三菱Q系列PLC Error Code List.docx
《三菱Q系列PLC Error Code List.docx》由会员分享,可在线阅读,更多相关《三菱Q系列PLC Error Code List.docx(21页珍藏版)》请在冰豆网上搜索。
三菱Q系列PLCErrorCodeList
Errorcodelist[Errorcode1000]
ApplicablemachineBasicmodelQCPU,HighPerformancemodelQCPU,ProcessCPU
RedundantCPU,UniversalmodelQCPU
=====================================================================================
Errorcode(SD0)1000
ErrormessageMAINCPUDOWN
Commoninformation(SD5-15)-
Individualinformation(SD16-26)-
LEDstatus(RUN)Off
LEDstatus(ERROR)Flicker
PLCoperatingstateStop
DiagnosticstimingAlways
Errordescription&cause
RunawayorfailureoftheCPUmodule.
(1)Malfunctioningduetonoiseorotherreason.
(2)Hardwarefailure.
Correctiveaction
(1)Takenoisereductionmeasures.
(2)ResettheCPUmoduleandrunitagain.
Ifthesameerrorcodeisdisplayedagain,thecauseisahardwarefailureoftheCPUmodule.
(PleaseconsultyourlocalMitsubishirepresentative,explainingadetaileddescriptionoftheproblem.)
------------------------------------------------------------------------------------
Errorcodelist[Errorcode1001]
ApplicablemachineLseriesCPU
=====================================================================================
Errorcode(SD0)1000
ErrormessageCPUUNITDOWN
Commoninformation(SD5-15)-
Individualinformation(SD16-26)Failureinformation
LEDstatus(RUN)Off
LEDstatus(ERROR)Flicker
PLCoperatingstateStop
DiagnosticstimingAlways
Errordescription&cause
RunawayorfailureoftheCPUmodule.
(1)Malfunctioningduetonoiseorotherreason.
(2)Hardwarefailure.
Correctiveaction
(1)Takenoisereductionmeasures.
(2)ResettheCPUmoduleandrunitagain.
Ifthesameerrorcodeisdisplayedagain,thecauseisahardwarefailureoftheCPUmodule.
(PleaseconsultyourlocalMitsubishirepresentative,explainingadetaileddescriptionoftheproblem.)
ApplicablemachineBasicmodelQCPU,HighPerformancemodelQCPU,ProcessCPU
RedundantCPU,UniversalmodelQCPU
=====================================================================================
Errorcode(SD0)1001
ErrormessageMAINCPUDOWN
Commoninformation(SD5-15)-
Individualinformation(SD16-26)-
LEDstatus(RUN)Off
LEDstatus(ERROR)Flicker
PLCoperatingstateStop
DiagnosticstimingAlways
Errordescription&cause
RunawayorfailureoftheCPUmodule.
(1)Malfunctioningduetonoiseorotherreason.
(2)Hardwarefailure.
(3)Thedevicesoutsidetherangewasaccessedeventhoughdevicechecksareprohibited(SM237ison).
(ThiserroroccursonlywhenanyoftheBMOV,FMOV,orDFMOVinstructionsisexecuted.(UniversalmodelQCPUonly.))
Correctiveaction
(1)Takenoisereductionmeasures.
(2)ResettheCPUmoduleandrunitagain.
Ifthesameerrorcodeisdisplayedagain,thecauseisahardwarefailureoftheCPUmodule.
(PleaseconsultyourlocalMitsubishirepresentative,explainingadetaileddescriptionoftheproblem.)
(3)CheckthedevicesspecifiedbyBMOV,FMOV,andDFMOVinstructionsandcorrectthedevicesettings.
(UniversalmodelQCPUonly)
------------------------------------------------------------------------------------
ApplicablemachineLseriesCPU
=====================================================================================
Errorcode(SD0)1001
ErrormessageCPUUNITDOWN
Commoninformation(SD5-15)-
Individualinformation(SD16-26)Failureinformation
LEDstatus(RUN)Off
LEDstatus(ERROR)Flicker
PLCoperatingstateStop
DiagnosticstimingAlways
Errordescription&cause
RunawayorfailureoftheCPUmodule.
(1)Malfunctioningduetonoiseorotherreason.
(2)Hardwarefailure.
(3)Thedevicesoutsidetherangewasaccessedeventhoughdevicechecksareprohibited(SM237ison).
(ThiserroroccursonlywhenanyoftheBMOV,FMOV,orDFMOVinstructionisexecuted.)
Correctiveaction
(1)Takenoisereductionmeasures.
(2)ResettheCPUmoduleandrunitagain.
Ifthesameerrorcodeisdisplayedagain,thecauseisahardwarefailureoftheCPUmodule.
(PleaseconsultyourlocalMitsubishirepresentative,explainingadetaileddescriptionoftheproblem.)
(3)CheckthedevicesspecifiedbyBMOV,FMOV,orDFMOVinstruction,andcorrectthedevicesettings.
Errorcodelist[Errorcode1002
ApplicablemachineBasicmodelQCPU,HighPerformancemodelQCPU,ProcessCPU
RedundantCPU,UniversalmodelQCPU
=====================================================================================
Errorcode(SD0)1002
ErrormessageMAINCPUDOWN
Commoninformation(SD5-15)-
Individualinformation(SD16-26)-
LEDstatus(RUN)Off
LEDstatus(ERROR)Flicker
PLCoperatingstateStop
DiagnosticstimingAlways
Errordescription&cause
RunawayorfailureoftheCPUmodule.
(1)Malfunctioningduetonoiseorotherreason.
(2)Hardwarefailure.
Correctiveaction
(1)Takenoisereductionmeasures.
(2)ResettheCPUmoduleandrunitagain.
Ifthesameerrorcodeisdisplayedagain,thecauseisahardwarefailureoftheCPUmodule.
(PleaseconsultyourlocalMitsubishirepresentative,explainingadetaileddescriptionoftheproblem.)
------------------------------------------------------------------------------------
ApplicablemachineLseriesCPU
=====================================================================================
Errorcode(SD0)1002
ErrormessageCPUUNITDOWN
Commoninformation(SD5-15)-
Individualinformation(SD16-26)Failureinformation
LEDstatus(RUN)Off
LEDstatus(ERROR)Flicker
PLCoperatingstateStop
DiagnosticstimingAlways
Errordescription&cause
RunawayorfailureoftheCPUmodule.
(1)Malfunctioningduetonoiseorotherreason.
(2)Hardwarefailure.
Correctiveaction
(1)Takenoisereductionmeasures.
(2)ResettheCPUmoduleandrunitagain.
Ifthesameerrorcodeisdisplayedagain,thecauseisahardwarefailureoftheCPUmodule.
(PleaseconsultyourlocalMitsubishirepresentative,explainingadetaileddescriptionoftheproblem.)
Errorcodelist[Errorcode1003
ApplicablemachineBasicmodelQCPU,HighPerformancemodelQCPU,ProcessCPU
RedundantCPU,UniversalmodelQCPU
=====================================================================================
Errorcode(SD0)1003
ErrormessageMAINCPUDOWN
Commoninformation(SD5-15)-
Individualinformation(SD16-26)-
LEDstatus(RUN)Off
LEDstatus(ERROR)Flicker
PLCoperatingstateStop
DiagnosticstimingAlways
Errordescription&cause
RunawayorfailureoftheCPUmodule.
(1)Malfunctioningduetonoiseorotherreason.
(2)Hardwarefailure.
Correctiveaction
(1)Takenoisereductionmeasures.
(2)ResettheCPUmoduleandrunitagain.
Ifthesameerrorcodeisdisplayedagain,thecauseisahardwarefailureoftheCPUmodule.
(PleaseconsultyourlocalMitsubishirepresentative,explainingadetaileddescriptionoftheproblem.)
------------------------------------------------------------------------------------
ApplicablemachineLseriesCPU
=====================================================================================
Errorcode(SD0)1003
ErrormessageCPUUNITDOWN
Commoninformation(SD5-15)-
Individualinformation(SD16-26)Failureinformation
LEDstatus(RUN)Off
LEDstatus(ERROR)Flicker
PLCoperatingstateStop
DiagnosticstimingAlways
Errordescription&cause
RunawayorfailureoftheCPUmodule.
(1)Malfunctioningduetonoiseorotherreason.
(2)Hardwarefailure.
Correctiveaction
(1)Takenoisereductionmeasures.
(2)ResettheCPUmoduleandrunitagain.
Ifthesameerrorcodeisdisplayedagain,thecauseisahardwarefailureoftheCPUmodule.
(PleaseconsultyourlocalMitsubishirepresentative,explainingadetaileddescriptionoftheproblem.)
Errorcodelist[Errorcode1004]
ApplicablemachineBasicmodelQCPU,HighPerformancemodelQCPU,ProcessCPURedundantCPU,UniversalmodelQCPU
=====================================================================================
Errorcode(SD0)1004
ErrormessageMAINCPUDOWN
Commoninformation(SD5-15)-
Individualinformation(SD16-26)-
LEDstatus(RUN)Off
LEDstatus(ERROR)Flicker
PLCoperatingstateStop
DiagnosticstimingAlways
Errordescription&cause
RunawayorfailureoftheCPUmodule.
(1)Malfunctioningduetonoiseorotherreason.
(2)Hardwarefailure.
Correctiveaction
(1)Takenoisereductionmeasures.
(2)ResettheCPUmoduleandrunitagain.
Ifthesameerrorcodeisdisplayedagain,thecauseisahardwarefailureoftheCPUmodule.
(PleaseconsultyourlocalMitsubishirepresentative,explainingadetaileddescriptionoftheproblem.)
------------------------------------------------------------------------------------
ApplicablemachineLseriesCPU
=====================================================================================
Errorcode(SD0)1004
ErrormessageCPUUNITDOWN
Commoninformation(SD5-15)-
Individualinformation(SD16-26)Failureinformation
LEDstatus(RUN)Off
LEDstatus(ERROR)Flicker
PLCoperatingstateStop
DiagnosticstimingAlways
Errordescription&cause
RunawayorfailureoftheCPUmodule.
(1)Malfunctioningduetonoiseorotherreason.
(2)Hardwarefailure.
Correctiveaction
(1)Takenoisereductionmeasures.
(2)ResettheCPUmoduleandrunitagain.
Ifthesameerrorcodeisdisplayedagain,thecauseisahardwarefailureoftheCPUmodule.
(PleaseconsultyourlocalMitsubishirepresentative,explainingadetaileddescriptionoftheproblem.)
Errorcodelist[Errorcode1005]
ApplicablemachineBasicmodelQCPU,UniversalmodelQCPU,RemoteI/Omodules
=====================================================================================
Errorcode(SD0)1005
ErrormessageMAINCPUDOWN
Commoninformation(SD5-15)-
Individualinformation(SD16-26)-
LEDstatus(RUN)Off
LEDstatus(ERROR)Flicker
PLCoperatingstateStop
DiagnosticstimingAlways
Errordescripti