492.30
18-19
5.72
5.00
4.17
0.83
396.71
0.72
344.13
19-20
5.00
5.00
4.17
0.83
396.71
0.00
0.00
20-21
3.19
2.77
4.16
-1.39
-664.36
0.42
200.74
21-22
2.69
2.78
4.17
-1.39
-664.36
-0.09
-43.02
22-23
2.58
2.78
4.17
-1.39
-664.36
-0.20
-95.59
23-24
1.87
2.78
4.16
-1.38
-659.58
-0.91
-434.94
合计
100.00
100.00
100.00
12.50
5974.50
7.65
3656.39
3.1清水池所需有效容积计算
清水池调节容积为
=12.50%*47796=5974.5m3
水厂自用水量调节容积按最高日用水设计用水量的5%计算,则
=5%*47796=2389.8m3.
该城镇人口数12万人,则确定同一时间内的火灾次数为2次,一次灭火用水量为45L/s。
火灾延续时间按2h计,故火灾延续时间内所需总用水量为
=2*45L/s*3.6*2h=648m3.
另需一部分安全储量
,则清水池的有效容积可按以上三部分容积和取整,得:
W清=
+
+
+
=9012.3+
m3=10000m3
如采用两座钢筋混凝土水池,每座池子有效容积为5000m3。
3.2水塔有效容积计算
水塔调节容积为
=7.65%*47796
=3656.39m3
故水塔的有效容积为
Wt=
+
=3656.39+6=3665.39m3。
其中
——水塔调节容积,m3;
——室内消防贮备水量,m3,按10L/s计。
最高日设计用水量为:
47766(m3/d),管网中设置对置水塔
最高用水时(8~9点)水塔的设计供水流量为:
47796×(6.10%-5.00%)×1000/3600=146.04(L/s);
最大传输时(3~4点)水塔的最大进水流量为:
47796×(2.78%-1.43%)×1000/3600=179.24(L/s)。
第三节经济管径确定
1沿线流量及节点流量
从整个城镇管网分布情况来看,干管的分配比较均匀,故按长度流量法计算。
1.1配水干管计算长度:
二级泵站-1为输水管,不参与配水,其计算长度为零。
管段1-2,2-3,16-17,17-18,为单侧配水,其计算长度按实际长度的一半计入。
其余均为双侧配水管段,均按实际长度计入。
则:
=20339.4m
1.2配水干管比流量:
最高时总用水量可从用水量计算表中查得为807.66L/s.大用户集中用水量包括
工业区1:
Q1==2400m3/d=27.78L/s
工业区2:
Q2=3600m3/d=41.67L/s
车站Q3=2000m3/d=23.15L/s
则由公式有
=[807.66-(27.78+41.67+23.15)]/20339.4
=0.0351564L/(s·m)。
1.3沿线流量:
各管段的沿线流量计算见下表:
各管段的沿线流量计算
管段编号
管段长度/m
管段计算长度/m
比流量/L/(s.m)
沿线流量/L/s
1-2
656.9
328.45
0.0351564
11.547
2-3
716
358
12.586
3-4
1066.3
1066.3
37.487
4-5
716
716
25.172
2-5
1066.9
1066.9
37.508
5-6
644.5
644.5
22.658
1-6
985.9
985.9
34.661
6-9
1078.1
1078.1
37.902
9-10
644.3
644.3
22.651
10-11
716
716
25.172
4-11
1078.1
1078.1
37.902
5-10
1078.1
1078.1
37.902
11-12
1037.3
1037.3
36.468
13-14
644.1
644.1
22.644
9-14
1037.3
1037.3
36.468
12-13
716
716
25.172
10-13
1037.3
1037.3
36.468
12-18
912.8
912.8
32.091
16-17
643.9
321.95
11.319
13-17
912.8
912.8
32.091
17-18
716
358
12.586
14-16
912.8
912.8
32.091
6-7
611.5
611.5
21.498
8-9
613.9
613.9
21.583
14-15
610.5
610.5
21.463
12-19
852.5
852.5
29.971
合计
20339.4
715.060
1.4节点流量计算:
工业区1由节点18集中供水,其集中流量为27.78L/s,
工业区2由节点16供水,则其集中流量为41.67L/s,
车站由节点11供水,则其集中流量为23.15L/s。
各节点的节点流量计算表如下:
各管段节点流量计算
节点
连接管段
节点流量L/s
集中流量L/s
节点总流量L/s
1
1-2,1-6
23.104
23.104
2
1-2,2-5,2-3
30.821
30.821
3
3-4,2-3
25.037
25.037
4
3-4,4-11,4-5
50.281
50.281
5
5-6,2-5,5-10,4-5
61.620
61.620
6
5-6,1-6,6-9,6-7
58.360
58.360
7
6-7
10.749
10.749
8
8-9
10.791
10.791
9
6-9,9-14,9-10,8-9
59.302
59.302
10
10-11,5-10,10-13,9-10
61.097
61.097
11
11-12,4-11,11-10
49.771
23.150
72.921
12
12-19,12-13,12-18,12-11
61.851
61.851
13
13-10,13-17,13-12,13-14
58.187
58.187
14
14-15,14-13,9-14,14-16
56.333
56.333
15
15-14
10.731
10.731
16
16-14,16-17
21.705
41.670
63.375
17
16-17,17-13,17-18
27.998
27.998
18
17-18,12-18
22.338
27.780
50.118
19
19-12
14.985
14.985
总计
715.060
807.660
最高时总用水量L/s
大用户集中用水量L/s
管网总长m
比流量L/(s.m)
807.660
92.600
20339.4
0.035
2初始分配流量
根据节点流量连续性方程和供水的经济型与可靠性,
初始分配流量如下表:
管段编号
初始分配流量L/s
管径确定
公式算得管径(mm)
对应标准管径(mm)
处理后(连接管、分界线处放大)
1-2
320
606.6
600
600
2-3
150
438.6
450
450
3-4
124.96
405.7
400
400
4-5
19
181.2
200
300
2-5
139.18
424.8
450
450
5-6
35
235.4
250
350
1-6
318.61
605.4
600
600
6-9
214.5
511.2
600
600
9-10
26
207.2
200
300
10-11
19
181.2
200
250
4-11
93.68
358.6
350
350
5-10
93.56
358
350
350
11-12
39.76
248.55
250
350
13-14
18.98
181.14
200
250
9-14
118.41
396.43
400
400
12-13
18.55
179.4
200
250
10-13
39.46
247.74
250
350
12-18
18.53
179.3
200
400
16-17
31
223.45
250
300
13-17
18.3
178.34
200
350
17-18
77
329.77
350
400
14-16
32.37
227.62
250
350
6-7
10.75
142
150
150
8-9
10.79
142.3
150
150
14-15
10.73
141.9
150
150
12-19
14.99
163.7
200
200
3管径的确定
根据设计资料中的要求,经济管径原则上按简化公式
计算确定(f=0.92,α=1.8),计算时采用海森威廉公式(
),取m=4.87,n=1.852。
而由于最高时采用多水源供水,管网中存在供水分界线,分界线上的节点流量一般由两个水源共同供给,因此应适当放大供水分界线附近管段。
另外,考虑到事故时需要,连接管也应适当放大一