NFPA16Foam
NFPA16
StandardfortheInstallationofFoam-WaterSprinklerandFoam-WaterSpraySystems
1999Edition
Copyright©1999NFPA,AllRightsReserved
ThiseditionofNFPA16,StandardfortheInstallationofFoam-WaterSprinklerandFoam-WaterSpraySystems,waspreparedbytheTechnicalCommitteeonFoam-WaterSprinklers,releasedbytheTechnicalCorrelatingCommitteeonAutomaticSprinklerSystems,andactedonbytheNationalFireProtectionAssociation,Inc.,atitsFallMeetingheldNovember16-18,1998,inAtlanta,GA.ItwasissuedbytheStandardsCouncilonJanuary15,1999,withaneffectivedateofFebruary4,1999,andsupersedesallpreviouseditions.
ThiseditionofNFPA16wasapprovedasanAmericanNationalStandardonFebruary4,1999.
OriginandDevelopmentofNFPA16
Thefirststandardinvolvingfoam-watersprinklersystemswaspublishedin1954bytheNationalBoardofFireUnderwriters(nowAmericanInsuranceAssociation)andwastitledStandardforCombinedFoam-andWater-SpraySystems.TheNFPATechnicalCommitteeonfoam-watersprinklerswasestablishedin1959withassistancefromtheNBFU.Thefirsteditionofthisstandardwaspublishedin1962.
Variousupdatestothestandardwerecompletedin1968,1974,1988,and1990.Changesweremadetorecognizetheuseofnewfoamconcentratesandtoimprovethelanguageandformatofthedocument.
The1995editionincludedclarificationofthescopeofthestandard,improvementstothehydraulicdesigncriteria,andrecognitionofafourthproportioningmethod.
The1999editioncombinestheprevioustextofNFPA16andNFPA16Aintoonecomprehensivedocument.Numerouseditorialchangeshavealsobeeninstituted.
TechnicalCorrelatingCommitteeonAutomaticSprinklerSystems
JohnG.O’Neill,Chair
Gage-Babcock&Assoc.Inc.,VA[SE]
MiloshT.Puchovsky,Secretary
Nat’lFireProtectionAssn.,MA
(Nonvoting)
JoseR.Baz,Int’lEngineeredSystems,LTD,Inc.,FL[M]
Rep.NFPALatinAmericanSection
KerryM.Bell,UnderwritersLaboratoriesInc.,IL[RT]
EricCote,RolfJensen&Assoc.,Inc.,MA[SE]
RussellP.Fleming,Nat’lFireSprinklerAssn.,NY[M]
JosephB.Hankins,Jr.,FactoryMutualResearchCorp.,MA[I]
RolandJ.Huggins,AmericanFireSprinklerAssn.,Inc.,TX[IM]
AndrewKim,Nat’lResearchCouncilofCanada,ON,Canada[RT]
GeraldR.Kirby,MarriottInt’l,Inc.,DC[U]
Rep.AmericanHotel&MotelAssn.
B.J.Lukes,GrinnellFireProtectionSystemCo.Ltd/Tyco,Canada[M]
Rep.CanadianAutomaticSprinklerAssn.
JosephW.Noble,ClarkCountyFireDept.,NV[E]
DonaldR.Oliver,WilsonFire/RescueServices,NC[E]
Rep.Int’lAssn.ofFireChiefs
JamesRetzloff,TheVikingCorp.,MI[M]
ChesterW.Schirmer,SchirmerEngrCorp.,NC[SE]
JohnNigelStephens,LossPreventionCouncil,England[I]
LynnK.Underwood,WausauHPREngr,WI[I]
JohnJ.Walsh,UAJointApprenticeshipCommitteeLocal669,MD[L]
Rep.UnitedAssn.ofJourneymen/ApprenticesofPlumbing/PipeFitting
Alternates
Donald“Don”D.Becker,MidlandAutomaticSprinklerCo.,Inc.,MO[IM]
(Alt.toR.J.Huggins)
RaymondA.Grill,RolfJensen&Assoc.,Inc.,VA[SE]
(Alt.toE.Cote)
KennethE.Isman,Nat’lFireSprinklerAssn.,NY[M]
(Alt.toR.P.Fleming)
GeorgeE.Laverick,UnderwritersLaboratoriesInc.,IL[RT]
(Alt.toK.M.Bell)
DonatoA.PirroE.,ElectroSistemasDePanama,S.A.,Panama[M]
(Alt.toJ.R.Baz)
WilliamE.Wilcox,FactoryMutualResearchCorp.,MA[I]
(Alt.toJ.B.Hankins,Jr.)
Nonvoting
EdwardK.Budnick,HughesAssoc.,Inc.,MD[SE]
(Chair,TConSprinklerSystemDischargeCriteria)
RolfH.Jensen,Largo,FL[SE]
(MemberEmeritus)
WilliamE.Koffel,Jr.,KoffelAssoc.Inc.,MD[SE]
(LiaisonfromSafetytoLifeProject)
KennethW.Linder,HSBIndustrialRiskInsurers,CT[I]
(Chair,TConSprinklerSystemInstallationCriteria)
ChristopherT.Lummus,InsuranceServicesOffice,Inc.,TX[I]
(LiaisonfromStorageProject)
DanielMadrzykowski,U.S.Nat’lInst.ofStandards&Technology,MD[RT]
(Chair,TConResidentialSprinklerSystems)
PeterPapavasiliou,EngrProfessionals,LTD,IL[SE]
(Chair,TConFoam-WaterSprinklers)
J.WilliamSheppard,GeneralMotorsCorp.,MI[M]
(Chair,TConBracingofWater-BasedFireProtectionSystems)
MiloshT.Puchovsky,NFPAStaffLiaison
ThislistrepresentsthemembershipatthetimetheCommitteewasballotedonthetextofthisedition.Sincethattime,changesinthemembershipmayhaveoccurred.Akeytoclassificationsisfoundatthebackofthisdocument.
NOTE:
MembershiponacommitteeshallnotinandofitselfconstituteanendorsementoftheAssociationoranydocumentdevelopedbythecommitteeonwhichthememberserves.
CommitteeScope:
Pending
TechnicalCommitteeonFoam-WaterSprinklers
PeterPapavasiliou,Chair
EngrProfessionals,LTD,
IL[SE]
V.FrankBateman,WilliamsFire&HazardControl,CA[M]
TraceyD.Bellamy,Tomes,VanRickleyandAssoc.,GA[SE]
WilliamM.Carey,UnderwritersLaboratoriesInc.,IL[RT]
SalvatoreA.Chines,HSBIndustrialRiskInsurers,CT[I]
RonaldC.Correia,Nat’lFoam,Inc.,PA[M]
HerbertN.Davidson,LibertyMutualGroup,MA[I]
Rep.TheAllianceofAmericanInsurers
JohnAugustDenhardt,StricklandFireProtection,Inc.,MD[IM]
Rep.AmericanFireSprinklerAssn.,Inc.
DavidDixon,SecurityFireProtection,TN[IM]
Rep.Nat’lFireSprinklerAssn.
RobertM.Gagnon,GagnonEngr,MD[SE]
RichardR.Harrington,UnitedAirlines(SFOSY),CA[U]
AlanL.Holder,LouisianaPower&LightCo.,LA[U]
Rep.EdisonElectricInst.
KirkW.Humbrecht,PhoenixFireSystems,Inc.,IL[IM]
Rep.FireSuppressionSystemsAssn.
EldonD.Jackson,VikingCorp.,MI[M]
Rep.Nat’lFireSprinklerAssn.
DennisC.Kennedy,RolfJensen&Assoc.,Inc.,IL[SE]
DanR.Loris,KemperNat’lInsuranceCos.,IL[I]
ScottL.Maxwell,Fireman’sFundInsuranceCo.,CO[I]
RobertC.Merritt,FactoryMutualResearchCorp.,MA[I]
RichardF.Murphy,Cranford,NJ[SE]
MauriceM.Pilette,MechanicalDesignsLtd,MA[SE]
TommyPreuett,RoadSprinklerFittersLocal669,DC[L]
Rep.UnitedAssn.ofJourneymen/ApprenticesofPlumbing/PipeFitting
PaulE.Rivers,3M,MN[M]
JosephL.Scheffey,HughesAssoc.,Inc.,MD[SE]
TerryL.Victor,TycoInt’l,Ltd,MD[M]
AndrewM.Wahl,Gage-Babcock&Assoc.,VA[SE]
FredK.Walker,U.S.AirForce,FL[U]
LaurenceD.Watrous,HSBProfessionalLossControlInc.,TN[I]
CherilynA.Zeisset,PennzoilCo.,TX[U]
Rep.AmericanPetroleumInst.
Alternates
PaulF.Crowley,FactoryMutualResearchCorp.,MA[I]
(Alt.toR.C.Merritt)
DennisL.Doherty,HSBIndustrialRiskInsurers,CT[I]
(Alt.toS.A.Chines)
BrianR.Foster,HSBProfessionalLossControlInc.,FL[I]
(Alt.toL.D.Watrous)
JohnA.Frank,KemperNat’lInsuranceCos.,GA[I]
(Alt.toD.R.Loris)
ChristopherP.Hanauska,HughesAssoc.,Inc.,MN[SE]
(Alt.toJ.L.Scheffey)
MichaelJ.Madden,Gage-Babcock&Assoc.,CA[SE]
(Alt.toA.M.Wahl)
KeithOlson,TycoInt’l,Ltd,WI[M]
(Alt.toT.L.Victor)
RichardE.Ottman,3M,MN[M]
(Alt.toP.E.Rivers)
LeeRindfuss,J&HMarsh&McLennan,MA[I]
(VotingAlt.toJ&HM&MRep.)
ThomasM.Suehr,WausauHPREngr,WI[I]
(Alt.toH.N.Davidson)
KennethW.Zastrow,UnderwritersLaboratoriesInc.,IL[RT]
(Alt.toW.M.Carey)
MiloshT.Puchovsky,NFPAStaffLiaison
ThislistrepresentsthemembershipatthetimetheCommitteewasballotedonthetextofthisedition.Sincethattime,changesinthemembershipmayhaveoccurred.Akeytoclassificationsisfoundatthebackofthisdocument.
NOTE:
MembershiponacommitteeshallnotinandofitselfconstituteanendorsementoftheAssociationoranydocumentdevelopedbythecommitteeonwhichthememberserves.
CommitteeScope:
ThisCommitteeshallhaveprimaryresponsibilityfordocumentsontheprotectionofhazardsbysystemsdesignedtofunctionasbothsprayedfoamandwaterdischarge,asfromasprinklersystem.
NFPA16
StandardfortheInstallationofFoam-WaterSprinklerandFoam-WaterSpraySystems
1999Edition
NOTICE:
Anasterisk(*)followingthenumberorletterdesignatingaparagraphindicatesthatexplanatorymaterialontheparagraphcanbefoundinAppendixA.
InformationonreferencedpublicationscanbefoundinChapter7andAppendixB.
Chapter1GeneralInformation
1-1Scope.
1-1.1
Thisstandardcontainsminimumrequirementsforthedesign,installation,andmaintenanceoffoam-watersprinklerandspraysystems.Thesesystemsshallbedesignedwiththerequireddensityforeitherfoamorwaterapplicationasthecontrollingfactor,dependingonthedesignpurposeofthesystem.Itisnottheintentofthisstandardtospecifywherefoam-watersprinklerandsprayprotectionisrequired.Thedeterminationofwherefoam-watersprinklersandspraysystemsarerequiredshallbemadeinaccordancewithsuchapplicablestandardsasNFPA30,FlammableandCombustibleLiquidsCode,andNFPA409,StandardonAircraftHangars.
1-1.2*
Thisstandardshallapplyonlytosystemsusinglow-expansionfoam.
1-2*Purpose.
1-2.1
Thepurposeofthisstandardistoprovideareasonabledegreeofprotectionforlifeandpropertyfromfirethroughinstallationrequirementsforfoam-watersprinklerandspraysystemsbasedonsoundengineeringprinciples,testdata,andfieldexperience.
Nothinginthisstandardisintendedtorestrictnewtechnologiesoralternatearrangements,providedthelevelofsafetyprescribedbythestandardisnotlowered.
1-2.2
Unlessotherwisenoted,theprovisionsofthisdocumentarenotintendedtobeappliedtofacilities,equipment,structures,orinstallationsthatwereexistingorapprovedforconstructionorinstallationpriortotheeffectivedateofthedocument,exceptinthos