1、 Installation,use and maintenance instructions Gas Burners RS 190/M Low-High-Low or Modulating Operation C6505057 CONTENTSTECHNICAL DATA.page 3burner models .3Accessories.3Burner description.4Packaging-Weight.4Max.dimensions.4Standard equipment.4Firing rates.5Minimum furnace dimensions.5Gas pressure
2、.6INSTALLATION.7Boiler plate.7Blast tube length .7Securing the burner to the boiler.7Ignition pilot adjustment.7Combustion head adjustment.8Gas piping .9Adjustments before first firing.10Servomotor.11Burner starting.12Air pressure switch.13Maximum gas pressure switch.13Minimum gas pressure switch.13
3、Flame present check.13Maintenance.14Factory wiring diagram-burner mounted LFL.15Field wiring diagram-Burner mounted LFL.16Factory wiring diagram-remote panel.17Appendix-Burner firing rates according to air density.18Siemens LFL control sequence of operation.19Siemens LFL troubleshooting guide.20Burn
4、er start up report.21N.B.Figures mentioned in the text are identified as follows:#1)(A)=part 1 of figure A,same page as text;#1)(A)p.4=part 1 of figure A,page number 4.WARNINGIf you smell gas:#Do not touch any electrical items.Open all windows.Close all gas supply valves.Contact your local gas autho
5、rity immediately.Do not store flammable or hazardous materials in the vicinityof fuel burning appliances.Improper installation,adjustment,alteration,service or main-tenance can cause property damage,personal injury ordeath.Refer to this manual for instructional or additional in-formation.Consult a c
6、ertified installer,service representativeor the gas supplier for further assistance.Burner shall be installed in accordance with manufacturersrequirements as outlined in this manual,local codes and au-thorities having juristiction.2 TECHNICAL DATA MODELRS 190/MOutput(1)MAX.kW1420-2542MBtu/hr4845-867
7、3MIN.kW522MBtu/hr1781FuelNatural or Propane gas-max.deliverySCFH8673-pressure at max.delivery(2)“WC5.9OperationLow-high or modulatingStandard applicationsBoilers:#water,steam,thermal oilAmbient temperatureF32-104(0-40 C)Combustion air temperatureF max140(60 C)Main electrical supply(+/-10%)V/Ph/Hz208
8、-230/460/575/3/60Fan motorrpm3400W-HP4000-5.5V208-230/460/575A15.8-9.1-7.3Ignition transformerV1-V2120 V-1 x 7 kVI1-I21.6 A-23 mAElectrical power consumptionW max5500Electrical protectionNEMA 1Noise levels(3)dBA83.1(1)Reference conditions:#Ambient temperature 68 F(20 C)-Barometric pressure 394”WC-Al
9、titude 329 ft.(2)Pressure at test point 17)(A)p.4,with zero pressure in the combustion chamber,with open gas ring 2)(B)p.6 an maximum burner output(3)Sound pressure measured in manufacturers combustion laboratory,with burner operating on test boiler and at maximum rated output.Burner models designat
10、ions:#ModelCodeVoltageFlame SafeguardRS 190/MC9527300(3787670)208-230/460/3/60Burner mountedC9527301(3787670)575/3/60Remote panelC9627300(3787672)208-230/460/3/60Burner mountedC9627301(3787672)575/3/60Remote panel ACCESSORIES(optional):#Kit for LPG operation:#The kit allows the RS 190/M burners to o
11、perate on LPG.BURNERRS 190/MOutputkW516-2542MBtu/hr1761-8673Code3010276 Gas train according to UL regulation:#see page 9.Important:#The installer is responsible for the supply and installation of any safety device(s)not indicated in this manual.3 BURNER DESCRIPTION(A)(A)ABClbs4931/32“281/2“30 29/32“
12、181(B)ABCDE11D2430D36D731FGHILM NO2115“51 21“9 1“5 29”2”1Combustion head2Ignition electrode3Screw for combustion head adjustment4High gas pressure switch5Sleeve6Servomotor controlling the gas butterfly valve and ofair damper(by means of a variable profile cam mech-anism).When the burner is not opera
13、ting the air damper is fully closed in order to reduce heat dispersion from the boiler due to the flue draught which draws airfrom the fan suction inlet.7Plug-socket on ionisation proble(flame rod)cable8Extensions for slide bars 16)(with kit)9Motor contactor and thermal overload with reset but-ton10
14、 Power switch for different operations:#automatic-manual-offSwitch for:#Power increase-power reduction11 Terminal strip12 Pilot burner attachment13 Flame safeguard(flame relay)with lock-out pilot lightand lock-out reset button14 Flame inspection window15 Low air pressure switch(differential operatin
15、g type)16 Slide bars for opening the burner and inspecting thecombustion head17 Gas pressure test point and head fixing screw18 Air pressure test point19 Flame sensor probe(flame rod)20 Air damper21 Air inlet to fan22 Screws securing fan to sleeve23 Gas input pipework24 Gas butterfly valve25 Boiler
16、mounting flange26 Flame stability disk27 Ignition pilotTwo types of burner failure may occur:#Flame safeguard lock-out:#if the flame relay 13)(A)push-button lights up,it indicates that the burner is in lock-out.To reset,press the pushbutton.Motor trip:#release by pressing the pushbutton on ther-mal relay 9)(A).PACKAGING -WEIGHT (B)-Approximate measure-ments The burner is shipped skid mounted Outer dimen-sions of packaging are indicated in(B).The weight of the burner complete with packaging is indicated in Tabl