INDOORENVIRONMENTALQUALITY

Intent

Requirements

PotentialTechnologies&Strategies

SummaryofReferencedStandard

ApproachandImplementation

Calculation

ExemplaryPerformance

SubmittalDocumentation

EQP1:

MinimumIAQPerformance

Establishminimumindoorairquality(IAQ)performancetoenhanceindoorairqualityinbuildings,thuscontributingtothecomfortandwell-beingoftheoccupants

1)MeettheminimumrequirementsofSection4~7ofASHRAE62.1-2004,VentilationforAcceptableIndoorAirQuality

2)MechanicalventilationsystemsshallbedesignedusingtheVentilationRateProcedureortheapplicablelocalcode,whicheverismorestringent

3)NaturallyventilatedbuildingsshallcomplywithASHRAE62.4-2004,paragraph5.1

1)Designventilationsystems>=theminimumoutdoorairratesofASHRAE62.2-2004

2)Balancetheimpactsofventilationratesonenergyuseandindoorairqualitytooptimizeforenergyefficiencyandoccupanthealth

3)UsetheASHRAE62UsersManualfordetailedguidanceonmeetingthereferencesrequirements

ASHRAEStandard62.1-2004:

VentilationforAcceptableIndoorAirQuality

1)Specifyminimumventilationrates&IAQthatwillbeacceptabletohumanoccupants

2)Tominimizethepotentialforadversehealtheffects

3)Appliestoallindoororenclosedspacesthatpeoplemayoccupy,exceptwhereotherapplicablestandards&requirementsdictatelargeramountsofventilationthanStd.62.1

4)Releaseofmoistureinresidentialkitchens&bathrooms,lockerrooms,andswimmingpoolsisincludedinthescopeofthisstandard

5)Additionalrequirementsforlaboratory,industrial,andotherspacesmaybedictatedbyworkplaceandotherstandards,aswellasbytheprocessoccurringwithinthespace

6)Considerschemical,physical,andbiologicalcontaminantsthatcanaffectairquality

7)ThermalcomfortrequirementsareNOTincludedinstd.62.1

8)Std.62.4istherelevantstandardforthevastmajorityofprojects,certainlow-riseresidentialprojectspursuingcertificationunderLEEDforNCmayuseStd.62.2

1)Buildingmechanical&passiveventilationsystemsseektoensurethatadequatefreshairisavailableforoccupantsinthespace

2)Std.62.1-2004establishesminimumrequirementsfortheventilationairratesinvarioustypesofoccupiedzones&buildingventilationsystems

3)Thestandardtakesbelowitemsintoaccount

a)Thedensityofpeoplewithinanarea

b)Thetypeofactivitythatisexpectedtooccurinthespace

c)Thenatureoftheventilationairdeliverysystem

Strategies

ActiveVentilation:

MechanicallyVentilatedSpaces—VentilationRateProcedure

1)ASHRAEStandard62.1-2004,Section6:

presentsproceduresfordeterminingtheminimumrequiredventilationratesforvariousapplications,usingeithertheVentilationRateProcedureortheIndoorAirQualityProcedure

2)TheVentilationRateProcedureis:

a)Morestraightforwardtoapplyand

b)Muchmorecommoninpracticeand

c)IstheprescribedapproachrequiredbyEQPrerequisite1

c)Breathingzoneoutdoorairflow=

Sum[outdoorairflowraterequiredperperson]xZonepopulation+OutdoorairflowraterequiredperunitareaxZonefloorarea

3)Std.62.1Table6-1“MinimumVentilationRatesinBreathingZone”

a)providesinformationbyoccupancycategorytodetermineboththeamountofoutdoorairneededtoventilatedpeople-relatedsourcecontaminants&area-relatedsourcecontaminants

b)people-relatedsource:

--addressesactualoccupancydensityandactivity

c)area-relatedsource:

--accountsforbackgroundoff-gaddingfrombuildingmaterials,furniture&materialstypicallyfoundinthatparticularoccupancy

d)therequiredzoneoutdoorairflow:

--isthebreathingzoneoutdoorairflowadjustedtoreflectthe“zoneairdistributioneffectiveness”usingadjustmentfactorsinTable6-2

4)Formultiple-zonesystems,outdoorairintakeflowisadjustedtoreflectthe“systemventilationefficiency”oftheairdistributionconfiguration,usingadjustmentfactorsinTable6-3

5)RequiredapplicantsdemonstratethatthedeliveredminimumzoneoutdoorairflowforeachzoneandtheoutdoorairintakeflowforthesystemmeetsorexceedsthatrequiredbyASHRAE62.1-2004foreachzone

PassiveVentilation--NaturallyVentilatedPaces

1)Section5.1providesrequirementsonthelocation&sizeofventilationopeningsfornaturallyventilationbuildings

2)Requiresthatallnaturallyventilatedspacesshallbepermanentlyopentoandwithin25feetofoperablewallorroofopeningsand

3)Theoperablearea>=4%ofthenetoccupiablefloorarea

4)Allothernon-ventilation-relatedrequirementsinthestandardmustbemettocomplywiththisprerequisite

3)Mixed-modeVentilatedSpaces

1)NeedtomeettheminimumventilationratesrequiredbyChapter6ofStd.62.1regardlessofventilationmode

CALCULATION

N/A

N/A

DSubmittal

1)Designnarrativedescribingtheproject’sventilationdesign.Includespecificinformationregardingfreshairintakevolumesandanyspecialconditionsthataffectedtheproject’sventilationdesign

AND

2)ForMechanicalVentilationBuildings:

a)ConfirmationthattheprojecthasbeendesignedtomeettheminimumrequirementsofASHRAE62.1-2004

b)VentilationforAcceptableIndoorAirQuality,usingtheVentilationRateProcedure.

OR

3)ForNaturalVentilationBuildings:

a)Confirmationthattheprojecthasbeendesignedtocomplywiththerequirementsforlocation&sizeofwindowopeningsperSection5.1

b)Provideapplicableprojectdrawingstoshowthenaturallyventilatedbuildingzones&theoperablewindowareas

EQP2:

EnvironmentalTobaccoSmoke(ETS)Control

Minimizeexposureofbuildingoccupants,indoorsurfaces,andventilationairdistributionsystemstoETS

Option1—NoSmoking

1)Prohibitsmokinginthebuilding

2)Exteriordesignationsmokingareas>=25feetawayfromentries,outdoorairintakesandoperablewindows

Option2—DesignatedInteriorSmokingArea

1)Prohibitsmokinginthebuildingexceptindesignatedsmokingareas

2)Exteriordesignationsmokingareasatleast25feetawayfromentries,outdoorairintakesandoperablewindows

3)Locatedesignationsmokingroomstoeffectivelycontain,capture&removeETSfromthebuilding

a)Mustbedirectlyexhaustedtotheoutdoorswithnore-circulationairtothenon-smokingareaofthebuilding

b)Enclosedwithimpermeabledeck-to-deckpartitions

c)Createanegativepressurewithrespecttotheadjacentspacesofatleastanaverageof5Pa(0.02inchesofwatergauge)andwithaminimumof1Pa

d)Performanceofthesmokingroomshallbeverifiedbyconducting15minutesofmeasurement,withaminimumof1measurementevery10seconds

4)Thetestingwillbeconductedwitheachspaceconfiguredforworstcaseconditionsoftransportofair

Option3(ForResidentialBuildingsOnly)

1)Prohibitsmokinginallcommonareasofthebuilding

2)Exteriordesignationsmokingareasatleast25feetawayfromentries,outdoorairintakesandoperablewindows

3)MinimizeuncontrolledpathwaysforETStransferbetweenindividualresidentialunitsby:

a)Sealingpenetrationsinwalls

b)Ceilingsandfloorsintheresidentialunits

c)Sealingverticalchasesadjacenttotheunits

4)Alldoorsleadingtocommonhallwaysshallbeweather-strippedtominimizeairleakageinthehallway

1)Prohibitsmokingincommercialbuildings

2)Effectivelycontroltheventilationairinsmokingrooms

3)Prohibitsmokinginresidentialbuilding’scommonarea,designbuildingenvelope&systemtominimizeETStransferamongdwellingunits

ANSI/ASTM-E779-03,StandardTestMethodforDeterminingAirLeakageRateByFanPressurization

1)Coversastandardizedtechniqueformeasuringair-leakageratesthroughabuildingenvelopeundercontrolledpressurization&de-pressurization

2)Intendstoproduceameasureofairtightnessofabuildingenvelope

ResidentialManualforCompliancewithCalifornia’s2001EnergyEfficiencyStandards(ForLowRiseResidentialBuildings),Chapter4

1)RequirequalitydesignandconstructionofHVACsystem&airdistributionsystems

2)Offercompliancecreditfortheconstructionoflessleakybuildingenvelopes

3)Requireinstallerdiagnostictesting&certification,andindependentdiagnostictestingandfieldverificationbyacertifiedHomeEnergyRater

1)Prohibitsmokinginthebuilding

2)Providedesignatedsmokingareas

a)OutsideofthebuildinginlocationswhereETSwillnotenterthebuildingorventilationsystem

b)Belocatedawayfromconcentrationsofbuildingoccupantsorpedestriantraffic

1)Interiorsmokingareas

a)Separateventilationsystemmustbeinstalled

b)Effectivenessmustbetestedtoensurethattheyareisolatedfromthenon-smokingportionsofthebuilding

N/A

N/A

DSubmittal

1)Confirmationthattheprojecthasmettherequirementsfortheappropriateprojectcategory

2)Forbuildingswithinteriorsmokingroomsorforresidentialprojects:

Provideappropriatecopiesofconstructiondrawingstodocumentthelocationofthesmokingrooms,designedareaseparations,anddedicatedventilationsystems

3)Provideoptionalnarrativetofurtherdescribethetestingprotocols/results&compliancemethodsimplementedbyproject

EQC1:

OutdoorAirDeliveryMonitoring

Providecapacityforventilationsystemmonitoringtohelpsustainoccupantcomfortandwell-being

1)Installpermanentmonitoringsystemthatprovidefeedbackonventilationsystemperformance

2)Configureallmonitoringequipmenttogeneratedanalarmwhentheconditionsvaryby10%ormoreforsetpoint,via

a)Buildingautomationsystemalarmtothebuildingoperator

b)Visualoraudiblealerttothebuildingoccupants

ForMechanicallyVentilatedSpaces

1)MonitorCO2concentrationswithinalldenselyoccupiedspaces

a)Withadesignoccupantde