Q/GDW
JiangsuElectricPowerCompany
CompanyStandard
Q/GDW-10-316-2007
TechnicalSpecificationof
20kVAlternatingCurrentGasInsulatedMetalEnclosedSwitchgear
Released:
Sep20,2007
CONTENT
Foreword………………………………………………………………………………………….3
1Scope…………………………………………………………………………………….4
2Normativereferences…………………………………………………………………..4
3Environmentalconditions………………………………………………………………5
4Technicaldataandrequirement……………………………………………………..6
5Teststandardandrequirement……………………………………………………12
FOREWORD
Theobjectofthestandardistopromoteapplicationof20KVformediumvoltagenetworkinJiangsuElectricPowerCompany.TheexistingGB,DLandcompanystandardprovideverylittlerequirementof20KVelectricalequipment.ThisstandardiseditedInordertoassurethatthe20KVelectricalequipmentfulfillthenetworkrequirement.
Thisstandardisoneofthe9standardsfor10KVand20KVequipment,whicharelistedasbelow:
1.TechnicalSpecificationof220/110/20,220/20KVPowerTransformer
2.TechnicalSpecificationof110/20KVPowerTransformer
3.TechnicalSpecificationof20KVCircuitBreaker
4.TechnicalSpecificationof20KVDisconnector
5.TechnicalSpecificationof20KVACMetralEnclosedSwitchgear
6.TechnicalSpecificationof20KVACGISMetalEnclosedSwitchgear
7.TechnicalSpecificationof20KVCapacitorBanks
8.TechnicalSpecificationof20KVShuntreactors
9.TechnicalSpecificationof20KVEarthingResistor
ThestandardformatisinaccordancewithGB/T1.1andDL/T600-2001.
ThestandardisproposedandexplainedbyJiangsuPowerCompany,Production&TechnicalDepartment.
ThestandardiscoordinatedbyJiangsuPowerCompany,Production&TechnicalDepartment.
Thestandardwaseditedby:
-JiangsuPowerCompany,Production&TechnicalDepartment
-SuzhouPowerSupplyCompany
-JiangsuElectricTestInstituteCo.,Ltd
Editor:
TangJun,GaoShan,ChenShaobo
TechnicalSpecificationof
20KVACGISMetalEnclosedSwitchgear
1.Scope
Thistechnicalspecificationclassifiedgroupsoftechnicalrequirementincludingmaintechnicalparameters,functionaldesign,construction,characteristics,installationandtest,towhichthe20KVGISSwitchgearwith0.3Mpadesignpressurearesubjected.
Therequirementstipulatedinthespecificationisthelowesttechnicalrequirement,notcoveringalldetails,neithercoveringallnominativereferencesorstandards.Theequipmentmanufacturersshallprovidehighqualityproductsinaccordancetothisstandard,GBstandard,DLstandardandInternationalstandard.
Whereconflictexistsbetweenthisstandardandmanufacturer’sstandard,thehigherstandardshallapply.
Theneutralpointof20KVnetworkisearthedviasmallresistance.
2.NominativeReferences
Thefollowingreferenceddocumentsareindispensablefortheapplicationofthisdocument.Fordatedreferences,onlytheeditioncitedapplies.Forundatedreferences,thelatesteditionofthereferenceddocument(includinganyamendments)applies.
GB156
Standardvoltage
GB311.1
Insulationco-ordinationforhigh-voltagetransmissionanddistributionequipment
GB1408
Testmethodofpowerfrequencyelectricstrengthofsolidinsulatingmaterial
GB2900.1
ElectricalTerms,BasicTerms
GB3309
MechanicaltestofHVSwitchgearundernormaltemperature
GB3906
ACmetalenclosedswitchgearandcontrolgearforratedvoltageabove3.6kvanduptoandincluding40.5kv
GB7354
Measurementofpartialdischarge
GB/T11022
Commonspecificationforhigh-voltageswitchgearandcontrolgearstandards
SD/T318
TechnicalspecificationofHVSwitchgearinterlockingdevice
DL/T402
HValternating-currentCircuitBreaker
DL/T403
VacuumCircuitBreakerforratedvoltageabove12kvanduptoandincluding40.5kv
DL/T404
IndoorHVACSwitchgear
DL/T486
ACHVDisconnectorandEarthingSwitch
DL/T539
Condensationtestanddirtytest?
?
ofindoorACHVSwitchgearandcomponents
DL/T593
Commonspecificationforhigh-voltageswitchgearandcontrolgearstandards
DL/T615
SelectionofmainparameterofHigh-voltageACcircuitbreaker
DL/T617
Gasinsulatedmetalenclosedswitchgear
DL/T728
GISmetalenclosedswitchgear–orderingguidance
DL/T791
Indoorgasinsulatedswitchgear
IEC62271-102
HVACDisconnectorandearthingswitch
IEC62271-201
ACmetalenclosedswitchgearandcontrolgearforratedvoltageabove1kvanduptoandincluding38kv
IEC60480
VerificationofSF6gasinelectricalequipment
JiangsuPSB
2002No320
Guidelineofacceptancetestandpreventativetestofelectricalequipment
3.Environmentconditions
3.1
Altitude
1000m
3.2
Max.Ambienttemperature
+40°C
3.3
Min.Ambienttemperature
-25°C(isthismandatoryeverytime?
?
)
3.4
Max.Temperaturechange/day
25K
3.5
Indoorrelativehumidity
Averageperday95%
Averagepermonth90%
3.6
Resistancetoearth-quakes
(only8DAandNXPlusChasaninterntlreportLDnot)
Horizontal:
02g
Vertical:
0.1g
Vibration:
5cycles5withinterval2sSafetyfactor:
1.67
3.7
Ratedfrequency
50Hz
3.8
Installation
Indoor
4.Technicaldataandrequirement
4.1
TechnicalData
4.1.1
Type
20KVSF6insulatedmetalenclosedswitchgear
4.1.2
Ratedvoltage
24kV
4.1.3
Ratedfrequency
50Hz
4.1.4
Ratedcurrentpanel:
630A/1250A/2500A(8DA2500AOKNXPlusC200A)
Ratedcurrentbusbar
1600A/2000A/2500A
4.1.5
TemperatureRise:
Temperatureriseofmaincircuitunderratedcurrentandratedfrequency,shouldfulfillnotonlyGB/T11022standard,butalsothestandardrelevanttoeachindividualcomponents.Thetemperatureriseofaccessibleenclosureandcoversshouldnotexceed30K.?
?
?
?
4.1.6
Ratedshortcircuitbreakingcurrent
25KA/31.5KA(NXPlusConly25kA)
4.1.7
Ratedmakingcurrent(peak)
63KA/80KA(NXPlusConly63kA)
4.1.8
Ratedshorttimewithstandcurrent(4s)mandatory?
?
?
25KA/31.5KA
4.1.9
Ratedpeakwithstandcurrent
63KA/80KA
4.1.10
Insulationlevel
a)Powerfrequencywithstandvoltage(1min)
Phasetoearth:
50(65)KV
Isolatingdistance:
64(79)kV
ValuesinbracketsifneutralpointnotearthedmostsituationinChina
b)Lightningimpulsewithstandvoltage(1.2/50s,peak)
Phasetoearth:
95(125)KV
Opengap:
110(145)kV
c)creepagedistance
Pureporcelain18mm/kV
Epoxy20mm/kV
4.1.11
Auxiliaryvoltage
Auxiliaryvoltage:
AC/DC220V
Open/CloseSolenoid:
DC220V
4.2
CircuitBreaker
4.2.1
Type
VacuumorSF6
4.2.2
RatedVoltage
24KV
4.2.3
RatedFrequency
50Hz
4.2.4
RatedCurrent
630A/1250A/2500A
4.2.5
Ratedshortcircuitbreakingcurrent
25KA/31.5KA
4.2.6
Ratedmakingcurrent(peak)
63KA/80KA
4.2.7
Ratedshorttimewithstandcurrent(4s)
25KA/31.5KA
4.2.8
Ratedpeakwithstandcurrent
63KA/80KA
4.2.9
Insulationlevel
Sameas4.1.10
4.2.10
Operatingauxiliarypower
Motor:
AC220V
Open/CloseSolenoid:
DC220V
4.2.11
Installation
Refertoscopeofsupply
4.2.12
Ratedoperatingcycle:
MainincomerandBussection:
Outgoing:
0–180s–CO–180s–CO
0–0.3s–CO–180s–CO
4.2.13
Electricalandmechanicalendurance
Ratedelectricalendurancebreakingshortcircuitcurrent
30times(20timesfor31.5KA)
Ratedelectricalendurancebreakingnormalcurrent
10000times
Mechanicalendurance
>10000times
4.2.14
Ratedcapacitorbanksbreakingcurrent
400(630)A(whatareSIEMENSvalue)
4.2.15
Ratedsmallinductivebreakingcurrent
Over-voltagefactorandchoppingcurrentshouldbeprovidedbymanufacturers
4.2.16
Freeauxiliarycontactforenduser
10NO+10NC
4.2.17
VacuumInterrupter
Servicelife:
20years
Ceramicenclosure
Vacuum1.33x10-3Pa
(translationtobecheckedlaterwithVI)
4.2.18
Operatingcountersshouldbeequippedwithallcircuitbreakers.Thecountershouldcorrect,reliable,longendurance,clearindication,installedatthefrontsideofthepanel,visibleduringoperation.
4.3
Three-positiondisconnector
4.3.1
Mechanicalendurance:
2000timeswithoutmaintenance(mandatory)Ch
4.3.2
Inordertoisolatingandearthing,3-posdisconnectorshouldbeinstalled,withOn/Off/Earthpositions.Disconnectorshallbeinstalledinbetweenbusbarandcircuitbreaker.Thefixedcontactisonthebusbar.(notvalidforthe2008version)
4.3.3
Threephasesofdisconnectorsshouldbesimultaneouslyoperatedbyoneoperatingmechanism.Theratedtechnicaldatafulfilsitem4.3.1
4.3.4
Reliablepositionindicationwithremotesignallingshouldbeprovidedinordertobeeasilyinspectedbytheoperators.Mal-ON/OFFofdisconnectorduetomechanicalstress(i.g.causedbyshortcircuit)duringoperationduetoshouldbeavoided.Disconnectorshallbeabletobreaksmallcurrent(i.g.circuitbreakerchargingcurrent).Instantaneousovervoltageshouldnotoccuratcontrolcircuitorexternalenclosureduringoperation.
4.3.5
Interlockingbetween3-posdisconnectorandcircuitbreakershouldbeprovided.
4.3.6
Operatingmechanismshouldbeheat-proof,frigid-proof,dust-proof,moisture-proof,rust-proof.
4.3.7
Freeauxiliarycontactforbuyershouldbeatlease6NO+6NC.ThecontactshouldbeabletobreakDC220V,5A.
4.4
CurrentTransformer
4.4.1
Type:
CastResin
4.4.2
RatioandAccuracy:
refertoscopeofsupply
4.4.3
Zero-sequenceCTshouldbetwo-halftypesandfastsaturated.Tightandstableinstallation,easyformaintenanceandreplacement.
4.4.4
Otherrequirement:
a)primaryterminalofcurrenttransformerinsidepanelshouldbecopper?
?
?
typeterminals.ScrewtypeterminalisNOTallowed.
b)Shorttimewithstandcurrentrequirementisthesameasforcircuitbreaker.
c)Currenttransformershallbefitforalltypeofoperationmod