Section 23 73 00INDOOR CENTRALSTATION AIRHANDLING UNITS.docx

《Section 23 73 00INDOOR CENTRALSTATION AIRHANDLING UNITS.docx》由会员分享,可在线阅读,更多相关《Section 23 73 00INDOOR CENTRALSTATION AIRHANDLING UNITS.docx(20页珍藏版)》请在冰豆网上搜索。

Section 23 73 00INDOOR CENTRALSTATION AIRHANDLING UNITS.docx

Section237300INDOORCENTRALSTATIONAIRHANDLINGUNITS

SECTION237300

INDOORCENTRAL-STATIONAIR-HANDLINGUNITS

SPECWRITERNOTES:

1.Deletebetween////ifnotapplicabletoproject.Alsodeleteanyotheritemorparagraphnotapplicableinthesectionandrenumbertheparagraphs.

2.Referencestopressureinthissectionaregagepressureunlessotherwisenoted.

PART1GENERAL

1.1DESCRIPTION

A.Airhandlingunitsincludingintegralcomponentsspecifiedherein.

B.Definitions:

AirHandlingUnit(AHU):

Afactoryfabricatedandtestedassemblyofmodularsectionsconsistingof//housed-centrifugalfanwithV-beltdrive////singleormultipleplenumfanswithdirect-drive//,coils,filters,andothernecessaryequipmenttoperformoneormoreofthefollowingfunctionsofcirculating,cleaning,heating,cooling,humidifying,dehumidifying,andmixingofair.Designcapacitiesofunitsshallbeasscheduledonthedrawings.

1.2RELATEDWORK

//A.Seismicrestraintsforequipment:

Section130541,SEISMICRESTRAINTREQUIREMENTSFORNON-STRUCTURALCOMPONENTS.//

B.Generalmechanicalrequirementsanditems,whicharecommontomorethanonesectionofDivision23:

Section230511,COMMONWORKRESULTSFORHVACANDSTEAMGENERATION.

C.Soundandvibrationrequirements:

Section230541,NOISEANDVIBRATIONCONTROLFORHVACPIPINGANDEQUIPMENT.

D.Pipingandductinsulation:

Section230711,HVAC,PLUMBING,ANDBOILERPLANTINSULATION.

E.Pipingandvalves:

Section232113/232213,HYDRONICPIPING/STEAMANDCONDENSATEHEATINGPIPING.

F.Heatingandcoolingcoilsandpressurerequirements:

Section238216,AIRCOILS.

G.Returnandexhaustfans:

Section233400,HVACFANS.

H.Requirementsforflexibleductconnectors,soundattenuatorsandsoundabsorbingductlining,andairleakage:

Section233100,HVACDUCTSandCASINGS.

I.Airfiltersandfilters'efficiency:

Section234000,HVACAIRCLEANINGDEVICES.

J.HVACcontrols:

Section230923,DIRECT-DIGITALCONTROLSYSTEMFORHVAC.

K.Testing,adjustingandbalancingofairandwaterflows:

Section230593,TESTING,ADJUSTING,ANDBALANCINGFORHVAC.

L.Typesofmotors:

Section230512,GENERALMOTORREQUIREMENTSFORHVACANDSTEAMGENERATIONEQUIPMENT.

M.Typesofmotorstarters:

Section262911,LOW-VOLTAGEMOTORSTARTERS.

N.GeneralCommissioning:

Section019100,GENERALCOMMISSIONINGREQUIREMENTS

O.HVACCommissioning:

Section230800,COMMISSIONINGOFHVACSYSTEMS

1.3QUALITYASSURANCE

A.RefertoArticle,QualityAssurance,inSection230511,COMMONWORKRESULTSFORHVACANDSTEAMGENERATION.

B.AirHandlingUnitsCertification

1.AirHandlingUnitswithHousedCentrifugalFans:

TheairhandlingunitsshallbecertifiedinaccordancewithAHRI430andtested/ratedinaccordancewithAHRI260.

2.AirHandlingUnitswithPlenumFans:

a.AirHandlingUnitswithasinglePlenumFanshallbecertifiedinaccordancewithAHRI430andtested/ratedinaccordancewithAHRI260.

b.AirhandlingUnitswithMultipleFansinanArrayshallbetestedandratedinaccordancewithAHRI430andAHRI260.

C.Heating,Cooling,andAirHandlingCapacityandPerformanceStandards:

AHRI430,AHRI410,ASHRAE51,andAMCA210.

D.PerformanceCriteria:

1.ThefanBHPshallincludeallsystemeffectsforallfansandv-beltdrivelossesforhousedcentrifugalfans.

2.Thefanmotorshallbeselectedwithintheratednameplatecapacity,withoutrelyinguponNEMAStandardServiceFactor.

3.Selectthefanoperatingpointasfollows:

a.ForwardCurveandAxialFlowFans:

Righthandsideofpeakpressurepoint.

b.AirFoil,BackwardInclined,orTubularFansIncludingPlenumFans:

Atornearthepeakstaticefficiencybutatanappropriatedistancefromthestallline.

4.OperatingLimits:

AMCA99andManufacturer’sRecommendations.

E.Unitsshallbefactory-fabricated,assembled,andtestedbyamanufacturer,inbusinessofmanufacturingsimilarair-handlingunitsforatleastfive(5)years.

SPECWRITERSNOTES:

Forlargerprojectsinvolvingmorethanfiveairhandlingunits,theA/EshallselectafewtypicalAHUs,indifferentconfigurations,foraninitialsubmission.Thesuggesteddifferentconfigurationsare:

1.100percentoutsideairAHUswithorwithoutheatrecoverycoils.

2.Re-circulatingtypeofvariableairvolumeAHUswithminimumoutsideairandeconomizercyclefeatures.Theremainingsubmissionshallbereceivedonlyaftertheinitialsubmissionisapprovedwithsatisfactoryresolutionofallcommentsmadeduringthereviewandapprovalprocess.

1.4.SUBMITTALS:

A.Thecontractorshall,inaccordancewithSection013323,SHOPDRAWINGS,PRODUCTDATA,ANDSAMPLES,furnishacompletesubmissionforallairhandlingunitscoveredintheproject.Thesubmissionshallincludeallinformationlistedbelow.Partialandincompletesubmissionsshallberejectedwithoutreviews.

B.Manufacturer'sLiteratureandData:

1.SubmittalsforAHUsshallincludefans,drives,motors,coils,//humidifiers,//soundattenuators//,mixingboxwithoutside/returnairdampers,filterhousings,//blendersections//,andallotherrelatedaccessories.Thecontractorshallprovidecustomdrawingsshowingtotalairhandlingunitassemblyincludingdimensions,operatingweight,accesssections,//diffusionplates//,flexibleconnections,doorswings,controlspenetrations,electricaldisconnect,lights,duplexreceptacles,switches,wiring,utilityconnectionpoints,unitsupportsystem,vibrationisolators,drainpan,pressuredropsthrougheachcomponent(filter,coiletc).

2.Submittaldrawingsofsectionorcomponentonlywillnotbeacceptable.Contractorshallalsosubmitperformancedataincludingperformancetestresults,charts,curvesorcertifiedcomputerselectiondata;datasheets;fabricationandinsulationdetails.Iftheunitcannotbeshippedinonepiece,thecontractorshallindicatethenumberofpiecesthateachunitwillhavetobebrokenintotomeetshippingandjobsiteriggingrequirements.ThisdatashallbesubmittedinhardcopiesandinelectronicversioncompatibletoAutoCADversionusedbytheVAatthetimeofsubmission.

3.SubmitsoundpowerlevelsineachoctavebandfortheinletanddischargeofthefanandatentranceanddischargeofAHUsatscheduledconditions.InabsenceofsoundpowerratingsrefertoSection230541,NOISEANDVIBRATIONCONTROLFORHVACPIPINGANDEQUIPMENT.

4.ProvidefancurvesshowingLiters/Second(cubicfeetperminute),staticpressure,efficiency,andhorsepowerfordesignpointofoperationandatmaximumdesignLiters/Second(cubicfeetperminute).

5.Submittotalfanstaticpressure,externalstaticpressure,forAHUincludingtotal,inletanddischargepressures,anditemizedspecifiedinternallossesandunspecifiedinternallosses.Refertoairhandlingunitscheduleondrawings.

C.MaintenanceandoperatingmanualsinaccordancewithSection010000,GENERALREQUIREMENTS.Includeinstructionsforlubrication,filterreplacement,motoranddrivereplacement,sparepartlists,andwiringdiagrams.

D.Submitwrittentestprocedurestwoweekspriortofactorytesting.Submitwrittenresultsoffactorytestsforapprovalpriortoshipping.

E.Submitshippinginformationthatclearlyindicateshowtheunitswillbeshippedincompliancewiththedescriptionsbelow.

1.Unitsshallbeshippedinone

(1)piecewherepossibleandinshrinkwrappingtoprotecttheunitfromdirt,moistureand/orroadsalt.

2.Ifnotshippedinone

(1)piece,providemanufacturerapprovedshippingsplitswhererequiredforinstallationortomeetshippingand/orjobsiteriggingrequirementsinmodularsections.Indicateclearlythattheshippingsplitsshowninthesubmittalshavebeenverifiedtoaccommodatetheconstructionconstraintsforriggingasrequiredtocompleteinstallationandremovalofanysectionforreplacementthroughavailableaccesswithoutadverselyaffectingothersections.

3.Ifshippingsplitsareprovided,eachcomponentshallbeindividuallyshrinkwrappedtoprotecttheunitandallnecessaryhardware(e.g.bolts,gasketsetc.)willbeincludedtoassembleunitonsite(seesection2.1.A4).

4.Liftinglugswillbeprovidedtofacilitateriggingonshippingsplitsandjoiningofsegments.Iftheunitcannotbeshippedinonepiece,thecontractorshallindicatethenumberofpiecesthateachunitwillhavetobebrokenintotomeetshippingandjobsiteriggingrequirements.

1.5APPLICABLEPUBLICATIONS

A.Thepublicationslistedbelowformapartofthisspecificationtotheextentreferenced.Thepublicationsarereferencedinthetextbythebasicdesignationonly.

B.AirConditioning,Heating,andRefrigerationInstitute(AHRI)/(ARI):

41001StandardforForced-CirculationAir-HeatingandAir-CoolingCoils

43009CentralStationAirHandlingUnits

C.AirMovementandControlAssociationInternational,Inc.(AMCA):

21007LaboratoryMethodsofTestingFansforRating

D.AmericanSocietyofHeating,RefrigeratingandAir-conditioningEngineers,Inc.(ASHRAE):

170-2008VentilationofHealthCareFacilities

E.AmericanSocietyforTestingandMaterials(ASTM):

ASTMB117-07aStandardPracticeforOperatingSaltSpray(Fog)Apparatus

ASTMD165408StandardTestMethodforEvaluationofPaintedorCoatedSpecimensSubjectedtoCorrosiveEnvironments

ASTMD173508StandardPracticeforTestingWaterResistanceofCoatingsUsingWaterFogApparatus

ASTMD335908StandardTestMethodsforMeasuringAdhesionbyTapeTest

F.MilitarySpecifications(Mil.Spec.):

MIL-P-21035B-2003Paint,HighZincDustContent,GalvanizingRepair(Metric)

G.NationalFireProtectionAssociation(NFPA):

NFPA90AStandardforInstallationofAirConditioningandVentilatingSystems,2009

H.EnergyPolicyActof2005(P.L.109-