《孟加拉国 50MVA 132kV 电力变压器英文招标书Word格式文档下载.docx》由会员分享,可在线阅读,更多相关《孟加拉国 50MVA 132kV 电力变压器英文招标书Word格式文档下载.docx(11页珍藏版)》请在冰豆网上搜索。
GhorashalPowerStation.
a.132/33/11KV,ONANrating25/25/18MVA,ONAFrating50/50/35MVA,outdoormounting,3phase.50Hz,uniforminsulation.1324x2%KV(HVtapson-loadoperating9Nos.oftaps),mineraloilimmersedequippedwithBCT.Thesupplyoftransformerwillalsoincludesuitablesize(sizewillbeconfirmedduringdetailEngineering)ofMSrailforplacingoftransformeronfoundation.DuringsubmissionofthebidthetechnicaldatarequirementofBPDBshallbefullycompliedbythebidder.IncaseofanydeviationobservedinbidderstechnicaldatafromUser’stechnicaldata,thebidder’sbidwillbedeclarednon-responsive.Thebidderwillprovide1(one)engineerforexpertserviceduringinstallation,testingandcommissioningofthetransformerfor15days.ThefollowingspecificationarepreparedbasedontheexistingonewithaviewtoprocureanidenticalonebecausebothwillruninParallel.SuccessfulBiddermayvisitGhorasalpowerstationfortakingnecessarydataformexistingoneexternallybymeasurementfordetailengineering.
b.TheinsulationvalueofHV/MV/LVsidesare:
(i)Highestsystemvoltage:
145/36/12kV
(ii)BasicinsulationLevel(BIL):
650/170/75kV
(iii)Powerfrequencywithstand
Voltage(1min):
275/70/28kV.
TheInsulationlevelofHV&
MVNeutralBushingshallbesameasPhaseBushings.
c.TheHVbushingandbushingfortheneutralshallbecapacitortype,porcelainbeingbrownglazed.TheBCTfittedintheneckofeachbushingshallhave2core&
4tappingofeachcore.Theratio,accuracyclassandburdenofBCTareasfollows:
HVBCT:
(i)1stcore:
Nooftapping:
4
1sttap:
400/1A,3P20,20VA.
2ndtap:
600/1A,3P30,30VA.
3rdtap:
750/1A,3P30,75VA.
4thtap:
1000/1A,1P30,30VA.
(ii)2ndcore:
4
400/1A,class0.2,20VA.
2ndtap:
600/1A,class0.2,30VA.
750/1A,class0.2,75VA.
1000/1A,class0.2,30VA.
BushingfortheneutralofHVside:
(1)1stcore:
200/5A,10P15,15VA.
300/5A,3P10,10VA.
400/5A,3P20,20VA.
600/5A,3P30,30VA.
(ii)2ndcore:
Sameas1stcore:
d.TheMVbushingandbushingfortheneutralmaybeofcapacitortypeorporcelaintypewithoutsideglazedofbrownporcelain.TheBCTfittedintheneckofeachbushingshallhave2core&
MVBCT:
600/5A,3P30,30VA.
750/5A,3P30,75VA.
1000/5A,1P30,30VA.
Sameas1stcore.
(I)1stcore:
1sttap:
e.TheLVbushingmaybeofcapacitortypeorporcelaintypewithoutsideglazedofbrownporcelain.NoCTrequiredforthebushing.
f.Valuesofresistancereactanceofthetransformershallnotbedeviatedbymorethan2%(twopercent)oftheBPDB’Srequirementsandthecore&
copperlossoftransformershallnotexceed5%(fivepercent)ofBPDB’Srequirements.Theabove-mentionedvaluesarethetolerancevaluestobemaintainedduringfactorytestingifexceedsthetransformerwillberejected.
Theimpedancevoltage,corelossandcopperlossofthetransformershallbe:
ImpedancevoltageatHV-132-kV,MV33,kvat50MVAandat750C:
BetweenHVandMVwinding=11.568%
BetweenHVandLVwinding=19.443%
BetweenMVandLVwinding=6.051%
Corelossatnominalvoltage,normalratioandatratedfrequency=37.914kW.
Totalexcitationcurrent=0.251%
Fullloadcopperlossatnominalvoltage(HV=132kV,MV=33kV)normalratioatratedfrequencyandat750C:
50MVAHVandMVwinding=271.712KW
35MVAHVandLVwinding=170.854KW
35MVAMVandLVwinding=130.092KW
g.Thewindingshallbecapableofwithstanding:
14.3timesbasecurrentfor5seconds.
16.6timesbasecurrentfor4seconds.
20.0timesbasecurrentfor3seconds.
25.0timesbasecurrentfor2seconds.
Thewindingshallbeofelectrolyticcopper,freefrombursandsplinter.Papershallbeusedforconductorinsulation.
h.TheinsulatingoilshallmeetallrequirementsasdefinedbyNEMAstandard/B.S.shallbechemicallystable,freefromacidityandothercorrosiveingredientsandshallposseshighdielectricstrength.Oilforfirstfillingshallbeshippedinnon-returnabledrums.10%ofthequantityrequiredforatransformeristobesuppliedinadditionduetousuallossesduringinstallationcentrifugingetc.
i.Thetransformertankshallbeofweldedconstructionfabricatedfromhightensilesteelplateandshallbedesignedtowithstandfullvacuum.
j.Thetransformershallhaveairsealcelltypeoilconservatortank(theoilsurfaceiscompletelyisolatedfromtheatmospherebyinstallinganoilresistantrubbercellintheinterioroftheconservator)atthetop.Transformerwillbeprovidedwith2separateconservators(1formaintankandanotherforOnloadTapChanger),whichwillbehavingprovisionformountingseparateMOLG.OneparttobeconnectedwithtransformermaintankthroughBuchholtzRelay(withcocksonbothside)andtheotherpartwithOLTCtankthroughanothergasRelay(withcockeitherside).Bothwillhaveoillevelindicate(visual)withcontactsformedicating“LOWOILLEVEL”inthecontrolpanel.
k.PressureReleaseDevicesforbothMainTankandOLTCTankshallbeprovided
l.SilicagelBreatherwithglasswindowshallbeprovidedforbothhalvesoftheconservatorlank.
m.TheOn-loadTapChangeroperatingdeviceshallbeequippedwithlocal(manualandelectrical)andremoteelectricaloperatingdevicewithappropriateinterlocking.TheOLTCmotorshallbe3-phase400Voperatingtype.Themechanicalpositionindicationshallbetherebothatthetapchangeraswellasontheoperatingdevice.ContactsArrangementsshallbethereforremotepositionindicator(bydigitaldisplaysystem)ofthetap.Appropriateglandsfortheentryofcontrolcableshallbeprovided.
n.SufficientCoolingFans(3-phase,400V,50HZ)ofadequatecapacityshallbefittedonthebodyofthetransformerforcoolingpurposetoachievetheONAFratingovertheaverageambienttemperatureof400C.ThereshallbeacontroldeviceinweatherproofhousingfittedonthebodyofthetransformerandequippedwithcontrolrelayoperatedbysensingdeviceofoiltemperatureinsidethetransformerandoperaterequisiteNo.offans.Besidethereshallbemanualswitchingdeviceofcoolingfans.
o.TheRadiatorsshallbeinbanks,whichcanbefilledwithorremovedfromthebedsoftransformertank.SufficientradiatorsshallbeprovidedtoachievetheONANratingataverageambienttemperatureof400C.Eachbankofradiatormusthavetwostopvalveoneofwhichshouldbefixedatthetopandtheotheratthebottom.
p.Besidethemaincomponentsofthetransformertheotherfeaturesandaccessoriestobeassociatedwhichareasfollows:
(i)Inspectionholewithcover.
(ii)Manhole.
(iii)Nameplatewithcompletediagramsandmainspeculations.
(iv)Upperandloweroilvalvesoilsamplingvalveanddrainvalve.
(v)Laddertoclimbuptotopwithbarrieratthebottom.
(vi)Thermometerforsendingoilandwindingtemperatureanddisplay:
WTIshallhavetwocontactsamongthemonewillbeusedforalarmcircuitandotherwillbesuitableforintercroppingofHVandMV/LVCircuitBreaker.
(vii)AllHV(132KV)terminalsshallbeprovidedwithappropriateconnectingclampstobeconnectedwith636MCMACSRconductors.TheLV(33KV)terminalsshallhavealsoconnectingclampsappropriateforbeingconnectedwithone636MCMACSRconductor.Theneutralterminalshallhaveconnectingclampstobeconnectedwith2/0HDBSwire.Thesizeofconductorsmaybechangedduringapprovalstage.
(viii)Thereshallbefourwheels(flangetype)suitableformountingonrailsandtocarrythetransformerasawhole.
(ix)Thetransformershallhaveatleasttwogroundingterminalsonitsbody.
AllferrouspartsofthetransformershallbegalvanizedorpaintedwithappropriatepaintsofMUNSELLNO-5Y7/1.Transformerwithmaximumshippingheight(notexceeding11feet)willbepreferred.
q.Onesetofextragasketsandonesetbushingofeachtypeistobesuppliedwiththetransformerlotwithoutextracost.
r.Thelosscapitalizationofpowertransformerwillbedonebythefollowingformulaforevaluation.
C=A+25650XFL.
Where:
C=CapitalizedcostinTaka.
A=QuotedC&
FcostinTake.
FL=TotalconsumptionofcoolingfansinKW.
s.MakeandModelofTapChanger:
ThetransformerwillbefittedwithMR,GermanymakeOnLoadTapChanger(M111500YModel)
t.ColorofFinishPaint:
AlltheexistingtransformersatGhorashalarehavingexternalAluminumfinishPaint,Thesamewillbeprovidedforthenewtransformer.
u.Terminationoftertiary:
Tertiary(11KV)windingwillbebroughtoutsidetotanktopafterclosingdeltawindinginsidethrough3externalbushings.(Bushingswillbesuppliedextra)
v.ControlschemeofTapChanger:
OnLoadTapChangercontrolschemeofnewtransformerwillbesuitableforindividualoperationoftransformerfromControlroom.Master–Follower,Individualoperationfacilitywillbeprovidedinthisunit.
w.Terminalconnector:
Transformerwillbesuppliedwithterminalconnector