RSLogixEmulator5000手册
AQuickTutorialonRSLogixEmulator5000
RSLogixEmulator5000isasoftwaresimulatorfortheAllenBradleylineofLogix5000controllers(ControlLogix®,CompactLogix®,FlexLogix®,SoftLogix5800®andDriveLogix®). ThegoalistomimicthefunctionofaPLCwithouttheactualhardwareandthusdoadvanceddebugging. MoreinformationcanbefoundintheABpublicationLGEM5K-GR015A-EN-P.
Asaquickintroductionwe’llgothroughasimpleexampleofsettingupasimulation. Thisinvolvesthreemajorsteps.
1.Settingupthechassismonitor.
2.CreatingaconnectioninRSLinx.
3.Creatingaprojectwithassociatedemulationhardware.
SettinguptheChassisMonitor
TostarttheChassisMonitor,clickStart>Programs>RockwellSoftware>RSLogixEmulate5000>RSLogixEmulate5000ChassisMonitor.
Whentheemulatoropensupyou’reconfrontedwithwhatlookslikeanemptychassis. Inslot0isanRSLinxmodulewhichhastobetherefortheemulatorcommunicationstowork. Yourslot1mighthaveanotherirremovableRSLinxmoduledependingifyouarerunningRSLogixEnterprise.
Fromherewesetupourhardwareconfigurationforsimulation. OurfirststepwillbetoaddtheCPU. InthiscaseitisaspecialonecalledanEmulationController.
1.ClickSlot>CreateModule.
2.ChoosetheEmulatorRSLogixEmulate5000Controller.
3.Choseslot2forthecontroller
4.ClickOKtoaddittothechassismonitor.
5.Atthispointyoumaybeaccostedwithamessageaboutpreviousconfigurations. JustselectResettheConfigurationtoDefaultValuesandclickNEXT.
6.Thenexttwodialogscreensareforsettingupthecontrollerdetails. ClickNEXTandFINISHtoacceptallthedefaults.
Nextwe’lladdsomeinput/outputsimulation.
1.ClickSlot>CreateModule.
2.Choosethe1789-SIM32PointInput/OutputSimulator.
3.Choseslot3forthesimulatorandclickOK.
4.AcceptthedefaultsforthesetupbyclickingNEXTandFINISH.
Thechassismonitorwillnowhavetwoemulationmodulesinitreadytogo.
CreatingaconnectioninRSLinx
1.StartRSLinxunderStart>Programs>RockwellSoftware>RSLinx>RSLinxClassic
2.ClickCommunications>ConfigureDrivers.
3.SelecttheVirtualBackplane(SoftLogix58xx)driverfromtheAvailableDriverTypeslist.
4.ClickAddNew.TheAddNewRSLinxDriverdialogboxappears.ClickOK.
5.ThenewdriverappearsintheConfiguredDriverslist.ClickClose.
UsingRSLogixEmulatorinaProject
Tousetheemulatorinaprojectyoumustsetupthehardwarecorrectly.
1.StarttheRSLogix5000softwareandcreateanewproject.
2.UndertheNewControllerwindowtypeselectanEmulator–RSLogixEmulator5000Controller. GiveitanameandassignittothesameslotastheoneyouputintheChassisMonitorwhichinourexampleisslot2. ClickOK.
3.InRSLogix5000'sControllerOrganizer,rightclickontheI/OConfigurationfolder,andthenclickNewModule.ThesoftwaredisplaystheSelectModulewindow.
4.OpentheOtherfolder.Selectthe1756-MODULEfromthemoduleslistandthenclickOK.
5.ThesoftwaredisplaystheNewModulewindow.
a. AddaNameforthecard.
b. IntheSlotfieldputthenumberthatcorrespondswiththeChassisMonitor.
c. FortheConnectionParametersputinthefollowingandclickOK
AssemblyInstance
Size
Input
1
2
Output
2
1
Configuration
16
0
6.
7.
8.OnthenextModulePropertiesscreenmakesuretochangetheRequestedPacketIntervalto50.0ms.
Ready,Set,Go
YouarenowreadytousetheemulatorjustlikeyouwouldanyotherPLC. OpenWhoActiveandsetthepathtotheRSLogix5000Emulator.
Theinputscanbesimulatedintheemulator’sChassisMonitorbyrightclickingonthemoduleandselectingProperties. UndertheI/ODatatabistheabilitytotoggleeachoftheinputsonoroff.