AS NZS 3000 5Word文档下载推荐.docx

上传人:b****5 文档编号:18758434 上传时间:2023-01-01 格式:DOCX 页数:27 大小:34.65KB
下载 相关 举报
AS NZS 3000 5Word文档下载推荐.docx_第1页
第1页 / 共27页
AS NZS 3000 5Word文档下载推荐.docx_第2页
第2页 / 共27页
AS NZS 3000 5Word文档下载推荐.docx_第3页
第3页 / 共27页
AS NZS 3000 5Word文档下载推荐.docx_第4页
第4页 / 共27页
AS NZS 3000 5Word文档下载推荐.docx_第5页
第5页 / 共27页
点击查看更多>>
下载资源
资源描述

AS NZS 3000 5Word文档下载推荐.docx

《AS NZS 3000 5Word文档下载推荐.docx》由会员分享,可在线阅读,更多相关《AS NZS 3000 5Word文档下载推荐.docx(27页珍藏版)》请在冰豆网上搜索。

AS NZS 3000 5Word文档下载推荐.docx

Earthingarrangementsforprotectivepurposesshallbecomprisedofprotectiveearthingconductorsusedwithovercurrentprotectivedevicesprovided,intheactive,forprotectionagainstindirectcontactandovercurrent.

NOTE:

Theprotectiveearthingconductorsshouldbeincorporatedinthesamewiringenclosureastheassociatedactiveconductorsorinthenearvicinity.

5.2.3Forfunctionalpurposes出于功能目的

Earthingarrangementsforfunctionalpurposesshallbecomprisedoffunctionalearthingconductorsprovidedtoensurecorrectoperationofelectricalequipmentortopermitreliableandproperfunctioningofelectricalinstallations.

Wherea‘cleanearth’isspecifiedforaparticularitemofelectricalequipment,themanufactureroftheelectricalequipmentshouldbeconsultedinordertoconfirmthenecessaryarrangements.

5.2.4Forcombinedprotectiveandfunctionalpurposes

Whereearthingforcombinedprotectiveandfunctionalpurposesisrequired,therequirementsforprotectivepurposes(seeClause5.2.2)shallprevail.

5.2.5Selectionandinstallation选择和安装

Theselectionandinstallationoftheequipmentoftheearthingarrangementsshallbesuchthat—

(a)thevalueofearthingresistanceisinaccordancewiththeprotectiveandfunctionalrequirementsoftheelectricalinstallationandexpectedtobecontinuouslyeffective;

and

 

(b)earth-faultcurrentsandearth-leakagecurrentscanbecarriedwithoutdanger,particularlyfromthermal,thermomechanicalandelectromechanicalstresses;

(c)itisadequatelyrobustorhasadditionalmechanicalprotectionappropriatetotheassessedconditionsofexternalinfluenceinaccordancewithClause3.3.

5.2.6Precautions防范措施

Precautionsshallbetakenagainsttheriskofdamagetotheearthingarrangementandothermetallicpartsoftheelectricalinstallationthroughelectrolysisorgalvanicaction.

5.3MULTIPLEEARTHEDNEUTRAL(MEN)SYSTEM多重接地中线系统

ThesystemofearthingthatshallbedeemedtosatisfytherequirementsofClause5.1isthemultipleearthedneutral(MEN)systeminwhichthepartsofanelectricalinstallationrequired,underthisStandard,tobeearthedareconnectedtothegeneralmassofearthand,inaddition,areconnectedwithintheelectricalinstallationtotheneutralconductorofthesupplysystem.

NOTES:

1ExamplesoftheMENsystemofearthingareshowninFigures5.1and5.2.

2Alternativeearthingsystemsthatsatisfythegeneralsafetyandfunctionalrequirementsmaybeused.

5.4EARTHINGREQUIREMENTS接地要求

5.4.1General概述

Theexposedconductivepartsofelectricalequipmentshallbeearthedwheretheelectricalequipmentis—

(a)installedormightoperateinanearthedsituation;

or

(b)notinstalledinanearthedsituationbutanyexposedconductivepartoftheelectricalequipmentiselectricallycontinuouswithconductivematerialwhichislocatedinanearthedsituation.

Thetermexposedconductivepartdoesnotapplytothefollowing:

(a)Conductivepartswithinanenclosurewherethepartscannotbetouchedunlessakeyoratoolisrequiredtoremovethecoversoftheenclosure.

(b)Conductivepartswithinelectricalequipmentwherethepartscannotbetouchedinnormaluseandmovementoftheelectricalequipmentduetoitsconfigurationandsize,e.g.sometypesofwashingmachines.

(c)Conductivepartswhichareseparatedfromlivepartsby—

(i)doubleinsulation;

(ii)otherconductivepartswhichareearthed.

(d)Conductivepartswhichareintheformofnameplates,screwheads,coversandsimilarattachmentsthatcannotbecomeliveintheeventoffailureofinsulationofliveparts,duetothemannerinwhichtheyaresupportedandfixed.

Onlysinglephaseconnectionsshownforclarity.

FIGURE5.1MULTIPLEEARTHEDNEUTRAL(MEN)SYSTEMOFEARTHING—MENLINKATCUSTOMER’SMAINSWITCHBOARD

DistributionasFigure5.1

FIGURE5.2MULTIPLEEARTHEDNEUTRAL(MEN)SYSTEMOFEARTHING—MENLINKREMOTEFROMCUSTOMER’SMAINSWITCHBOARD

5.4.2Connectionofelectricalequipmenttoearth电气设备接地连接

Electricalequipmentrequiredtobeearthedshallbearrangedforconnectionto—

(a)protectiveearthingconductorsintheformofcables,cords,busbarsorsimilarformsofcurrent-carryingmaterial;

(b)anotherearthingmediumsuchasmetallicpartsofcables,wiringenclosures,switchboardframeworkorthelike.

5.4.3Resistanceoftheearthingsystem接地系统电阻

Theresistancefromanypointontheelectricalinstallationrequiredtobeearthedtothepointwherethemainearthingconductorisconnectedtotheneutralconductorofthesupplysystemshallbelowenoughtopermitthepassageofcurrentnecessarytooperatethecircuitprotectivedevices.

Theresistanceofthemainearthingconductorshallbenotmorethan0.5?

.

AsdescribedinAppendixB,themaximumresistanceoftheprotectiveearthingconductorassociatedwithanyparticularcircuitdependsonthetypeandratingoftheprotectivedeviceandtheimpedanceoftheliveconductorsthatcomprisethecircuit.

5.5EARTHINGCONDUCTORS接地导线

5.5.1Size尺寸

5.5.1.1General概述

ThesizeofanearthingconductorshallbesuchthatitmeetstherequirementsofClause5.2.

Guidanceonthedeterminationofthemaximumlengthofacircuit,inrelationtothecharacteristicsofprotectivedevicesandthesizeoftheprotectiveearthingconductor,isprovidedinAppendixB.

5.5.1.2Minimumsize最小尺寸

Theminimumsizeofanearthingconductorshallbedeterminedasfollows:

(a)GeneralExceptwherevariedbyItems(b)to(f),theminimumsizeofanycopperearthingconductorrequiredfortheprotectionofanyportionofanelectricalinstallationshallbedeterminedfromTable5.1

inrelationtothecross-sectionalareaofthelargestactiveconductorsupplyingtheportionoftheelectricalinstallationtobeprotected.

ThedeterminationmethodusingTable5.1mayalsobeappliedinthefollowingsituations:

(i)Wheretheactiveconductorsinamultiphasecircuitcomprisedifferentsizeconductors,theearthingconductorshallbedeterminedinrelationtothecross-sectionalareaofthelargestactiveconductortobeprotected.

(ii)Wheretheactiveconductorcomprisesanumberofconductors,connectedinparallel,theearthingconductorshallbedeterminedinrelationtothesummationofthecross-sectionalareasoftheindividualconductorsformingthelargestactiveconductortobeprotected.

Wherethesummationofcross-sectionalareasdoesnotcorrespondexactlywiththenominalsizeoftheactiveconductorgiveninTable5.1,theconductorshallbedeterminedinrelationtothenearestlargersizeofactiveconductor.

TABLE5.1MINIMUMCOPPEREARTHINGCONDUCTORSIZE

Nominalsizeofactiveconductor

Nominalsizeofcopperearthingconductor

Withcopperactiveconductors

Withaluminiumactiveconductors

1

1.5

2.5

1*

1.5*

-

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

500

630

*Theseearthingconductorsmaybeusedonlywhereincorpratedinamulticorecableorflexiblecord,otherthanalifttravelingcable,inaccordancewithClause5.5.1.2(e)(ii)and(iii).

(b)CalculationAsanalternativetothedeterminationmethoddescribedinItem(a),theminimumsizeofanearthingconductorrequiredmaybedeterminedbycalculationprovidedthataccurateinformationisobtainedonthevalueoftheprospectivefaultcurrent,thedisconnectingtimeoftheprotectivedevice,andconductorandinsulationcharacteristics.

AsuitableequationforthecalculationofconductorsizesunderfaultcurrentconditionsisgiveninClause5.6.7.4.3.

(c)MainearthingconductorIngeneral,theminimumsizeofthemainearthingconductorshallbedeterminedinaccordancewithItem(a)andTable5.1inrelationtothecross-sectionalareaofthelargest

activeconductoroftheconsumersmains.

Thesizeofthemainearthingconductorneednotbedeterminedinrelationtothesizeofthelargestactiveconductoroftheconsumersmainsunderthefollowingconditions:

(i)Wheredoubleinsulationismaintainedbetweenthepointofsupplyandtheloadterminalsoftheprotectivedevicesonthesubmainsandfinalsubcircuitsoutgoingfromthemainswitchboard,theminimumsizeofthemainearthingconductormaybedeterminedinrelationtothecross-sectionalareaofthelargestactiveconductorofthelargestoutgoingsubmainorfinalsubcircuit.

(ii)Wherethecross-sectionalareaoftheconsumersmainsislargerthanthatrequiredtocarrythemaximumdemandoftheinstallationbecauseofvoltage-droplimitations,theminimumsizeofthemainearthingconductormaybedeterminedinrelationtothecross-sectionalareaoftheminimumcablesizerequiredtocarrythemaximumdemand.

Inanycase,thecross-sectionalareaofacoppermainearthingconductorshallbenotlessthan4mm2.

(d)AerialearthingconductorTheminimumsizeofanearthingconductorinstalledasanaerialconductorshallbedeterminedinaccordancewithItem(a)andTable5.1providedthatthecross-sectionalareaoftheearthingconductorsodeterminedshallbenotlessthanthesizespecifiedinCla

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 外语学习 > 法语学习

copyright@ 2008-2022 冰豆网网站版权所有

经营许可证编号:鄂ICP备2022015515号-1