RCS978C定值整定与说明文档格式.docx
《RCS978C定值整定与说明文档格式.docx》由会员分享,可在线阅读,更多相关《RCS978C定值整定与说明文档格式.docx(34页珍藏版)》请在冰豆网上搜索。
Network_Printer_Option
9
Comm._Protocol_Option
10
Enable_Remote_Modify_Setting
11
Enable_Monitor_Comm._Blk
12
Disable_Adaptive_InrushThreshold
2System_parameter
Trans._Capa._IntPart
0—2000
315
Trans._Capa._DecPart
0—99
Rated_Frequency
50Hz或60Hz
50
CT_Sec._Rated_Curr.
1A或5A
S1_CT8_Sec_Rated_Curr.
0—10A
CW_ZS_CT10_Sec_RatedCurr
S1_CT8_Pri_Rated_Curr
0—65535A
1000
CW_ZS_CT10_Pri_RatedCurr
1500
VT_Sec._Rated_Volt.
57.7-63.5V
63.5
S1_VT1_Pri._Rated_Volt.
0—6550kV
230.9
S2_VT2_Pri._Rated_Volt.
127
S3_VT3_Pri._Rated_Volt.
19
13
S1Br1_System_Volt.
400
14
S1Br2_System_Volt.
15
S2_System_Volt.
220
16
S3Br1_System_Volt.
33
17
S3Br2_System_Volt.
18
Trans._Connection_Mode
0—4
Enable_Diff._Protection
20
Enable_OverExci_Prot.
21
Enable_Side1_BakProt
22
Enable_Side2_BakProt
23
Enable_Side3Br1_BakProt
24
Enable_Side3Br2_BakProt
25
Enable_ComWind_BakProt
3Differential_protection_setting
S1Br1_CT1_Pri_RatedCurr
2000
S1Br2_CT2_Pri_RatedCurr
Side2_CT3_Pri_RatedCurr
1600
S3Br1_CT4_Pri_RatedCurr
800
S3Br2_CT5_Pri_RatedCurr
CW_CT6_Pri_RatedCurr
ET_ZS_CT7_Pri_RatedCurr
500
Diff._Pickup_Curr.
0.1—1.5Ie
0.4
Diff._Stabilizing_Factor
0.2—0.75
0.5
2nd_Harm._Stab._Factor
0.05—0.35
0.15
3rd_Harm._Stab._Factor
0.2
Inst._Diff._Curr.
2—14Ie
Diff._CT_Superv._Alarm
0.01—1.5Ie
0.25
WD_Pickup_Curr.
0.1—1.5In
WD_Stabilizing_Factor
ET_REF_Pickup_Curr.
ET_REF_Stabiliz_Factor
CT_Superv._Blk_Diff.
CT_Superv._Blk_WD
0-1
CT_Superv._Blk_ET_REF
Inrush_Blk_Diff.
0/1
Diff._Prot._TripMatrix
0000—FFFFH
000F
ET_REF_Prot._TripMatrix
0009
Enable_Inst._Diff._Prot.
Enable_Percent_Diff._Prot.
Enable_Percent_WD_Prot.
Enable_DPFC_Diff._Prot.
Enable_3rd_Harm._Blk_Diff.
Side1_3/2_Breaker_Option
26
Enable_ET_REF_Prot.
4overexcitation_setting
Def.OverExci._Zone1
1.0—1.7
1.3
Def.OverExci._Zone1_Delay
0—6000S
Def.OverExci._Zone2
1.4
Def.OverExci._Zone2_Delay
8.3
Def.OverExci._Alarm
1.25
Def.OverExci._Alarm_Delay
Inv.OverExci.Ratio_UpLimit
1.7
Inv.OverExci_UpLimit_Delay
2.75
Inv.OverExci._Ratio1
1.6
Inv.OverExci._Delay1
3.8
Inv.OverExci._Ratio2
1.5
Inv.OverExci._Delay2
5.7
Inv.OverExci._Ratio3
Inv.OverExci._Delay3
Inv.OverExci._Ratio4
Inv.OverExci._Delay4
Inv.OverExci._Ratio5
Inv.OverExci._Delay5
Inv.OverExci._Ratio6
1.2
Inv.OverExci._Delay6
55
Inv.OverExci._Ratio7
1.17
Inv.OverExci._Delay7
100
Inv.OverExci._Ratio8
1.13
Inv.OverExci._Delay8
350
Inv.OverExci.Ratio_LowLimit
1.1
Inv.OverExci_LowLimit_Delay
1200
27
Inv.OverExci._Alarm
1.08
28
Inv.OverExci._Alarm_Delay
2200
29
Enable_Def.OverExci._Prot.
30
Enable_Def.OverExci._Alarm
31
Enable_Inv.OverExci._Prot.
32
Enable_Inv.OverExci._Alarm
OverExci._Install_Option
5S1_side_backup_protection_setting
Pickup_Curr.
0.05—30In
Pickup_ZS_Curr.
OC_Zone1_Curr.
OC_Zone1_Delay1
0—20S
OC_Zone1_TripMatrix1
OC_Zone1_Delay2
OC_Zone1_TripMatrix2
ROC_Zone1_Curr.
ROC_Zone1_Delay1
ROC_Zone1_TripMatrix1
ROC_Zone1_Delay2
ROC_Zone1_TripMatrix2
ROC_Zone2_Curr.
ROC_Zone2_Delay1
ROC_Zone2_TripMatrix1
ROC_Zone2_Delay2
ROC_Zone2_TripMatrix2
ROC_Zone3_Curr.
ROC_Zone3_Delay1
ROC_Zone3_TripMatrix1
ROC_Zone4_Curr.
ROC_Zone4_Delay1
ROC_Zone4_TripMatrix1
InvTime_OC_Curr.
0.05—20In
InvTime_OC_Delay
0—10S
InvTime_OC_TripMatrix
InvTime_ROC_Curr.
InvTime_ROC_Delay
InvTime_ROC_TripMatrix
OverLoad_Curr.
OverLoad_Delay
CoolerStart_Curr.
CoolerStart_Delay
34
Enable_OverLoad_Alarm
35
Enable_CoolerStart
36
ROC_Zone1_Blk_by_Harm.
37
ROC_Zone2_Blk_by_Harm.
38
ROC_Zone1_Blk_by_Direction
39
ROC_Zone2_Blk_by_Direction
40
ROC_Direction_Option
41
ROC_Zone3_Blk_by_Direction
42
VT_Supervision_Criterion
43
VT_Out_of_Service
44
ROC_Blk_by_CT_Superv_Alarm
45
InvTime_OC_Blk_by_Dir.
46
InvTime_OC_Direction_Opt
47
InvOC_Inherent_Delay_Opt
48
InvTime_ROC_Blk_by_Dir.
49
InvROC_Inherent_Delay_Opt
6S2_side_backup_protection_setting
7S3Br1_side_backup_protection_setting
Pickup_Curr.
Pickup_ZS_Curr.
NS_Volt_for_CompVolt.Blk
2—100V
LowVolt_for_CompVolt.Blk
OC_Zone1_Curr.
OC_Zone1_Delay1
OC_Zone1_TripMatrix1
OC_Zone2_Curr.
OC_Zone2_Delay
OC_Zone2_TripMatrix
ROC_Zone1_Delay
ROC_Zone1_TripMatrix
ROC_Zone2_Curr.
ROC_Zone2_Delay
ROC_Zone2_TripMatrix
ROC_Alarm_Curr.
2—150V
ROC_Alarm_Delay
OC_Zone1_Blk_by_CompVolt
OC_Zone2_Blk_by_CompVolt
Enable_OverLoad_Alarm
Enable_ROC_Alarm
VT_Supervision_Criterion
VT_Out_of_Service
8S3Br2_side_backup_protection_setting
Enable_OverLoad_Alarm
9Comm_side_backup_protection_setting
N