BYQseriesliquidresistorisanewstartingequipment,developedforheavyloadingstartingoflargeandmedium-sizewound-rotorasynchronousmotor.Itiswidelyusedinthefieldsofbuildingmaterial,metallurgy,mine,petroleum&chemicalengineeringindustries,etc;Anditistheprefectequipmentforheavyloadingstartingofmotorofballmill,elevator,crusher,aircompressor,fan&pumps,etc.
Ⅱ.Characteristics
1.Theliquidresistorisputinseriesontherotor(orstator)startingcircuitoflargeandmedium-sizemotor,theresistorwillbeautomaticallybroughtintooperationwhenstartingmotor,andauto-cutoffinthefixedtime,sothemainmotorcanrunsmoothly.
2.Accordingtodifferentrequirementofstart-uptoadjustdensityofelectrolyte,thevalueofresistancewillbechangedwithit.Soitcanbesatisfyrequirements.
3.Becauseelectrolytehasverylowsensitivitytotemperature,thisequipmentcanbecontinuouslystartedmanytimes.
4.Becausewedon’tusemechanicalswitchcontact,thisequipmenthasfewworkingformaintenance.
5.Thisliquidresistorhasovercomeshortcomingsofoldresistors(adjustableresistor,oil-immersedstartingresistorandcastironresistorrequire,etc),whichneedhighrequirementforpowernet,largestartingcurrent,heavyimpactingtomechanicalequipment,hardtostart;Thisliquidresistorcanbestart-upsmoothlyunderlowstartingcurrent,lowpowervoltage.
Ⅲ.Maintechnicalparameters
1.Powerofcontrolledmotor:
50~3000KW;
2.Currentofrotor(orstator)ofcontrolledmotor:
200~2000A;
3.Voltageofrotor(orstator)ofcontrolledmotor:
200~2200V;
4.Startingtime:
20S,25S,30S;
5.Timesofcontinuousstart-up:
6~8;
6.Normalworkingtemperatureforelectrolyte:
:
0~60℃;
7.Voltage&frequency:
380V60Hz;
8.Surroundtemperature:
0~50℃;
9.Heightabovesealevel:
≤3000m;
10.Airrelativehumidity(RⅡ):
≤85%;
11.Surroundmediumshouldnothavexplosiondanger,andgasanddusttocorrodemetal&destroyinsulation.
12.Noobviousvibrationininstallationsite.
Ⅳ.Operatingprinciple
Beforemotorstarted,aliquidresistorhasbeenseriesinthemotor’srotor(orstator)circuit,andmotorwillbestartedthroughadjustingcontinuouslytheresistancevalueofliquidresistor.Itscourse:
Valueofresistancewillbechangedwithmovingcranesupport,andwhenspeedofmotorisuptonormaloperatingspeed,resistorwillbeautomaticallycutoff,andnormalworkingswitchisautomaticallyclosed,somotorstartingprocessisend.Fordetails,Pleaseseetheprincipledrawing.
Ⅴ.Descriptionofelectrolyte
(1)Tomechanicalequipment,oncepowerofdraggingmotoriscurtained,ratedvoltage¤tofrotor(orstator)willbecurtainedwithit.Meanwhile,thevalueofresistancewillalsobecurtained.Thevalueofresistancecanbeestimatedbythefollowingmethods:
Romeansthevalueofeach-phaseintherotorcircuit.
U2emeansopenvoltageofrotor.
I2emeansratedcurrentintherotorcircuit(seeingnamecard)
Kmmeansratioofstart-uptorque,usuallythevalueis1.1~1.3(thatmeansstartingcurrentis1.1~1.3ofratedcurrent)
2.preparationofelectrolyte
(1)Movethemovableplatetothestartingposition,andputcleanwaterintothewatertank,about3/4ofspecifiedwaterlevel.
(2)Mixelectrolytepowderwithwater,thenpourequalquantitysolutionsintothreecisternstomakethesolutionconcentrationabout3%.
(3)Liftthemovableplateseveraltimes,afteruniformlymixthesolution,movethemoveableplateintheoriginalplace.MeasurethevalueofresistanceRbetweentwoplatesforeachphase.
(4)IfthevalueRisintherangeofthevalue(Ro),motorcanbestarted.Otherwise,wemustadjustitagain.WeshallincreasedensityofelectrolytepowderwhenthevalueRisverylarge.
3.Measuringliquidresistance
Takingapartthree-phasemaincircuitfromconnectionendandputtingthemovableplateofliquidresistoratthestart-upplace;Thenputtingin5A/50HzA.C.currentI(A)betweentwoelectrodes.measuringtheirvoltage.AccordingtoR=U/I,wecangetthevalueofresistance.(Seeingthedrawings)
Ⅵ.OperationandMaintenance
1.Beforeopeningthemachine,wecheckifpowersupplyofthree-phasefour-wireisnormal.
2.Whenpressingthetestbutton,weobserveifliftframe,limitswitch&contactorarenormal.
3.Weshallcheeklevelofliquidandtemperaturerise.Whenstart-uplampislight,wecanopenthemachine.
4.Afterusingitforlong-time,weshallregularlychecklevelofliquidelectrolytebox,driveconstitution&assemblepart.
5.Ifsomewrongwithcontrolcabinet,wemustimmediatelystopit.ThenwecheckSQ2,SQ1accordingtoprincipledrawing.
6.Changedtimeofelectrolyteisbetween4&5.Whencompoundingliquidresistanceorpouringwater,weshallavoidwatertosplash.Sothatinsulationisnotdestroyed.
Ⅶ.Purchasingspareparts&attentiontoorderinggoods
1.Providetherelatedparameterofmotor.
2.Sparepartsshallbeaccordingtoname,code&quantity,etcofinprincipledrawingtocontactdirectlywiththemanufacturerforpurchasing.
3.Youcanbuythisproductwithmainmachineorbuythisproductseparately.
VIII.Drawings
BYQ系列液体变阻器
使用说明书
江苏鹏飞集团
南通新业电子有限公司
目录
一、用途
二、特点
三、主要技术参数
四、工作原理
五、电解液概述
六、使用与维修
七、备件购置及订货须知
八、附图(3张)
一、用途
BYQ系列液体变阻器是为了适应大中型绕线式异步电动机的重载起动而研制的新型起动设备。
广泛应用于建材、冶金、矿山、石油、化工等行业中,是目前球磨机、提升机、破碎机,压缩机,风机、各类机泵等重载电机进行起动的理想设备。
二、BYQ系列液体变阻器的特点
1、在起动的大、中型电动机的转子(亦可在定子)回路中串入一液体电阻,且此电阻在电动机起动时自动投入并在预定的时间内无级均匀自动切除,从而使主电机平稳起动。
2、根据不同的起动要求调整电解液浓度,使其阻值随之变化,满足其要求。
3、因电液对温度的敏感性小,故能连续多次起动。
4、因不使用机械开关触点,故检修和维护工作量小。
5、克服了频敏变阻器,油浸变阻器及铸铁变阻器等老式变阻器进行重载荷电机起动对电网要求高,起动电流大,对机械设备冲击大,难以起动的弊端,具有起动电流小,电网电压较低的情况下亦能顺利起动。
三、主要技术参数
1、被控电机功率:
50~3000KW
2、被控电机转子(定子)电流:
200~2000A
3、被控电机转子(定子)电压:
200~2200V
4、起动时间:
20S,25S,30S
5、连续起动次数:
6~8次
6、电液正常工作温度:
0~60℃
7、供电电压:
380V60Hz
8、环境温度:
0~50℃
9、海拔高度:
≤3000m
10、大气相对湿度:
≤85%
11、周围介质应无爆炸危险,无足以腐蚀金属和破坏绝缘的气体和尘埃。
12、安装地点应无显著振动。
四、工作原理
电动机起动前,将其转子(定子)回路中串入一液体电阻,通过不断调整液体电阻值进行电机起动,其过程:
液体电阻的大小随其升降架移动而变化,电机以缓慢均匀的速度提速,达到正常运转速度时电阻自动切除,正常运行开关自动合上,起动过程结束。
具体电路,详见原理图。
五、电解液概述
1、对于机械设备而言,其拖动电机的功率确定后,定子和转子的额定电压、电流也就随之确定,起动柜的液体阻值也跟随确定。
电阻值的估算下面介绍方法:
其中:
R0为串入电机转子回路的每相电阻值;
U2e为转子开路电压;
I2e为转子回路额定电流(电机铭牌标有);
Km为起动转矩之比,一般取1.1~1.3(即启动电流为额定电流1.1~1.3倍)。
2、电解液的配制
①先将活动极板移到起动位置,并将清水冲入水箱,达到规定水位的3/4左右。
②将电液粉加水溶解后,等量注水三个水槽内,使溶液浓度在3%左右。
③将活动极板升降数次,溶液搅拌均匀后复位,测每相两极板间的电阻值R。
④若R值在R0范围内,即可起动,若R值未在R0范围内,则需要调整,R过大应增大电液粉浓度,R过小则应降低电液粉浓度。
3、液体电阻的测量
将三相主电路从接线端上拆下,使液体变阻器的活动极移到起动位置,给任意两极之间通过5A50Hz的交流电流I(A),并测量两电极之间的压降U(V),再由R=U/I,测算其阻值。
具体测量电路如下:
六、使用与维护
1、开机前应检查三相四线供电是否正常。
2、按试验按钮看变阻器升降架,行程开关,接触器工作是否正常。
3、检查液位及温升情况,待允许起动灯亮时,方可开机。
4、长期使用后定期检查液位,电解液箱是否有泄漏,传动机构是否灵活,部件有无卡阻现象。
5、控制柜遇有故障必须立即停机,应按原理图检查SQ1、SQ2、SQ3、SQ4、KA2是否正常工作。
过流,欠压继电器是否动作,待故障查明处理后方可开机。
6、电解液的更换时间一般4-5年,在配制液体电阻或充水时应防止水珠飞溅,以免破坏绝缘。
七、备件购置及订货须知
1、提供电机有关参数(U1e、U2e、I1e、I2e)。
2、购置备件应按原理图中的名称及设备编号、数量等,直接与制造厂家联系。
3、本产品可配套订货,也可单件订货。
八、附图