计算书文档格式.docx
《计算书文档格式.docx》由会员分享,可在线阅读,更多相关《计算书文档格式.docx(20页珍藏版)》请在冰豆网上搜索。
1水电厂S–1:
Xjss–1=X29*(SN∑1/Sj)=0.143*(3*200/0.875/100)=0.98
2水电厂H–1:
XjsH–1=X30*(SN∑1/Sj)=0.0598*(4*300/0.85/100)=0.844
查运算曲线:
t=0”时
I*S-1”=1.061
I*H-1”=1.242
IS-1”=(I*S-1”*SNS-1)/(√3*Uj)
=1.061*(3*200/0.875)/(√3*230)=1.826KA
IchS-1=IS-1”*√[1+2*(Kch-1)²
]
=1.826*√[1+2*(1.85-1)²
]=2.855KA
IH-1”=(I*H-1”*SNH-1)/(√3*Uj)
=1.242*(4*300/0.85)/(√3*230)=4.402KA
IchH-1=IH-1”*√[1+2*(Kch-1)²
=4.402*√[1+2*(1.85-1)²
]=6.883KA
I”=IS-1”+IH-1”=1.826+4.402=6.288KA
Ich1=IchS-1+IchH-1=2.855+6.833=9.738KA
t=2”时
I*t=2s-1”=1.225
I*t=2H-1”=1.36
It=2s-1”=(I*t=2s-1”*SNS-1)/(√3*Uj)
=1.225*(3*200/0.875)/(√3*230)=2.109KA
It=2H-1”=(I*t=2H-1”*SNH-1)/(√3*Uj)
=1.36*(4*300/0.85)/(√3*230)=4.8198KA
It=2”=It=2s-1”+It=2H-1”=2.109+4.8198=6.928KA
T=4”时
I*t=4s-1”=1.225
I*t=4H-1”=1.375
It=4s-1”=(I*t=4s-1”*SNS-1)/(√3*Uj)
It=4H-1”=(I*t=4H-1”*SNH-1)/(√3*Uj)
=1.375*(4*300/0.85)/(√3*230)=4.873KA
It=4”=It=4s-1”+It=4H-1”=2.109+4.873=6.982KA
⑵、d2点短路电流的计算:
X31=(X19+X20)/2=0.03035
X32=X29+X31+X29*X31/X30
=0.143+0.03035+0.143*0.03035/0.0598=0.246
X33=X30+X31+X30*X31/X29
=0.0598+0.03035+0.0598*0.03035/0.143=0.103
①水电厂S–1:
Xjss–1=X32*(SN∑1/Sj)=0.246*(3*200/0.875/100)=1.687
②水电厂H–1:
XjsH–1=X33*(SN∑1/Sj)=0.103*(4*300/0.85/100)=1.454
I*S-1”=0.616
I*H-1”=0.71
=0.616*(3*200/0.875)/(√3*230)=1.06KA
=1.06*√[1+2*(1.85-1)²
]=1.657KA
=0.71*(4*300/0.85)/(√3*230)=2.516KA
=2.516*√[1+2*(1.85-1)²
]=3.934KA
I”=IS-1”+IH-1”=1.06+2.516=3.576KA
Ich1=IchS-1+IchH-1=1.657+3.934=5.591KA
I*t=2s-1”=0.649
I*t=2H-1”=0.74
=0.649*(3*200/0.875)/(√3*230)=1.117KA
=0.74*(4*300/0.85)/(√3*230)=2.623KA
It=2”=It=2s-1”+It=2H-1”=1.117+2.623=3.74KA
I*t=4s-1”=0.649
I*t=4H-1”=0.74
=0.74*(4*300/0.85)/(√3*230)=2.623KA
It=4”=It=4s-1”+It=4H-1”=1.117+2.623=3.74KA
⑶、d3点短路电流的计算:
X34=(X19+X21)/2=0.0129
X35=X29+X34+X29*X34/X30
=0.143+0.0129+0.143*0.0129/0.0598=0.187
X36=X30+X34+X30*X34/X29
=0.0598+0.0129+0.0598*0.0129/0.143=0.078
Xjss–1=X35*(SN∑1/Sj)=0.187*(3*200/0.875/100)=1.282
XjsH–1=X36*(SN∑1/Sj)=0.078*(4*300/0.85/100)=1.101
I*S-1”=0.810
I*H-1”=0.94
=0.810*(3*200/0.875)/(√3*230)=1.394KA
=1.394*√[1+2*(1.85-1)²
]=12.18KA
=0.94*(4*300/0.85)/(√3*230)=3.331KA
=3.331*√[1+2*(1.85-1)²
]=5.21KA
I”=IS-1”+IH-1”=1.394+3.331=4.725KA
Ich1=IchS-1+IchH-1=2.81+5.21=7.39KA
I*t=2s-1”=0.888
I*t=2H-1”=1.011
=0.888*(3*200/0.875)/(√3*230)=1.529KA
=1.011*(4*300/0.85)/(√3*230)=3.583KA
It=2”=It=2s-1”+It=2H-1”=1.529+3.583=5.112KA
I*t=4s-1”=0.888
I*t=4H-1”=1.011
=1.011*(4*300/0.85)/(√3*230)=3.583KA
It=4”=It=4s-1”+It=4H-1”=1.529+3.583=5.112KA
电气设备的选择与校验
一、断路器的选择与校验,隔离开关的选择与校验
1、220KV电压等级
断路器
Sn=240MVA
最大工作电流:
Imax=1.05*Sn/(√3*Un)
=1.05*240/(1.732*220)=661A
选SW2-220型断路器
型号
额定电压
额定电流
额定断开电流
极限通过电流
热稳定电流
断开
容量
固有分闸时间
SW2-220
220KV
1000A
15.8KA
59KA
21KA
5000MVA
0.05”
假定主保护动作时间为0.05”,后备保护3.9”。
则:
断路计算时间:
tk=0.05+0.39+0.05=4”
短路点选主变压器与断路器之间,流经该断路器的短路电流为最大。
1)热稳定校验;
I”=6.228KA、I2.0=6.928KA、I4.0=6.56KA
QP=(tK/12)*(I”²
+10Itk/2²
Itk²
)
=(4/12)*(6.228²
+10*6.928²
+6.56²
=187.26[(KA)²
.S]
由于tK>1秒故不计QNP
所以:
QK=QP=187.26[(KA)²
It²
*t=21²
*4=1764[(KA)²
QK<It²
*t热稳定满足。
2)动稳定校验:
ish=Ksh√2*I”=2.55*I”=2.55*6.228=15.8814KA
ies=59KA
因为ies>ish,所以动稳定满足。
3)I”=6.228KA<INbr=15.8KA
ish=15.8814KA<INcl=59KA
综上所述:
隔离开关
选GW6-220G型
型号
额定电压
额定电流
动稳定电流
GW6-220G
50KA
21KA(5秒)
1)热稳定校验
QK=187.26[(KA)²
*5=2205[(KA)²
2)动稳定校验
ish=15.8814KA
ies=50KA
选GW6-220G型隔离开关满足要求。
2、110KV电压等级
IMax=1.05*Sn/(√3*Un)
=1.05*240/(1.732*110)=1323A
选SW2-110I型断路器
额定电压
额定电流
热稳定
电流
SW2-110I
110KV
1500A
31.5KA
80KA
31.5KA(4秒)
6000MVA
0.045”
tk==4”
I”=3.576KA、I2.0=3.74KA、I4.0=3.74KA
=(4/12)*(3.576²
+10*3.74²
+3.74²
=55.55[(KA)²
QK=QP=55.55[(KA)²
*t=31.5²
*4=4961.25[(KA)²
ish=Ksh√2*I”=2.55*I”=2.55*3.576=9.1188KA
ies=80KA
3)I”=3.576KA<INbr=31.5KA
ish=9.1188KA<INcl=80KA
选GW5-110GK型
GW5-110GK
83KA
25KA(4秒)
1)热稳定校验
QK=55.55[(KA)²
*t=25²
*5=2500[(KA)²
ish=9.1188KA
ies=83KA
选GW5-110GK型隔离开关满足要求。
3、10KV电压等级
母线分段断路器,最大工作电流为一组变压器的持续工作电流,因此,母线分段设备同三相变压器回路。
Sn=240/2MVA=120MVA
=1.05*120/(1.732*10.5)=6928A
I4.0=5.112KA
选SN4-10G/8000型断路器
SN4-10G/8000
10KV
8000A
87KA
300KA
120KA(5秒)
3000MVA
0.15”
I”=4.725KA、I2.0=5.112KA、I4.0=5.112KA
=(4/12)*(4.725²
+10*5.112²
+5.112²
=103.26[(KA)²
QK=QP=103.26[(KA)²
*t=120²
*4=72000[(KA)²
ish=Ksh√2*I”=2.55*I”=2.55*4.725=12.049KA
ies=300KA
3)I”=4.725KA<INbr=87KA
ish=12.049KA<INcl=300KA
选GN10-10T/8000型
GN10-10T/8000
250KA
80KA(5秒)
QK=103.26[(KA)²
*t=80²
*5=32000[(KA)²
ish=12.049KA
ies=250KA
选GN10-10T/8000型隔离开关满足要求
二、电压互感器的选择:
6-220KV屋内配电装置一般采用油浸绝缘结构,也可采用树脂浇注绝缘结构的电压互感器。
35-110KV配电装置,一般采用油浸绝缘结构的电压互感器。
220KV及以上配电装置,当容量和准确度等级满足要求时,一般采用电容式电压互感器。
在需要检查和监视一次回路单相接地时,应选用三相五柱式电压互感器或具有第三绕组的单相电压互感器。
根据以上要求选择如下:
电压等级
额定变比
YDR-220
(220000/√3)/(100/√3)/100
YDR-110
(110000/√3)/(100/√3)/100
JDZJ-10
(10000/√3)/(100/√3)/100
三、电流互感器的选择
220KV电压等级
UN=220KVIMax=661Akt
选LCW-220
额定电流比
热稳定倍数(kt)
动稳定倍数(kes)
LCW-220
4*300/5
60
(kt*IN)²
*t=(1.2*60)²
*1=5184[(KA)²
.S](t=1)
QK<(kt*IN)²
热稳定满足。
ies=kes√2*IN=60*1.414*1.2=101.808KA
选LCW-220满足要求。
四、接地开关的选择:
35KV及以上电力系统中必须设置接地开关、选择结果如下:
220KV:
JW1-220
110KV:
JW1-110
五、母线选择与校验
1、220KV侧
IMax=661A
选LGJQ-400型钢芯铝绞线
导体允许最高温度
长期允许载流量
LGJQ-400
70℃
825
1)裸道体载流量在不同海拔高度及环境温度下的综合效正系数:
K=0.83(T=40℃)
Ia-1(40℃)=KIa-1=0.83*825=684.75A
Ia-1(40℃)>IMax
2)正常运行导体温度
Q=Q0+(Qa-1-Q0)*IMax²
/Ia-1²
=25+(70-25)*661²
/685²
=66.9
因为:
C=84
热稳定校验:
Smin=√(Qk*Ks)/C=164mm²
<400mm²
热稳定满足要求
3)电晕校验
Ucr=44.38mSr*(1+0.298/√rb)tg(Dm/r)
m=0.9(绞线)
S=1.0(晴天)
Dab=4mDbc=4mDca=8m
Dm=504cm
R=√(400/∏)=11.29mm=1.129cm
Ucr=44.388*0.9*1.0*(1+0.298/√1.129)*tg(504/1.129)
=153KA
Umax=242/√3=139.88KV
Ucr>Umax
选LGJQ-400满足要求
1、110KV侧
Imax=1323A
选LGJQ-800型钢芯铝绞线
LGJQ-800
1600
1)裸道体载流量在不同海拔高度及环境温度下的综合效正系数:
Ia-1(40℃)=KIa-1=0.83*1600=1328A
=25+(70-25)*1323²
/1328²
=69.6
Smin=√(Qk*Ks)/C=427.9mm²
<800mm²
选LGJQ-800满足要求。
3、10.5KV侧
Imax=6928A
选双槽型导体2*175*80*8
截面尺寸
双槽型导体截面
Kf
导体截面流量
截面积系数
175*80*8
4880mm²
1.195
6600A
25m²
六、避雷器的选择
220KV发电厂、变电所的配电装置选FZ型号。
选FZ-220J
灭弧电压
公频放电电压
FZ-220J
488KV-536KV
校验:
(1)、0.8*1.1*220=193.6KV(导线对地电压)
193.6KV<200KV
(2)、K0=3
K0uxg=3*1.1*220/1.732=419.1KV
419.1KV<488KV
1.8*200=360KV
360KV<488KV
FZ-220J合格
选FZ-110J
FZ-110J
100KV
224KV-268KV
(1)、0.8*1.1*110=96.8KV(导线对地电压)
96.8KV<100KV
(2)、K0=3.5
K0uxg=3.5*1.1*110/1.732=244.5KV
244.5KV<268KV
1.8*100=180KV
180KV<268KV
FZ-110J合格
3、10.5KV电压等级
选FZ-10
FZ-10
12.7KV
26KV-31KV
(1)、1.1*10=11KV(导线对地电压)
11KV<12.7KV
(2)、K0=4
K0uxg=4*1.1*10/1.732=25.4KV
25.4KV<26KV
1.8*12.7=22.9KV
22.9KV<26KV
FZ-10合格
4、220KV、110KV变压器中性点避雷器
(1)220KV电压等级FZ-1