1、按PAR#键,输入访问的参数号,如3013. 完成变频器Start-up向导按键,选中Start-up菜单,进入启动向导。启动向导结构如下:选择”Begin Start Up”,按确认键进入。面板提示“Start-Up consists of several steps to configure the drive.Press Enter”, 按“Enter”键确认。面板提示“Geneal Startup”“Appl Specific“选择“Geneal Startup”,按“Enter“键确认面板显示:“Motor Control”“Motor Data”“Feedback”“Limits”
2、“Ref Ramp Stop“I/O”顺序选择以上菜单进入选择”Motor Control”菜单,面板显示”This section select the type of Motor Control the drive will use.Press Enter”,按“Enter”键确认“Please Select:Sensorless Vect V/HzFlux Vector”对于原料变频器,选择“Sensorless Vect”,对于烧结机一台变频器带两台电机应用,选择“V/Hz”“Motor Control”设置完成后,选择“Motor Data”,按“Enter”确认变频器面板显示“Ed
3、it Motor NP Volts” “ 400 VAC”按”Enter”确认“Select type of power units shown on motor nameplateHPKW”选择”KW”,按“Enter”键确认“Edit Motor NP PowerXX KW”,输入电机额定功率(使用软按键,删除原有显示值再输入电机功率值),按”Enter”键确认“Edit Motor NP Amps”XX Amps”,输入电机额定电流值,按”Enter”键确认“Edit Motor NP HertzXX Hz” 变频器额定是50Hz,按”Enter”键确认“Edit Motor NP RP
4、MXX RPM”,输入电机额定转速,按”Enter”键确认“Edit Motr OL Factor1” 电机缺省过载倍数为1,按Enter键确认“Edit Motor PolesXX Pole” ,输入电机极数(注意:4极电机同步转速1500RPM,6极电机同步转速1000RPM),按Enter键确认“Edit Speed Units Hz 0” 缺省是 “Hz 0”,按Enter键确认(如果要改为RPM,这里设置“RPM 1”)“Motor Data”设置完成后,可直接跳过”Feedback”,变频器缺省工作在无编码器反馈模式,选择”Limits”,按Enter键确认“Edit Max Fw
5、d Speed 50Hz” 按Enter键确认“Edit Max Rev Speed-50Hz”按Enter键确认“Edit Min Fwd Speed1.0 Hz”按Enter键确认“Edit Min Rev Speed1.0 Hz” 按Enter键确认“Limits”设置完成后,选择”Tests”,按Enter键确认“Complete these steps in orderDirection TestAuto TuneDone”选择“direction test”,按Enter键确认“Press START to begin test!Motor will run!”键起动变频器“Is
6、the direction of rotation forward?YesNo”如果变频器旋转方向为正向,选择“Yes”,按Enter键确认如果变频器旋转方向为反向,选择”No”,按Enter键确认“How would you like to fix motor polarity?Automatic ChangeChange mtr wires”选择”Automatic Change”,按Enter键确认“Press STOPStartup will then automatically change rotation as if motor lead were reversed.”键停止变频
7、器变频器会再次显示选择“Yes”,按Enter键确认“Direction Test”完成后,选择”Auto Tune”“ IMPORTANT ! Use Rotate Tune for best results.Rotate Tune works best under no load/low friction condition.Use Static Tune if load can not be rotated .Press Enter”按Enter键确认“Select the tuning mode:Rotate TuneStatic Tune”选择”Rotate Tune”,按Enter
8、键确认“Press START to begin test.CAUTION:Rotate Tune will cause motor shaft rotation.”变频器会自动完成整定过程,整定结束后,按键停止变频器,选择“Done”,按Enter键确认。“Tests”完成后,选择”Ref Ramp Stop”,按Enter键确认“Edit Direction Mode Unipolar 0”“Please select the speed reference source:Local HIMAnalog InputMore Choices”选择”Analog Input”,按Enter键确
9、认“Edit Spd Ref A selSelect Port to useZero SpeedPort 00 PowerFlex 753Port 04 I/O Module 24V”选择”Port 00 PowerFlex 753”,按Enter键确认“Edit Spd Ref A SelSelect parameter To Use.”按向下方向键翻页,选中”Par 0558 MOP Reference”,按Enter键确认“Edit DI MOP IncSelect Port To UseDisabled选中”Port 04 I/O Module 24V”,按Enter键确认Select
10、 Param To UsePar 0001 Dig In Sts”,选中”Par 0001 Dig In Sts”,按Enter键确认Select Bit To Use”选中”Bit 03 Input 3”,按Enter键确认(这里 I/O Module 24V DI 3接机旁操作箱频率上升按钮,实际选择哪位以现场接线为准)“Edit DI MOP Dec选中”Bit 04 Input 4”,按Enter键确认(这里 I/O Module 24V DI 4接机旁操作箱频率下降按钮,实际选择哪位以现场接线为准)“Edit MOP Rate 1.000%/S”“Do you want to sav
11、e MOP speed at stop?NoYes”选择”No”,按Enter键确认“Do you want to save MOP speed at power down?“Edit Stop Mode A Ramp 1”“Edit Bus Reg Mode AAdjust Freq 1”“Edit Accel Time 110.00 Secs”暂时用缺省加速时间10秒钟,按Enter键确认“Edit Decel Time 1暂时用缺省减速时间10秒钟,按Enter键确认“Do you want to perform S-Curve for accel/decal?选择”Yes”,按Ente
12、r键确认“Edit S Curve Accel0.00%”修改为10%,按Enter键确认“Edit S Curve decel以上设置完成后,选择”I/O”,按Enter键确认“Make a selection:Start Stop & Dir.”选择”Start Stop & Dir”,按Enter键确认“This section defines Start Stop and Direction digital input functions. Press Enter”“Will a digital input be used as a START source?选择”Yes”,按Ente
13、r键确认“Is REVERSE required from a digital input?选择”NO”,按Enter键确认“Enter choice for the control method:3 wire2 wire”选择”2 wire”,按Enter键确认“Edit DI Run选择”Port 04 I/O Module 24V”,按Enter键确认选中”Bit 01 Input 1”,按Enter键确认(这里 I/O Module 24V DI 1接运行命令,实际选择哪位以现场接线为准)“Edit Digital In Cfg Run Edge 0“ 设置完”Start Stop &
14、 Dir”后,直接跳过”Digital Inputs”,”Digital Outputs”,”Analog Outputs”,选择”Done”,按Enter键确认。再次选择”Done”,按Enter键确认。“Please make selectionGeneral StartupAppl SpecificExit Startup”选择”Exit Startup”,按Enter键确认,退出启动向导剩余的工作是完成对I/O Module的设置。首先选中I/O Module,按键,选择Ports,选择“04 I/O Module 24V”,I/O设置数字量输入,输出和模拟量输出Digital in
15、选择 digital in status bit 1 为运行(已经通过设置向导设置好了)Digital output设置RO0设置:按PAR# 10,按EDIT键“Edit RO0 Sel Disabled选择”Port 00 PowerFlex 753”,按Enter键确认用向下方将键选中”Par 0935 Drive Status 1”,按Enter键确认选中”Bit 00 Ready”,按Enter键确认RO1设置:按PAR# 20,按EDIT键“Edit RO01Sel选中”Bit 16 Running”,按Enter键确认设置模拟量输出信号类型为毫安信号按PAR# 70,按EDIT键
16、“Port 07 Host Param 70Anlg Out TypeXXXXXXXX00”按EDIT键,把最低两位都设为”1”,按Enter键确认AO1设置按PAR# 85,按EDIT键“Edit Anlg Out 1 Sel选择Port 00 PowerFlex 753,按Enter键确认Select Param to use.选择“Par 0001 Output Frequency”,按Enter键确认设置模拟量输入信号类型为毫安信号按PAR# 45,按EDIT键“Port 07 Host Param 45Anlg In Type选中Port 00 PowerFlex 753,按PAR#
17、 550,按Enter键确认“Port 00 Dev Param 550 Spd Ref B Sel”,按EDIT键“Edit Spd Ref B sel选择”Port 04 Port 04 I/O Module 24V”,按Enter键确认“Edit Spd Ref B SelPar 0050 Anlg In 0 Value Par 0060 Anlg In 1 Value ”按向下方向键翻页,选中”Par 0060 Anlg In 1 Value”,按Enter键确认最后完成本体和远程速度给定切换按PAR# 174,按Enter键确认“Port 00 Dev Param 174 Spd Ref B SelDI Speed Sel 1 ”,按EDIT键“Edit DI Speed Sel 1 选择Port 04 I/O Module 24V,按Enter键确认Par 0001 Dig In Sts”选择Par 0001 Dig In Sts,按Enter键确认选择”Bit 02 Input 2”,按Enter键确认I/O Module Input 2 断开时,使用本地机旁操作箱升速按钮和降速按钮调节频率;I/O Module Input 2 闭合时,使用远程PLC模拟量调节频率;
copyright@ 2008-2022 冰豆网网站版权所有