1、、对相间及相间对地距离不能满足带电规定期需采用母排硫化解决或采用异形母排或母排套热缩套管,接头也应用绝缘罩包覆。、理解低压塑壳断路器附件意义,如下表:序号附件代号含义13300普通型113380带分励线圈及二组辅助触头23300P 带电动操作机构123370带辅助触头及欠压线圈33300Z带手动操作机构133308带报警触头433002电动机保护型143318带分励线圈及报警触头53310带分励线圈153328带辅助触头及报警触头63320带辅助触头163338带欠压线圈及报警触头73330带欠压线圈173348带分励线圈、辅助触头及报警触头83340带分励线圈及辅助触头183368带二组辅助
2、触头及报警触头93350带分励线圈及欠压线圈193378带辅助触头、欠压线圈及报警触头103360带二组辅助触头、理解低压抽出式开关柜构造(抽屉柜抽屉安装总有效高度1800.00mm),详见下表:开关柜型号抽屉模数GCKGCSMNS1/2单元1/229层(或1/28层)11层9层1/4单元/1/441单元9层(1单元高度为:200.00mm)或8层(1单元高度为:220.00mm)11层(1单元高度为:160.00mm)1.5单元6层(1.5单元高度为:300.00mm)1.5单元高度为:240.00mm2单元4层(2单元高度为:400.00mm)或4层(2单元高度为:440.00mm)2单元
3、高度为:320.00mm3单元3层(3单元高度为:600.00mm)3单元高度为:480.00mm注:1、以惯用塑壳断路器而言,63A抽屉模数为1/2或1/4,100A(125A)、160A、225A(250A)为1模数或1.5模数,400A为2模数或3模数,630A为2模数或3模数,当630A做成抽屉有困难时可改为固定插拔式安装。2、GCS、MNS有经济型与原则型之分;GCK、GCS、MNS还可做成固定分隔式。3、抽屉柜单元抽屉有效安装尺寸:160mm:160.00mm-41.00mm=119.00mm;200mm:200.00mm-41.00mm=159.00mm;220mm:220.00
4、mm-41.00mm=179.00mm;240mm:240.00mm-41.00mm=199.00mm320mm:320.00mm-41.00mm=279.00mm400mm:400.00mm-41.00mm=359.00mm600mm:600.00mm-41.00mm=559.00mm、GGD壳体电器元件有效安装尺寸:600mm柜宽:600.00mm-52-252-302=480.00mm800mm柜宽:800.00mm-52=680.00mm1000mm柜宽:1000.00mm-52=880.00mm1200mm柜宽:1200.00mm-52=1080.00mm、低压柜母线计算:变压器上进
5、线及联系柜三相主母排单拼大概16米(柜宽为800mm时)。当进线柜带计量时,由于计量互感器及计量表计占用一定空间致使刀开关及空气开关安装位置都要下移,故母线长度还应加长每相约0.6m;当母线长度不不大于6m时,母线之间需考虑搭接头;当母线为双拼或三拼时,还需考虑垫块;当进出线电缆较多时应考虑横排出线。五、熟悉并掌握惯用技术数据1、母排理论重量及载流量选用表a)、接触面搪锡或镀锡。b)、环境温度:铜母线为40,铝母线为35,最高工作温度为85。c)、周边环境温度不等于40校正系数见下表系数见下表周边环境温度20253035404550温度校正系数1.291.251.201.151.111.051
6、.00.940.88d)、周边环境温度不等于35校正系数见下表1.221.181.141.090.950.890.84e)、理论重量及载流量选用表矩型母线容许载流量(交流/直流)最高温度+85规格(mm)重量(kg/m)容许载流量(A)铜铝单根双根150.40.12205-170200.530.16270220250.670.20330301.070.32465401.420.43610-/1060495-/8801.780.54685/690-/1220555/560-/995502.220.68840/850-/1490-/12152.670.81935/940-/1660765/770-
7、/1355603.20.971100/11201700/1950900/9101390/1605804.271.31445/14752060/25701190/12001680/20701005.341.621770/18302410/31701470/1500/20951290/13102110/24201055/10751730/18905.71.731650/17152560/30201360/13952100/24707.122.162030/21303720/39901670/17402460/30401208.532.592340/25403320/43001960/2100273
8、0/34501440/14902500/26601190/12102070/21701855/19453030/34301520/15852480/28208.92.72260/24203520/42251870/19602940/345010.73.242585/28804000/48902140/23703300/40002、热轧等边角钢钢号规格2.51.1241.4591.3731.7862.4222.9763.7704.4656.3634.8225.7213、热轧普通槽钢374.65.444.86.63435.08.04485.310.0012.6126535.512.3214a140
9、586.014.5314b8.016.7316a1606.517.2316b658.519.744、热轧钢板厚度(mm)重量(kg/m2)7.853.023.551.29.424.031.41.511.77539.252.015.747.119.6257.054.955、依照负荷选用绝缘母线截面额定电流值A326380100125140160180200225250315350400导线截面积mm27095120185240额定电流A电缆截面积铜排尽寸数量截面积mm2尺寸mmmm500150630700、8006、以空气作为绝缘介质柜内各相导体间与对地净距(cm)额定电压KV3.67.2244
10、0.5导体至接地间净距7.512.5不同相导体间净距导体至无孔遮栏间净距10.515.52133导体至网状遮栏间净距17.522.528无遮栏裸导体至地板间净距237.5242.5248260需要不同步停电检修无遮栏裸导体间水平净距187.5190129.5198210出线套管至屋外通道地面间净距海拔高度超过1000m时1、2项应按每升高1000m增大10%进行修正;36项值应分别增长1或2项值修正值。7、高原型开关内一次元件带电距离海拔高度(m)额定电压(KV)相间、相对地空气绝缘距离(mm)100025003000350040007583869094981101151301381441561633003453603753908、工频耐压水平3436384346424749535660106111119126135上表各值为在海拔高度为1000m处(即在加工厂家内)工频耐压实验值。以上表格里信息如果在手机上看效果不好话,可以选取“分享到手机QQ上-我电脑”然后在电脑网页上阅读。
copyright@ 2008-2022 冰豆网网站版权所有
经营许可证编号:鄂ICP备2022015515号-1