1、数据中心CFD气流组织模拟方案数据机房CFD模拟报告一、机房内主要参数机房总面积404(含空调间),高度4.8m,高架地板高度1m。房间型空调数量(7+2)台(全部热备状态运行),单台空调额定显冷量(回风温度35)160kW,额定风量40000m/h,最低运行风量20000m/h,下沉式风机,变风量运行,空调尺寸:宽x深x高=2550x1000x2000mm。9台房间型空调实际运行参数如下表:空调编号WCU-1WCU-2WCU-3WCU-4WCU-5WCU-6WCU-7WCU-8WCU-9合计风量m/h2500025000250002000020000200002000020000200001
2、95000显制冷量kW74.773.571.150.344.643.447.348.350.6500回风温度3231.831.630.629.729.530.130.330.630.8(加权平均值)送风温度23232323232323232323(加权平均值)300mm宽列间空调4台(全部运行),单台空调额定显冷量(回风温度35)24kW,额定风量5000m/h。空调尺寸:宽x深x高=300x1200x2200mm。4台300mm宽列间空调实际运行参数如下表:空调编号ACU-1ACU-2ACU-3ACU-4合计风量m/h500050005000500020000显制冷量kW15.416.916
3、.518.567回风温度30.331.230.932.131.1(加权平均值)送风温度2121212121(加权平均值)600mm宽列间空调10 台(全部运行),单台空调额定显冷量(回风温度35)40kW,额定风量8500m/h。空调尺寸:宽x深x高=600x1200x2200mm。10台600mm宽列间空调实际运行参数如下表:空调编号ACU-5ACU-6ACU-7ACU-8ACU-9ACU-10ACU-11ACU-12ACU-13ACU-14合计风量m/h850085008500850085008500850085008500850085000显制冷量kW28.328.627.728.427
4、.429.128.729.528.428.3284回风温度31.131.230.831.130.731.431.331.631.131.131.2(加权平均值)送风温度21.121.12121.12121.121.121121.121.121.1(加权平均值)5kW网络核心机柜数量55台,机柜尺寸:宽x深x高=600x1200x2200mm。8kW网络核心机柜数量18台,机柜尺寸:宽x深x高=800x1200x2200mm。12kW网络核心机柜数量6台,机柜尺寸:宽x深x高=800x1200x2200mm。20kW网络核心机柜数量18台,机柜尺寸:宽x深x高=800x1200x2200mm。总
5、热负载851kW。通风地板158块,地板通风率50%。二、三维建模三、温度场模拟3.1各截面温度分布图(设定地板高度为0m)3.1.1截面高度-0.2m温度分布图3.1.2截面高度0.2m温度分布图3.1.3截面高度1.0m温度分布图3.1.4截面高度1.5m温度分布图3.1.5截面高度2.0m温度分布图3.1.6截面高度2.5m温度分布图3.1.7截面高度3.0m温度分布图3.1.8整个机房温度云图 3.2机柜及空调通风口温度分布图 3.2.1机柜通风口温度分布图A3.2.2机柜通风口温度分布图B3.2.3空调回风口温度分布图四、速度场模拟4.1房间型空调送、回风流线图4.1.1房间型空调送风流线图4.1.2房间型空调回风流线图4.2行间空调送、回风流线图4.3各截面风速、风压分布图(设定地板高度为0m)4.3.1截面高度-0.2m风速分布图4.3.2截面高度-0.2m风压分布图4.4各通风地板风量分布图 4.5各机柜通风量分布图五、模拟结果分析机房内温度场分布有些不均匀,但无局部过热点情况,最高温度35。