NFPA.docx

《NFPA.docx》由会员分享,可在线阅读,更多相关《NFPA.docx(20页珍藏版)》请在冰豆网上搜索。

NFPA.docx

NFPA

Chapter3-6-FireProtectionStandardforCorrectionalInstitutions

(PubliéaussienfrançaissousletitreChapitre3-6-Normessurlaprotectioncontrel'incendiepourlesétablissementsdedétention)

TableofContents

1.General1

2.Generalrequirements3

3.Construction4

4.Occupancyhazards6

5.Fireprotectionsystems7

6.Watersupplies10

7.Electrical11

8.Emergencyprocedures12

9.Maincommunicationandcontrolpost/communicationequipmentroom(mccp/cer)13

AppendixA14

Appendix B18

Appendix C20

1.General

1.1Purpose

ThisstandardprescribesfireprotectionrequirementsforcorrectionalinstitutionstominimizeriskstolifeandpropertyandtoprotectandconservetheGovernment'sfinancialposition.

1.2Application

(a)ThisstandardappliestocorrectionalinstitutionsundertheadministrationoftheCorrectionalServiceofCanada.

(b)Abuildingorstructureinaninstitutionthatisusedforfarmingpurposesandnotasaresidenceisexemptfromtherequirementsofthisstandard.(Seeappendix A)

(c)Communityresidentialfacilitiesareexemptfromtherequirementsofthisstandard.(Seeappendix A)

1.3Scope

(a)Therequirementsofthisstandardapplytoallnewconstruction,includingadditionsandalterations.

(b)Therequirementsofthisstandardapplytoexistingbuildingstotheextentpracticable.(Seeappendix A)

1.4Administration

(a)TheFireCommissionerofCanadaortheauthorizedrepresentativeoftheFireCommissioner(henceforthreferredtoas FC)isresponsiblefortheadministrationandenforcementofthisstandard.

(b)Thisstandardisnottobeinterpretedaspermittingpracticesspecificallyprohibitedbyprovincial,municipal,orotherfederallegislation.

(c)Wherereferenceismadetoothercodesandstandards,unlessotherwisestipulated,thereferenceshallbetothelatesteditionincludingamendmentstothatcodeorstandard.

1.5Definitions

(a)Certaintermsusedinthisstandardaredefinedtoensureunderstandingoftheirmeaningandintent.

Containeduseareameansasupervisedareacontainingoneormoreroomsinwhichoccupantmovementisrestrictedtoasingleroombysecuritymeasuresnotunderthecontroloftheoccupant,(seeappendix A);(zonededétentioncellulaire);

freeaccessmeansaccesswithoutbarriersthatrequirekeys,specialdevices,remotereleasingdevices,orspecializedknowledgeoftheopeningmechanism,toanapprovedsafearea,(seeappendixA),(accèslibre);

impededegresszonemeansasupervisedareainwhichoccupantshavefreemovementbutrequiretherelease,bysecuritypersonnel,ofsecuritydoorsattheboundarybeforetheyareabletoleavethearea,butdoesnotincludeacontainedusearea,(seeappendixA),(zoneàsortiecontrôlée);

listedmeansequipmentormaterialsincludedinalistpublishedbyanationallyrecognizedorganizationconcernedwithproductevaluation,thatmaintainsperiodicinspectionofproductionoflistedequipmentormaterialsandwhoselistingstateseitherthattheequipmentormaterialmeetsappropriatestandardsorhasbeentestedandfoundsuitableforuseinaspecifiedmanner,(répertorié);

livingunitmeansabuildingorportionthereofcontainingsleepingaccommodationforinmates,andmayincludeancillaryareassuchaslounges,kitchenettes,showers,andjanitor'sclosets.Familyvisitingunitsarenotconsideredtobelivingunits,(unitérésidentielle).

(b)Unlessotherwisestated,thedefinitionsofwordsandphrasesgivenintheNBCandNFCalsoapplytothisstandard.

1.6Abbreviations

(a)TheabbreviationsofpropernamesinthisstandardshallhavethemeaningsassignedtotheminthisClause.

CAN

NationalStandardofCanada

CER

CommunicationEquipmentRoom

CGSB

CanadianGeneralStandardsBoard

CSA

CanadianStandardsAssociation

CSC

TheCorrectionalServiceofCanada

CF

FireCommissionerofCanadaortheauthorizedrepresentativeoftheFireCommissioner

MCCP

MainCommunicationandControlPost

NBC

NationalBuildingCodeofCanada

NFC

NationalFireCodeofCanada

NFPA

NationalFireProtectionAssociation

TB

TreasuryBoard

ULC

Underwriters'LaboratoriesofCanada

(b)ThesymbolsandotherabbreviationsinthisstandardshallhavethemeaningsassignedtotheminthisClause.

C

degree(s)celsius

h

hour(s)

kg

kilogram(s)

kPa

kilopascal(s)

L

litre(s)

m

metre(s)

mm

millimetre(s)

No.

number(s)

o.c.

oncentre

s

second(s)

2.Generalrequirements

2.1Codesandstandards

Exceptasotherwiseprovidedinthisstandard,fireprotectioninallcorrectionalinstitutionsshallconformtotheapplicablerequirementsof:

(i)theNationalBuildingCodeofCanada(NBC);

(ii)theNationalFireCodeofCanada(NFC);

(iii)TreasuryBoardfireprotectionstandards;and

(iv)FCstandards.

2.2Reviewprocedures

Plansandspecificationsforallnewconstruction,includingadditionsandalterations,shallbesubmittedtotheFCforreviewinaccordancewiththeTreasuryBoardFireProtectionStandardforDesignandConstruction(chapter 32).

3.Construction

3.1Buildingswithoutfreeaccess

(a)BuildingsthatdonothavefreeaccessshallconformtotherequirementsoftheNBCforbuildingsofGroup BDivision 1occupancy.

(b)Buildingsthatdonothavefreeaccessshallbeofnoncombustibleconstruction.

3.2Buildingswithfreeaccess

(a)BuildingsthathavefreeaccessshallconformtotherequirementsoftheNBCforthemajoroccupanciesappropriatetotheiruse.(Seeappendix A)

(b)Abuildingthathasfreeaccessshallbeofnoncombustibleconstructionifthebuildingareaexceedsthelimitspermittedinappendix C.(Seealsoappendix A)

3.3Meansofegress

(a)MeansofegressshallconformtotherequirementsoftheNBC.

(b)Adoorinameansofegress,whichisrequiredtobelockedforreasonsofsecurity,shallbesuchastobeopenablebyakeyfrombothsidesofthedoor.(Seeappendix A)

(c)IfintheopinionoftheFCinconsultationwithCSCforreasonsofsecurityitmaybedifficulttogainaccesstoalockedegressdoorintheeventofanemergency,remotereleasingdevicesshallbeprovidedforsuchdoorsinadditiontothekeyreleaseprescribedin3.3(b).(Seeappendix A)

3.4Separationofmajoroccupancies

MajoroccupanciesshallbeseparatedfromeachotherbyfireseparationsinaccordancewiththerequirementsoftheNBC.

3.5Separationwithinfloorareas(seeappendix A)

(a)Exceptasprovidedinclause 3.5(b),thefollowingareasshallbeseparatedfromtheremainderofthebuildingbyafireseparationhavingafireresistanceratingofatleast2 h:

(i)livingunitsineithercontaineduseareasorimpededegresszones;and,

(ii)anyothercontaineduseareas.

(b)Thefireseparationin(a)maybereducedto1 hinasprinkleredbuildingprovidedtheadjacentareaisnotanindustrialuse.(Seeappendix A)

(c)Thefollowingroomsorareasshallbeseparatedfromtheremainderofthebuildingbyafireseparationhavingafireresistanceratingofatleast1 h:

(i)maintenanceshops;

(ii)storagerooms;

(iii)shippingandreceivingareas;and

(iv)kitchen,cafeteriaanddiningareas.

3.6Interiorfinishmaterials

(a)InteriorfinishmaterialsshallconformtotherequirementsoftheNBCandthissubsection.

(b)Exceptasprovidedin(c),interiorwallandceilingfinishesinacontaineduseareashallhaveaflamespreadratingofnotmorethan25andasmokedevelopedclassificationofnotmorethan50.

(c)Interiorpaddingusedforwallsorceilingsshallbeoffireretardantmaterials,suitableforinstitutionaluse.(Seeappendix A)

(d)Interiorfloorfinishmaterialsshallhaveaflamespreadratingofnotmorethan300andasmokedevelopedclassificationofnotmorethan500.

4.Occupancyhazards

4.1General

Unlessotherwisespecifiedinthisstandard,hazardousmaterials,processesandoperationsshallconformtotherequirementsoftheNFC.(Seeappendix A)

4.2Explosivesandammunition

Thestorage,handlinganduseofexplosivesandammunitionshallbeinaccordancewiththeExplosivesAct,R.S.,c.102,S.1andtheExplosiveRegulationspublishedbytheDepartmentofEnergy,MinesandResources.

4.3Mattresses,pillowsandfurniture(seeappendix A)

(a)Mattressesandpillowsshallbeofafireretardanttype,suitableforinstitutionaluse.(SeeappendixA)

(b)Upholsteredorplasticfurnitureshallnotbeusedinacontaineduseareaunlessthefloorareaissprinklered.

(c)Exceptaspermittedin(d),upholsteredorplasticfurnitureincontaineduseareasorimpededegresszonesshallbeofafireretardanttypesuitableforinstitutionaluse.(Seeappendix A)

(d)Furnitureinanimpededegresszoneisnotrequiredtobefireretardantprovided:

(i)thefloorareaissprinklered;and

(ii)thefloorareaisnotoccupiedbyinmates.

4.4Kitchencookingequipment

(a)Commercialkitchencookingequipmentsuchasarange,broiler,fryingunitorotherequipmentcapableofproducinggreaseladenvapoursshallbeprovidedwithalistedgreaseremovalsystem.

(b)Systemsfortheventilationofcommercialkitchencookingequipmentshallbedesigned,constructedandinstalledtoconformtoNFPAStandardNo. 96,InstallationofEquipmentfortheRemovalofSmokeandGreaseLadenVaporsfromCommercialCookingEquipment.

(c)(Seeappendix A)Anautomaticfiresuppressionsystemshallbeprovidedfortheprotectionof:

(i)commercialkitchencookingequipment;and,

(ii)residentialrangesinlivingunits.

5.Fireprotectionsystems

5.1Firealarmsystems

(a)Afirealarmsystemshallbeinstalledineverybuildingexceptaspermittedin(b).

(b)Forabuildinghavingfreeaccessandatotaloccupantloadof10orless,afirealarmsystemisnotrequiredifthebuildingis2storeysinheightandlessthan50 m2inbuildin