电气接线标准

WORKINSTRUCTION

DKIGENERALWIRINGPRACTICES

1.Scope

ThisworkinstructionshallbeappliedintheDiamondKeyInternationalWorkshopsElectricalwiringonskidsorassociatedisrequired.

Allwiringtobeperformedbyqualifiedexperiencedwiringpersonnelusingappropriatetoolsforstrippinginsulation,cutting,solderingandattachingmechanicalcrimptypeterminalswiththecorrectdiesandtoolsasadvisedbytheterminalmanufacturer.

ForemostelectricalinstallationsaretobeperformedtolatestissueofwiringrulesAS/NZS3000aswellasIECdirectives

 

2.Generalinstallation:

2.1.Whenremovinginsulationfromtheconductor,wirestrandsshallnotbenickedordamaged.Properstrippingtoolsshallbeusedtoavoidsuchdamage.

2.2.Wireandcabletiesshallbesnugbutshallnotbesotightastocauseindentationandcoldflowdamagetotheinsulation.

2.3.Cabletiesshallbetensionedandtrimmedusingcabletiemanufacturerstooling.

(Useofsidecuttersfortrimming,isnotpermitted)

2.4.AllwiringwithinExe,Exiorsimilarenclosurestobeterminated.

2.5.Wherepossible,adhesiveinstalledmountingbasesshouldnotbeusedfortiesorcablesupportunlessaffixedwithamechanicalfastener.

2.6.Wireandcabledressshallallowsufficientslackforremovalandreapplicationofthewireterminations,atleasttwicewithoutexcesstension.

2.7.Allwireandcable,includingthatinductsandconduit,shallbehandledtobefreefromkinksandinsulationabrasions.

2.8.Wireinstallationshallnotbesubjecttoaccumulationofwater,oilorotherforeignmatter.

2.9.InstrumentcablesaretobefreeofOrangedrainwires.

2.10.Cabletobelaidoutneatlyandunduecrossingofcablesistobeavoided(referAppendix3).

2.11.Allwireshallbeprotectedagainstanycontactwithanysurfaceotherthanthatdesignedspecificallytosupportorprotectthewire.

2.12.Protectiveedging,Grommetsandsimilarmaterialsshallbeappliedwhereveranypossibilityexistsforawiretocontactasharpedge.

2.13.Adriploopshallbeprovidedineachwireorcablewherewatercouldotherwiserunalongthewireorcabletothepointwhereitentersaboxorenclosure.

2.14.Wire/cablesformingpartofthewiringsystemshallbebentinamannerthatwillnotcausedamageorplaceunduestressontheirsheathingorinsulation.

2.14.1.1.Wheremanufacturer’sinformationonrecommendedbendradiiisnotavailable,thefollowingradiimaybeconsideredsuitable

2.14.1.2.Unarmouredsheathedcables6timesthecablediameter

2.14.1.3.Armouredsheathedcables12timesthecablediameter

2.14.1.4.(ChangeofdirectionAS/NZS30003.9.7.)

2.15.Wirejumpersondevicesshallberunwithintheloom,soastonotbemisplacedondevicereplacement.

 

3.CableColorsandtype:

WherepossibletheDKIstandardsforcablecolorsaretobestrictlyfollowed

3.1.Powercables–110v–240vOrange

3.2.Instrumentcables–0v–24vBlack

3.3.IScables-Blue

3.4.Flexiblecablesandcordsshallbe0.6/1kVor450/750Vrated,heavyduty,withmultiplestrandedtinnedcopperconductorsof1.5sqmmminimumcrosssectionandwithatinnedcopperbraidedscreen.

3.5.InsulationmaterialsmaybeeitherPVC,EPRorNBR

3.6.ScreensshallbeincludedinallZone1cables,withtheexceptionofshortlengths(not>600mm)ofinstrumentcables

3.7.WireandcabletypeusedshallbeasstatedonDKIdrawings,alternativesshallbesubmittedforDKIapproved.

3.8.Cablesusedforthetransmissionofsignalsfromtemperature,pressure,speed,flow,weight,levelandsimilarsignals,orany4-20mA,0-20mA,24VDCorsimilarextralowvoltagesignalshallcomprisetwistedscreenedpairs.

3.9.WireandcablesizestobeasstatedoragreedbyDKIcableblockdiagramandcableschedule,alternativesshallbesubmittedforDKIapproved.

 

4.WireColorsinsideofExe,Exdboxesandjunctionboxesshallbe:

240vActive

∙Red

∙White

∙Brown

240vNeutral

∙Black

∙LightBlue

240vEarth

∙Yellow/green

Allearthbonding

∙Yellow/green

+24vdc

∙Grey

24OV

∙Brown

+12vdc

∙Orange

12OV

∙Blue

4.1.Inextremecaseswhereuseofdifferentcorescolorisunavoidable,thenheatshrinksleevingappliedtothecoresisrequired.

5.Wiresegregation:

-

5.1.SegregationofwiringwithdifferingvoltageratedInsulationi.e.Dekoron110vacandPower/control0.6/1kvisamandatoryrequirement..

5.2.Theminimumseparationdistancebetweensuchcablesortheirrelatedequipmentshallnotbelessthanthedistancesgiveninthefollowingtable:

Circuitrating

(kVA)

Unshielded

powercables

(mm)

Shielded

powercables

(mm)

<1

300

25

>1<2

450

50

>2<5

600

150

>5

1500

300

SeparationbetweenPowerandSignal/DataCables

5.3.IntrinsicallySafecablesmayonlyruntogetherwithnonI.S.cablesprovidedthateithertheIntrinsicallySafecablesorthenon-I.S.cablesarearmoured.

5.4.Whereanon-armouredintrinsicallysafecableisinstalledwithnonarmouredpowerandcontrolcables,asegregationdistanceof50mmminimummustbestrictlyobservedthroughoutthecompletecablerun,andwithinanyswitchboard,junctionboxandthelike.

 

6.WireMarking:

-

6.1.AllwiresregardlessoflocationshallbeplainlyandsuitablyidentifiedwithDKIapproved,wiremarkersonbothendsoftheconductor,asperDKIwiringdiagrams.

6.2.Eachendofthewireshallhavethesameidentifyingmarkere.g.RTD+1,OUT#46AC,ESS-A,andetc(ReferAppendix1).Donotlabelthecablecoresaccordingtocablecolournoraccordingtotheterminalthatthewireisconnectedto.

6.3.Labelingonbothendsofacable/coremustbeidentical.Ifpossible,itshouldbeconsistentthroughoutthecircuit.

6.4.Inadditiontonumbering,allcablescarryingIntrinsicallySafecircuitsshallbeidentifiedbya200mmlengthofBLUEheatshrinkmaterialateachtermination(i.e.ateverycableglandingpoint).

 

7.PullingCompound:

-

7.1.PullingCompound,ifused,shallbenon-conductiveornon-odorous.

 

8.Conduit-Rigid:

-

8.1.ConduitshallbeSteelGalvanisedandconformtoAS/NZS2053.7inconjunctionwithAS/NZS2053.1orIECdirectives

8.2.Conduitbendsshallhavesuitablebendradiiforthenumberofwiresbeingcarried.

8.3.Conduitshallhavenomorethan40%fillratiofornewinstallations.

8.4.ConduitElbowsandTeesshallbeSteelandoftheinspectiontype.

8.5.Conduitentriesaftercuttingandthreadformingshallnothaveanyburrsorsharpedgesinsideoroutside,withallfilingsremovedbeforeinstallation.

8.6.Conduitentry/exitsintoEnclosuresorjunctionpointsaretohaveNylonorbrassbushes.

8.7.Conduitshallnotbeweldedtoanystructures.

 

9.ConduitSealingFittings:

9.1.Conduitsealingfittings(stuffingboxes)musttocomplytoASorIECstandards

9.2.InprinciplesealingisnottobedoneuntilaftertheFAT

9.3.Manufacturessealingcompoundisonlytobeused

9.4.Sealingmustbedoneinaccordancewiththemanufacturesinstructions

9.5.Forverticalsealingaphysicalbarriersuchassiliconmustbelaidatthelowerpointoftheconduitsealtoensurethecompoundcannotpass/drippastthesealingarea.

9.6.Forhorizontalsealingaphysicalbarriersuchassiliconmustbelaidatbothendpointsoftheconduitsealtoensurethecompoundcannotpass/drippastthesealingarea.

9.7.Allwirespassingthroughtheconduitsealmusthaveallouterinsulationandanyplasticwrappingremoved.Ensurethattheremovaloftheinsulationisvisible/traceableevenaftersealinghasbeendone(forinspectionpurposes).

9.8.Allwiresaretobestraightenedandnottwistedtogetherwhenpassingthroughthesealingarea.

9.9.Sealingcompoundistobemixedasperthemanufacturer’sinstructions,

9.10.PouringofthecompoundmustensurethatthesealingfittingiscompletelyfilledtotherequiredlevelandmustnotcoverthePlugbungthread.

9.11.Sealingfittingplugs/bungsarenottobeinstalleduntilthesealingcompoundhashardenedtoensuretheplug/bungisnotincontactwiththecompound.

 

10.Conduit-Flexible:

-

 

10.1.FlexibleconduitshallbeofaDKIapprovedtypesuchasSealsafe.

10.2.EquivalenttypesmaybepresentedtoDKIforapproval)

10.3.ConduitandfittingsshallberatedtoIP66whenentering/exitingenclosuresorterminationjunctionboxes.

10.4.WhenaFlexibleconduithasIScableinsidebothendsoftheconduitmustbesleevedinbluecolor.

11.CableGlands:

-

11.1.GlandsaretosuittheHazardousapplication.AndconformtoIECorASstandards

11.2.Glandsaretobeofcorrectsizeforthecablesused.

11.3.AllGlandsenteringanExdboxmustbeBarriertype

11.4.AllglandsenteringanExeboxmustberatedExetypeminimum.

11.5.Glandstobetightenedtomanufacturersrecommendations.

11.6.BarrierGlandstohavethecorrectepoxyresinapplied,tomanufacturer’sinstructions.

11.7.GlandstohavenylonwashersfittedtoEnclosureexternals.

11.8.GlandstohaveShroudsfitted,unlessrequestedbythecustomernotto.

Cableglandtypesshallbeselectedasfollows:

Cabletype

Enclosure

GlandType

Manufacturers

PVC/PVC/SWA/PVC

XLPE/PVC/SWA/PVC

Exe

CompressionglandscertifiedExeandfittedwithasealinggasket

∙Crouse-HindstypeTWAE

∙CMPE1FWseries

PVC/PVC/SWA/PVC

XLPE/PVC/SWA/PVC

Exd

SeeAS/NZS60079.14Figure2

CompressionglandcertifiedExdandfittedwithsealinggasket

∙CMPE1FWseries

BarriertypeglandcertifiedExd

∙Crouse-HindstypeTWAB

∙CMPPX2Kseries

PVCorEPRScreenedFlexible

ExeorExd

∙CMPE1FXseries

PVC/PVC

XLPE/PVC

IntrinsicallySafecircuits

Generalindustrialglands.

∙Crouse-HindsTUA

∙CMPA2series

PVC/PVC/SWA/PVC

XLPE/PVC/SWA