PcVue中IEC60870操作说明

OverviewofIEC60870-5-104andtheSupervisor

IEC60870-5-104isacommunicationstandardfortelecontrolparticularlyforthepowergenerationanddistributionmarket.ItisamasterslaveprotocoloperatingoverTCP/IP.InthecaseoftheSupervisor,itisthemasterandthefielddevicesaretheslaves.Bothpollingandunsoliciteddataexchangearesupported.Ingeneral,pollingisonlyusedatstartuptocollecttheinitialstateofslaves.Afterthatdataiscollectedfromaslavewhenitchanges.

∙AnIEC60870-5-104networkhasDevices,SectorsandInformationObjects.

∙ADevicecaneitherbeadataconcentrator,collectingtogetherseveraldiscreteSectors,oritcanhaveintegratedSectors.OftenaDevicewillonlyhaveoneSectormakingtheDeviceandSectorsynonymous.EachDeviceisidentifiedonthenetworkbyitsTCP/IPaddress.

∙ASectoristypicallyapieceofcontrolequipmentwithoneormoreInformationObjects-forexampleacircuitbreaker.

∙InformationObjectsrepresentthephysicalinputsandoutputs.ThetypesofInformationObjectthatareavailableisstrictlycontrolledbytheIEC60870-5-104specification.EachtypehasacorrespondingASDU(ApplicationServiceDataUnit)whichdefinesthestructure,typeandformatofmessages.

 

IEC60870-5-104withintheSupervisor

IEC60870-5-104supportwithintheSupervisorisprovidedbytheTriangleMicroWorkscommunicationstackwhichisintegratedintotheSupervisor'sCommunicationManager. TheSupervisor'sIEC60870-5-104configurationisaccessedfromtheApplicationExplorer-.Communication.Dataacquisition.IEC60870-5-104.

 

 

 

ManagingIEC60870-5-104intheApplicationExplorer

TasksapplicabletoIEC60870-5-104

WhentheIEC60870-5-104folderisselected.

Icon

Task

Description

Settings

DisplaythegeneralIEC60870-5-104settingsdialog.

Newnetwork

ConfigureaconnectiontoanIEC60870-5-104network.

WhenanIEC60870-5-104networkisselected.

Icon

Task

Description

Newdevice

Addadevicetothenetwork.

Startnetwork

Starttheconnectiontothenetwork.

Stopnetwork

Stoptheconnectiontothenetwork.

Remove

Permanentlyremovetheconfigurationoftheconnectiontothenetwork.

Mapping

OpenthemappingdialogusedtolinktheSupervisor'svariablestoIEC60870-5-104informationobjects.

Properties

Openthepropertiesdialogforthenetworkconnection.

WhenanIEC60870-5-104deviceisselected.

Icon

Task

Description

Newsector

Addasectortotheselecteddevice.

Startdevice

Starttheconnectiontotheselecteddevice.

Stopdevice

Stoptheconnectiontotheselecteddevice.

Remove

Permanentlyremovetheconfigurationoftheselecteddevice.

Properties

Openthepropertiesdialogfortheselecteddevice.

WhenanIEC60870-5-104sectorisselected.

Icon

Task

Description

Startsector

Starttheconnectiontothesector.

Stopsector

Stoptheconnectiontothesector.

Testcommand

Sendatestcommandtotheselectedsector.

Clocksynchrocommand

SendaClockSynchronizecommandtotheselectedsector.

Resetcommand

SendaResetcommandtotheselectedsector.

Remove

Permanentlyremovetheselectedsector.

Properties

Openthepropertiesdialogforthesector.

 

 

IEC60870-5-104NetworkSettings

AIEC60870-5-104networksettingsareaccessedfromtheApplicationExplorerbyselecting.Communication.Dataacquisition.IEC60870-5-104andchoosingtheSettingscommandfromthetasklist.Showpicture

∙Monitoringparameters

∙Doublepointinformation

∙Delayofintermediatestate-Thedelayinsecondsoftheintermediatestate(0,0or1,1)beforetheobjectisconsideredtobeinerror.

∙Controlparameters

∙Singlecommand

∙Defaultqualifier-ThedefaultqualifiersentwithaSinglecommand.

∙Defaultmethod-Thedefaultmethod,eitherDirectExecuteorSelectBeforeExecute,usedforeachcommandtype.

∙Timetagged-Ofthevaluefromadevicehasatimestampitwillbeused.OtherwisetheSupervisorwillusethelocal(PC)time.

∙Qualitydescriptormanagement-SelectswhichofthequalityflagsfromthenetworkareconsideredasinvalidqualityintheSupervisor.Bydefaultonlysubstituted(SB)isnotselected.

 

ConfiguringanIEC60870-5-104Network

AIEC60870-5-104NetworkobjectintheSupervisor'sconfiguration,representsandprovidesaccesstothephysicalconnectiontoanIEC60870-5-104network.TheconfigurationisaccessedfromtheApplicationExplorer-.Communication.Dataacquisition.IEC60870-5-104.

Addinganetwork

1.SelecttheIEC60870-5-104folderintheApplicationExplorerand,fromthetasklist,selectNewNetwork.TheIEC60870-5-104Networkdialogopens.Showpicture

2.IntheNametextbox,enterthenameofthenetwork.ThisisthenamebywhichthenetworkwillbeknownintheSupervisor.Youcanacceptthesuggesteddefaultorenteroneofyourown.

3.Enteradescriptionofthenetwork.ThedescriptionappearsinthecontentspaneoftheApplicationExplorerandcanbeusefultoidentifythenetworkatalaterdate.Thedescriptionisoptional.

4.Ifyouareconfiguringamulti-stationapplicationselecttheListofproducers.Thenetworkwillonlybeactivatedandvaluesgeneratedforvariableonthosestationsnamedinthatlist.

5.ToactivatethenetworkconnectionwhenthePCisstarted,tickActivateatstart-up.

6.ClickonOKtoconfirmtheconfigurationandclosethedialog.

TheTracestab 

TheTracestabisusedtoenabledebuggingtracesintheeventofanyproblemswiththenetwork.Onlyusethisifadvisedtodosobyyoursupportagency.

 

AddingDevicestoaIEC60870-5-104Network

AIEC60870-5-104deviceobjectintheSupervisor'sconfigurationrepresents,andprovidesaccessto,aIEC60870-5-104device.Inpracticeadevicemaybejustadataconcentratorcollectingtogetherseveraldiscretesectors,oritmayhavelocalsectorsofitsown.

AnIEC60870-5-104deviceisidentifiedbyitsIPAddress.IntheSupervisoritisknownbytheNamethatyougiveitduringtheconfiguration.

AddingaDevice

1.SelectanIEC60870-5-104networkintheApplicationExplorer.Fromthetaskpane,selectNewDevicetoopentheDevicedialog.Showpicture

2.IntheNamebox,enteranamefortheIEC60870-5-104device.ThisisthenamebywhichitwillbeknownintheSupervisor.

3.EntertheoptionaldescriptivetextintheDescriptionbox.ThedescriptionisonlyusedintheApplicationExplorer.

4.IntheIPAddressbox,enterthedevice'suniqueIPaddress.

5.ClickonOKtoconfirmtheconfigurationandclosethedialog.

TheAdvancedtab

TheAdvancedtabcontainsthemanydeviceparameters.Theparametersarepre-settorecommendeddefaultsandinmostcaseswillnotneedtobechanged.Formoreinformationaboutanychangesrequiredfromthedefault,seethedocumentationprovidedbythedevicemanufacturerortheIEC60870-5-104specification.Showpicture

Thefollowingpropertiesarethosemostlikelytobechanged.

∙TCP/IPparameters

∙TCPport-TheTCPportusedbytheSupervisortocommunicatewiththeDevice.Onlychangeifthedefaultportof2404isalreadyinuseonthehostPC.

TheTracestab

TheTracestabisusedtoenabledebuggingtracesintheeventofanyproblemswiththedevice.Onlyusethisifadvisedtodosobyyoursupportagency.

 

 

 

 

 

AddingSectorstoaIEC60870-5-104Device

AsectorobjectintheSupervisor'sconfigurationrepresents,andprovidesaccessto,aphysicalIEC60870-5-104sector.Asectornormallyrepresentsapieceofdiscretecontrolequipment(forexampleacircuitbreaker)andisconnectedtothenetworkviaadevice.Sometimesasectorcanbephysicallypartofadevice.

OnaIEC60870-5-104networkasectorisidentifiedbyitsCommonaddress.IntheSupervisoritisknownbytheNamethatyougiveitduringtheconfiguration.

AddingaSector

1.SelectanIEC60870-5-104deviceintheApplicationExplorer.Fromthetaskpane,selectNewSectortoopentheSectordialog.Showpicture

2.IntheNamebox,enteranamefortheIEC60870-5-104Sector.ThisisthenamebywhichitwillbeknownintheSupervisor.

3.EntertheoptionaldescriptivetextintheDescriptionbox.ThedescriptionisonlyusedintheApplicationExplorer.

4.IntheCommonaddressofADSUbox,entertheSector'saddress.ThisistheidentityoftheSectorwithintheDevicethroughwhichitisconnected.

5.TickActivateatstart-upifthesectoristobeactivatedwhenthedeviceisstarted.

6.ClickonOKtoconfirmtheconfigurationandclosethedialog.

TheAdvancedtab

TheAdvancedtabcontainsthemanysectorparameters.Theparametersarepre-settorecommendeddefaultsandinmostcaseswillnotneedtobechanged.Formoreinformationaboutanychangesrequiredfromthedefault,seethedocumentationprovidedbythesectormanufacturerortheIEC60870-5-104specification.Showpicture

Thefollowingpropertiesarethosethataremostcommonlychanged.

∙Communicationproperties

∙Addressformat-Theformatinwhichthesector'sinformationobjectsareaddressed.SeethetopicIEC60870-5-104variablemapping.

∙Cyclicrequests

∙Interrogationofgroups-Allowstheconfigurationofupto16groups.Whenenabled,agroupispolledbythemasteratthepollingperiod.Informationobjectscanbeassociatedwithagroup(intheequipmentconfigurationitself-notintheSupervisor)anddataforthoseobjectswillbereturnedeachtimethegroupispolled.

TheTracestab

TheTracestabisusedtoenabledebuggingtracesintheeventofanyproblemswiththeSector.Onlyusethisifadvisedtodosobyyoursupportagency.

 

 

 

 

 

IEC60870-5-104InformationObjecttoVariableMappin