SH30041999石油化工采暖通风与空气调节设计规范英文版.docx
《SH30041999石油化工采暖通风与空气调节设计规范英文版.docx》由会员分享,可在线阅读,更多相关《SH30041999石油化工采暖通风与空气调节设计规范英文版.docx(59页珍藏版)》请在冰豆网上搜索。
![SH30041999石油化工采暖通风与空气调节设计规范英文版.docx](https://file1.bdocx.com/fileroot1/2022-11/22/1372b6e6-199b-4422-ab3d-756fac4f9734/1372b6e6-199b-4422-ab3d-756fac4f97341.gif)
SH30041999石油化工采暖通风与空气调节设计规范英文版
SH3004-1999石油化工采暖通风与空气调节设计规范(英文版)
UDC
SH
IndustrialStandardofthePeople'sRepublicofChina
SH3004-1999
DesignCodeforHeating,VentilationandAir
ConditioninginPetrochemicalIndustry
石油化工采暖通风与空气调节设计规范
IssuedonApril15.1999ImplementedasofSeptemberL1999issuedbyTheStateBureauofPetroleum&ChemicalIndustry
IndustrialStandardofthePeople'sRepublicofChina
SH3004-1999
DesignCodeforHeating,VentilationandAirConditioningin
PetrochemicalIndustry
Preparedby:
LanzhouDesignInstituteofChinaPetrochemicalGroup
Corporation
EditedandCompiledby:
ChinaPetrochemicalGroupCorporation
Approvedby:
StateBureauofPetroleumandChemicalIndustry
1999,Beijing
Introduction
ThisCodeisprovidedonthebasisoftherevisionsmadetotheoriginaleditionof''DesignCodeforHeating,VentilationandAirConditioninginPetrochemicalIndustry''byourInstitutewiththeparticipationofBeijingPetrochemicalEngineeringCompanyaccordingtotheNoticeofDocumentNo.Jian-Bia-Zi-269issuedbyChinaPetrochemicalGroupCorporation.
ThisCodeisdividedinto5chaptersand3appendixes.Themaincontentsofthisrevisionareasfollows:
1.Theprovisionsintheoriginalcodewhicharenotadaptivetothenationalcurrentcodesarerevised,suchastheclassiflcationofexplosionhazardousareas,thepositivepressurevaluesofpositive-pressuretypeexplosion-proofelectricalequipment,thegasemissionstandards,airductmaterialsforventilationandairconditioning,etc.,soastomakethemcomplywiththenationalcurrentstandards.
2.AccordingtothegistofnSeveralProvisionsforPlantDesignofChinaPetrochemicalGroupCorporationclausesintermsofthereductionsinpersonnel,landcoverageandinvestment,savingenergy,etc.,havebeenrevisedandadded.
3.TakingintoaccountthewideapplicationsoftheDistributedControlSystem(DCS)inthepetrochemicalprojects,theexperienceinthedesignoftheairconditioningfortheDCScontrolroomhasbeensummedup,andtheclausesintermsoftheenvironmentalconditionsforDCScontrolroom,thecontrolandoperationofairconditioningsystem,theaircurrentcomposition,etc.,havebeenaddedandrevised.
4.Apartoftheclausesregardingsafetyaspectshavebeenaddedandrevised,suchasthecentralizedmonitoringandcontrolofthemajorventilationandairconditioningunitsandstandbyoftheequipment,theinterlocksoftheairconditioningunitsofDCScontrolroomwiththefireautomaticalarmsystem,theexhaustoftheroomsequippedwiththefullgassubmergingfirefightingsystem,etc.
5.Thoseclausesintheoriginalcodewhichareseldomusedordifficulttofunction,arecancelledormodified,suchasheatingwithsteam-ejectionhotwater,therecycleofcondensateforthesteamheatingsystem,diffusiveexplosionhazardoussubstancesorharmfulgasesandvapor,anddistributionofoverallexhaustratefortheplantbuildings,etc.
Duringrevision,widesurveysandstudieshavebeenmadebasedontheproblemsexistingintheoriginalcode,thepracticalexperiencesoftherecentyearsinthedesignofheating,ventilationandairconditioninginthepetrochemicalindustryhavebeensummedup,thecommentsontherelevantdesign,construction,operations,etc.,havebeenaskedfor,themajorproblemsfoundhavebeendiscussedseveraltimesandthecodeisflnalizedafterreviewismade.
IncaseanymodiHeationandsupplementationisfoundnecessaryduringtheimplementationofthisCode,pleaseprovidethecommentsandrelevantinformationtoourinstitute,sothatthereferencecanbemadetoforlaterrevisionofthisCode.
Addressofourinstitute:
1,FuliWestRoad,XiguDistrict,LanzhouCity,
GansuProvincePostCode:
730060
ThiscodeismainlypreparedbyLanzhouDesignInstitute,ChinaPetrochemicalGroupCorporationwiththeparticipationofBeijingPetrochemicalEngineeringCompany,ChinaPetrochemicalCorporation
KeyDraftsman:
JiangWeihan,ChiChimlin,ShiQiuheandBaoChangwei
CONTENTS
1.GeneralPrinciples8
2.Heating9
2.1GeneralProvisions9
2.2HeatingSystem10
3.Ventilation13
3.1GeneralProvisions13
3.2NaturalVentilation17
3.3MechanicalVentilation18
3.4EmergencyVentilation24
3.5EquipmentandAirDucts27
4.AirConditioning29
4.1GeneralProvisions29
4.2CalculationofLoads32
4.3SystemDesign34
5.FirePreventionandExplosionProtection...39
5.1FirePreventionandExplosionProtectionof
HVACSystem39
5.2FirePreventionandExplosionProtectionofVentilationandAirConditioningSystem....41
5.3Plenums47
5.4PositiveDraftforMotors49
AppendixA・CalculatedIndoorTemperaturesfor
HeatinginWinter51
AppendixB・NumbersofAirChangesfor
PetrochemicalShops54
57
AppendixC•NumbersofAirChangesforPlenums
NotesofWording57
Attachment:
ExplanatoryNotes
1.GeneralPrinciples
1.0.1ThisCodeisestablishedforthepurposeofimplementingtherelevantnationalgeneralandspecificpoliciesinthedesignofheating,ventilationandairconditioning(HVAC)forthepetrochemicalenterprises,soastoprovidenecessaryconditionsforsafeproductionactivities,improvementoflaborconditions,productqualityassurance,environmentalprotectionandrationalutilizationofresources.
1.0.2ThisCodeisapplicabletothedesignofHVACofthenewlyconstructed,expandedandrebuiltproductionplantbuildingsandannexbuildingsforthepetrochemicalenterprises.
1.0.3TheoperationstatusandmajorparametersshallbecentrallymonitoredandcontrolledforthoseHVACunitswhichexertsrelativesignificanteffectontheproductionsafetyandproductquality.
1.0.4Inthedesign,thefull-tineorpart-timespecializedtechnicalpersonnelandtheoperationandmaintenancepersonnel,aswellastheappropriatetestinginstrumentsshallbespecifiedaccordingtothequantity,importanceandcomplexityleveloftheHVACunits.
1.0.5DuringtheimplementationofthisCode,therequirementssetinthenationalcurrentmandatorystandardHDesignCodeforHeating,VentilationandAirConditioninginPetrochemicalIndustrynandtheotherrelevantcurrentstandardsandspecificationsshallbesatisHed.
2.Heating
2.1GeneralProvisions
2.1.1Centralizedheatingsystemshallbeprovidedfortheplantbuildingsandtheannexbuildingsintheregionswherethenumberofdayswithameandailytemperatureforyearsconstantly<5°Cisgreaterthan90days,andtherearesomepeopleusuallystayinginroomsorcertainrequirementsforroomtemperaturesmadefortheproduction.
2.1.2Centralizedheatingsystemisallowedtoprovidefortheplantbuildingsandannexbuildingsintheregionswherethenumberofdayswithameandailytemperatureforyearsconstantly<5°Cis45〜59days,andthemeanRHvalueforthecoldestmonthsforyearsisequaltoorgreaterthan75%andthereareoperationpersonnelstayingcollectivelyandfrequently,providedthatthereiswasteheatintheplantareathatcanbeutilizedanditisapprovedbythedepartmentincharge.
2.1.3CentralizedheatingsystemisallowedtoprovideforplantbuildingsandannexbuildingsintheregionsotherthanthatasspecifiedinClause
2.1.1andClause2.1.2ofthisCodewhentherearespecialrequirementsfortheambienttemperaturemadeforproduction.
2.1.4Asfortheproductionplantbuildingsprovidedwiththecentralizedheating,whenthereinnospecialrequirementsfortheambienttemperaturemadeforproductionandthebuildingareausedbyeachworkerdoesnotexceedlOOur,itisnotsuggestedtoprovideanoverallheating,however,thelocalheatingshallbeprovidedinthefixedworkpoints,andwhentheworkpointsarenotfixed,theheatingroomshallbeprovided.
2.1.5Theheatingmediumforthecentralizedheatingshallbedeterminedaccordingtotheeconomicandtechnicalevaluationsontheheatsupplyconditionsoftheplantarea.Firstofall,thewasteheatofproductionshallbeutilized,anditisrecommendedtousehotwaterasheatingmedium,andwhentheheatinginplantareamainlyusesthesteamforproduction,thesteamshallbeusedastheheatingmedium.Itissuggestedtorecyclethecondensate.
2.1.6Inthedesignofcentralizedheating,thecalculationofinteriortemperatureinwintershallbemadeanddeterminedaccordingtothefactorsofthepurposesofrooms,productioncharacteristics,laborintensity,levelofautomationandmechanization,conditionsofmaintenanceandpersonnelstay,etc.ThecalculationofinteriortemperatureforheatingoftheroomsofgeneralproductionplantbuildingsandannexbuildingsshallbemadeanddeterminedaccordingtoAppendixAtothisCode.
2.2HeatingSystem
2.2.1Selectionofheatingsystemsshallcomplywiththefollowingprovisions:
(1).Whenhotwaterisusedasheatingmedium,itisrecommendedtousedasinglepipelinesystemforthemulti-storeybuildings.
(2).Whensteamisusedasheatingmedium,itisrecommendedtousedual-pipingsystemforsupplyingsteamwithrisesanddistributingwithdowncomers.
2.2.2Selectionofradiatorsshallcomplywiththefollowingprovisions:
(1).Itisrecommendedtousetheradiatorsthatareeasytobecleanedfortheproductionplantbuildingswithrelativelyhighrequirementfordustdispersion
ordustproof.
(2).Itisrecommendedtousetheradiatorsmadeofironcastingfortheproductionplantbuildingsinwhichthecorrosivegasesaredispersedortheroomrelativehumidityishigh.
(3).Itisrecommendedtousetheradiatorswithaniceappearancefortheadministrativeofficesandtheroomsforthelivingandwelfarepurposes,laboratories,instrumentcontrolrooms,etc.
(4).Theplate-type,flat-tubingtypeandsteel-sheetpillartyperadiatorsshallnotbeusedinthesteamheat